Minor Franchise Permit: MFP20000149
IVR Number: 20000149
Permit Informaon
Permit Name:Puget Sound Energy - Electric
Address/Locaon :01/07/2020Application Date:3628600010Parcel Number:1201 N 37TH ST
Permit Type:01/16/2020Issue Date:Franchise
Permit Work Class:01/15/2021Expiration Date:Minor Utility
Job Number:105086571Franchise Type:Electric
Description:At P01 crew to replace 15KVA with new 37.5KVA. Dig 2 work pits and bore under N 37th St. Install (1) run 350 UG TPX
at P01. Pothole all existing utilities. Restoration per City of Renton standards.
APPROVED WITH COMMENTS OR REDLINES
Contacts
Name Address PhoneTypeBilling
Corrie Rydberg
Puget Sound Energy
6905 S 228TH St
KENT, WA 98032
C: (425) 892-0416Applicant
Marita Bond
Puget Sound Energy Billing
6905 S 228 St
Kent, WA 98032
B: (253) 395-6346Contact
Vicki Henson
Potelco Inc
8001 212th St S
Kent, WA 98032
B: (253) 863-0484Contractor
Business License Number: 5109Electrical Contractor: POTELI*344O4
Construction Contractor: POTELI*227PL
CAMPBELL JULIE E+KIMIAI ALI 1201 N 37TH ST
RENTON , WA 98056
Owner
Marita Bond
Puget Sound Energy Billing
6905 S 228 St
Kent, WA 98032
B: (253) 395-6346Specialized
Billing
X
General Condions & Signature
Permission is hereby given for the work described on this permit according to the conditions hereon and according to the
approved plans and specifications pertaining thereto, subject to compliance with the Ordinance of the City of Renton.
This permit and plans must be posted at the job site at all times.
I hereby certify that no work is to be done except as described above and in approved plans, and that work is to conform to
Renton Trench Restoration and Street Overlay Requirements.
Call 425.430.7203 or go to: https://permitting.rentonwa.gov one working day in advance to schedule an inspections and for ANY
work in the Right of Way.
Call 8 1 1 to locate underground utilities at least two full business days prior to any excavation.
In accordance with RCW 19.122.033(4) the permit holder is required to contact (Williams Northwest Pipeline at 425.868.1010)
(Olympic Pipeline at 206.510.0575) (Puget Sound Energy at 425.375.3397) to request a consultation with the transmission
pipeline company prior to performing any construction or excavation activities. This requirement to consult with the
transmission pipeline company is in addition to the requirement to Call before You Dig as required in RCW 19.122.
(Date)(Signature)
Page 1 of 1THIS PERMIT AND PLANS MUST BE POSTED AT THE JOB SITE AT ALL TIMES
DEPARTMENT OF COMMUNITY
AND ECONOMIC DEVELOPMENT
Page 1 of 1 | Published: 1/2/2019
Planning Division | 1055 South Grady Way, 6th Floor | Renton, WA 98057 | 425-430-7200
Email: franchisepermits@rentonwa.gov Website: rentonwa.gov
FRANCHISE PERMIT APPLICATION
Published: 1/2/2019
TO THE APPLICANT: Submit an electronic copy of the plans with the Franchise Permit Application and the Site
Specific Traffic Control Application to franchisepermits@rentonwa.gov. Permit cost is $630.00. Inspection fee
for trenching more than 60 lineal feet or installation of 6 or more poles will be billed at $60.00 per hour.
Franchise Agency:
Franchise Job Number: Phone:
Contact Name: Email:
Job Site Address: Project Name:
Description of Work:
Please check all that apply:
տ New Construction տ Repair/Relocate տ Underground տ Overhead տ Sidewalk տ Street
տ Open Trench տ Bore # of feet:
Contractor Name: Phone:
State Contractors License #: City of Renton Business License #:
“I certify that I am the owner or applicant’s authorized agent and do hereby agree to abide to the terms and conditions set forth
under this permit and shall comply with the City of Renton’s Trench Restoration and Street Overlay Requirements. ”
Signature Date
INSPECTIONS SHALL BE REQUESTED 24 HOURS PRIOR TO COMMENCEMENT OF ALL WORK BY CALLING THE
INSPECTION LINE AT 425-430-7203 OR BY GOING TO MYBUILDINGPERMIT.COM
Jobs are required to be called in for job start, re-inspection and project final. Re-inspection fees are billed at
$125/hour. All Pre-Construction meetings shall be scheduled at a maximum of 14 days prior to the job start date.
Plan Review/Development Engineering Date Approved as submitted
Pre-Construction Meeting required
Site Construction Inspector Date Approved with comments or redlines
Camera inspection of utilities required
Development Engineering Manager Date
WƵŐĞƚ^ŽƵŶĚŶĞƌŐLJͲůĞĐƚƌŝĐ
ϭϬϱϬϴϲϱϳϭ
ŽƌƌŝĞZLJĚďĞƌŐĐŽƌƌŝĞ͘ƌLJĚďĞƌŐΛƉƐĞ͘ĐŽŵ
ϭϮϬϭEϯϳd,^d
dWϬϭ;ϯϭϵϰϰϵͲϭϲϲϭϵϬͿZtdKZW>ϭϱ<st/d,Etϯϳ͘ϱ<sEh^dKDZdKysdtKZ<W/dϰΖyϰΖyϯΖ͘
h^dKDZdKysdϰΖyϲΖyϯΖKZW/ddE͘^/K&E͘ϯϳd,^dEKZhEZϯϳd,^d͘WWZKyϲϬΖ͘Ztt/>>/E^d>>;ϭͿZhEϯϱϬh'
dWydWϬϭ;ϯϭϵϰϰϵͲϭϲϲϭϵϬͿ͘W>^^dd,
ϱΖyϭϮΗyϯΖ
WKd>K͕/E͘ϮϱϯͲϮϯϰͲϲϰϭϬ
WKd>/ηϮϮϳW>>ϬϬϱϭϬϵ
ϭͬϳͬϮϬϮϬCorrie Rydberg Digitally signed by Corrie Rydberg
Date: 2020.01.07 10:07:40 -08'00'
MFP20000149
POTHOLE ALL EXISTING UTILITIES
RESTORATION PER CITY OF RENTON STANDARDS
Scott Warlick 1/13/2020
Holly Powers 1/16/2020
DEPARTMENT OF PUBLIC WORKS
Note: The Applicant is responsible for compliance with all codes and regulations, whether or not described in this document.
Page 1 of 2 | Published: 1ϭ/Ϯϱ/2019
Transportation Division | 1055 South Grady Way, 5th Floor | Renton, WA 98057 | 425-430-7380
Website: rentonwa.gov
TRAFFIC CONTROL PLAN (TCP) APPLICATION
Published: 1ϭ/Ϯϱ/2019
TRAFFIC CONTROL PLAN (TCP) MUST BE SUBMITTED TO PUBLIC WORKS TRANSPORTATION DIVISION
FOR REVIEW/APPROVAL NO LATER THAN FIVE (5) WORKING DAYS BEFORE THE DATE OF WORK.
The City of Renton requires any contractor, firm, corporation, or other public/private agency to prepare a TCP and
obtain City of Renton's approval of that plan when construction, repair, or maintenance work is to be conducted
within the city's right-of-way.
TO THE APPLICANT: Submit the TCP application form and required submittal documents to
TCP@rentonwa.gov with the subject line “TCP Application – [Project Name]” or the above address.
The following items, electronic copies preferred, are all required for submittal of the TCP Application:
1.܆ A copy of the Traffic Control Plan (TCP) Application form.
2.܆ A copy of the required TCP layout, preferred 11” X 17” paper size format, which shall:
܆ Include map(s) showing the location of the project and work area.
܆ Be legible lettering and clear, contrasting, symbols of viewing or printing.
܆ Must indicate street names, and north arrow and scale.
܆ All signs and detour routes shall conform to the MUTCD, WSDOT TCPs, and the Washington State
Traffic Control Flagger Certification handbook, by the Evergreen Safety Council.
܆ Types of plans required:
܆ Work hour plan – show all mobility impacts during construction hours.
܆ Non-work plan - show all mobility impacts after work hours when limited or no work is
happening in the right-of-way (ROW), if applicable.
܆ Changing construction phases – show construction sequence and each construction phase
change even if the traffic control is not modified, if applicable.
܆ Pedestrian access/detour plan, if applicable.
Project Name: ______________________________________________ Permit #: _____________________
Project Address: ____________________________________________________________________________
Work Date: From _____________ To _____________ Work Time: Start ______________ End ______________
Description of Work, Work Schedule, Equipment Used: _____________________________________________
___________________________________________________________________________________________
___________________________________________________________________________________________
Construction Company: ________________________________________ Phone/Cell: (_____) _____-________
Applicant Name: _________________________________ Email: ______________________________________
Business Address: _________________________________ City/State: __________________ Zip: __________
Approved By: _______________________________________________ Date: ________________________
Transportation Operations Engineering
ϭϮϬϭEϯϳd,^d
dddd
Eh^dKDZdKysdtKZ<W/dϰΖyϰΖyϯΖh^dKDZdKysdϰΖyϲΖyϯΖKZW/ddE͘^/K&E͘ϯϳd,^dEKZhEZϯϳd,^d͘
dWϬϭ;ϯϭϵϰϰϵͲϭϲϲϭϵϬͿZtdKZW>ϭϱ<st/d,Etϯϳ͘ϱ<s
WWZKyϲϬΖ͘Ztt/>>/E^d>>;ϭͿZhEϯϱϬh'dWydWϬϭ;ϯϭϵϰϰϵͲϭϲϲϭϵϬͿ͘W>^^dd,
WKd>K͕/E͘
&/E'KD&/E͘'KDΛW^͘KD
ϲϵϬϱ^ϮϮϴd,^d <Ed͕tϵϴϬϯϮ
MFP20000149
1/13/2020
Monday - Friday 8:00AM - 3:00PM
Scott Warlick C.E.D
Note: The Applicant is responsible for compliance with all codes and regulations, whether or not described in this document.
Page 2 of 2 | Published: 1ϭ/Ϯϱ/2019
APPLICANT AGREES TO ALL THE FOLLOWING:
x TCP must be approved prior to commencing the work, and all permit conditions shall be met.
x Existing pedestrian access shall be maintained. The work on pedestrian facilities shall be limited to one corner
at a time, with the least possible inconvenience or delay to pedestrians.
x Signage shall be used to warn motorcyclists/bicyclists of the potential hazards on any uneven surfaced or
slippery road conditions during work and non-work hours.
x The start of Work Time begins when any street or travel lane is fully/partially closed or impacts the follow of
traffic. This includes set up within the traveled way or immediately adjacent to the roadway.
x Emergency services (253-852-2121) shall be notified twenty-four (24) hours before any street or lane closures.
x Contractor or entity must call Renton School District (425-204-4455) or any public/private agency, including
public transit, to be affected by a temporary lane or road closure.
x TCP for all street and/or lane closures shall be implemented and performed in compliance with the Manual on
Uniform Traffic Control Devices (MUTCD) and/or State of Washington Department of Transportation (WSDOT)
and all traffic regulations of the City of Renton and Revised Code of Washington (RCW).
x Any lane or street closures not in conformance with the approved traffic control plan and/or without
notification of emergency services may result in receiving a citation for violation of RCW 47.36.200 Signs or
Flaggers at thoroughfare work sites and RCW 9A.36.050 Reckless Endangerment, and other applicable State
and City codes.
x Indemnify and hold harmless the City of Renton from any and all claims, actions, and judgments, including all
costs of defense and attorney’s fees incurred in defending against same, arising from and related to
implementation of the approved traffic control plans including claims arising from towing of private vehicles
and the acts of the Applicant’s agents and employees.
x The City of Renton shall be entitled, in its reasonable discretion, to settle claims prior to suit or judgment, and
in such event shall indemnify and hold harmless the City for any such claims paid, including the City’s
reasonable attorney’s fees and litigation costs incurred resulting from such claim.
x In the event any claim or suit is brought against the City within the scope of this Agreement, Applicant will pay
for legal counsel chosen by the City to defend against same.
x Flagger and sign placement are subject to revision by the City Inspector on site, if needed to address traffic or
pedestrian safety or travel.
x Total road closure lasting more than twenty-four (24) hours is subject to the approval by the City Council.
x Approved Temporary TCP must be at the work site during work hours.
x Complete assistance and accommodation shall be provided to all kinds of pedestrian traffic when sidewalk or
walkway is impeded to safely redirect pedestrians around a work zone.
x Any vehicle, equipment, barricade, or portable tow-away sign used within the work area must display a
company logo or any legally acceptable sign showing the company name, address, and telephone number at a
conspicuous place on the vehicle or equipment.
In the case of Temporary No Parking Zones, all the following apply in addition to previous:
x Contractor must complete form to show limits of Temporary No Parking Zone identifying barricade locations
for vacate parking or curb lane usage.
x Contractor must post notice of dates and time of Temporary No Parking Zone with at least two signs per block
seventy-two (72) hours in advance of effective date and time.
x The cover sheet of this TCP form must be attached to each Temporary No Parking Sign on the project site.
x Temporary traffic control devices must be removed immediately when work is done or no construction
activities are going on. If deemed abandoned, City crews will remove and store them at the City’s maintenance
shop (3555 NE 2nd Street; 425-430-7423).
_______________________________ _______________________________ _______________________
Applicant’s Signature Print Name Date
KZZ/ZzZ'ϭͬϳͬϮϬϮϬCorrie Rydberg Digitally signed by Corrie Rydberg
Date: 2020.01.07 10:08:02 -08'00'
1212N 37th STWELLS AVE N1212WELLS AVE N
111117171212P01STO
P
FLAGGERSTOP
FLAGGER N 37TH STONE LANEROADAHEADW20-4100'100'100'ROADWORKAHEADW20-1W20-7A100'ROADWORKAHEADW20-1ROADWORKAHEADW20-1
ONE LANEROADAHEAD W20-4X'100'X'ROADWORKAHEADW20-1W20-7A100'ROADWORKAHEADW20-1PARK AVE NPARK AVE N#1201FROMTOTOW AWAY AREAPHONE 888-9999INFRASOURCE
LLC
000
0000
000 NO PARKINGNO-PARKNO PARK SIGNAGE WILL BEPLACED ON ALL STREETS TOSURROUND WORK ZONERESIDENT(S) WILL BE INFORMEDOF POSSIBLE TEMPORARYDRIVEWAY CLOSUREPATH OF INSTALLATIONNCHANNELIZATIONDEVICE SPACINGMPH55/7035/4525/30TAPER403020TANGENT806040Job#1050865711201 N 37th ST, Renton WAOctober 13, 2017Sheet 1 of 2 ryan.honeysett@pse.com(425)457-5381PSEPUGETSOUNDENERGYNotes:1. All signs and spacing to conform to the MUTCDand City of Renton standards.2. All sidewalks, driveways, exits and egressesshall be completely clear unless otherwise indicated.3. Channelizing devices are 28" traffic cones.4. Sign size can be a minimum of 48" x 48" andshall not obstruct pedestrian access.5. Crew is required to leave a minimum of 11' fortraveling lane width.6. Alert affected residents and businesses.7. Work to take place between 9 a.m. and 4 p.m.TRENCH28" TRAFFIC CONELEGENDTRAFFIC FLOWSIGN LOCATIONFLAGGERSTOPWORK VEHICLE/FLASHING LIGHTSRIGHT OF WAYPuget Sound EnergyTraffic Control Supervisor:Ryan HoneysettCard No. 010760Card Exp. 06/30/2021ryan.honeysett@pse.com(425)457-5381MFP20000149
1212N 37th STWELLS AVE N1212WELLS AVE N
111117171212P01STOP
FLAGGERHH1 N 37TH STX'100'ROADWORKAHEADW20-1W20-7AONE LANEROAD
AHEAD W20-4100'100'100'ROADWORKAHEADW20-1W20-7A100'ROADWORKAHEADW20-1PARK AVE NPARK AVE N#1201FROMTOTOW AWAY AREAPHONE 888-9999
INFRASOURCE
LLC
000
0000
000 NO PARKINGNO-PARKNO PARK SIGNAGE WILL BEPLACED ON ALL STREETS TOSURROUND WORK ZONERESIDENT(S) WILL BE INFORMEDOF POSSIBLE TEMPORARYDRIVEWAY CLOSUREROADWORKAHEADW20-1 BEPREPAREDTOSTOPW3-4ROADWORKAHEADW20-1100'100'BEPREPAREDTOSTOPW3-4100'STOPFLAGGER
PATH OF INSTALLATIONNCHANNELIZATIONDEVICE SPACINGMPH55/7035/4525/30TAPER403020TANGENT806040Job#1050865711201 N 37th ST, Renton WAOctober 13, 2017Sheet 2 of 2 ryan.honeysett@pse.com(425)457-5381PSEPUGETSOUNDENERGYNotes:1. All signs and spacing to conform to the MUTCDand City of Renton standards.2. All sidewalks, driveways, exits and egressesshall be completely clear unless otherwise indicated.3. Channelizing devices are 28" traffic cones.4. Sign size can be a minimum of 48" x 48" andshall not obstruct pedestrian access.5. Crew is required to leave a minimum of 11' fortraveling lane width.6. Alert affected residents and businesses.7. Work to take place between 9 a.m. and 4 p.m.TRENCH28" TRAFFIC CONELEGENDTRAFFIC FLOWSIGN LOCATIONFLAGGERSTOPWORK VEHICLE/FLASHING LIGHTSRIGHT OF WAYPuget Sound EnergyTraffic Control Supervisor:Ryan HoneysettCard No. 010760Card Exp. 06/30/2021ryan.honeysett@pse.com(425)457-5381MFP20000149
D/R
"1201"DRIVEWAYN 37TH STN 37TH ST 60'
319450-166172
STORM DRAIN
WHITE LINE
HAZ
15
ADU
319451-166208
319449-166190
15 KVA 120/240V
37.5 KVA 120/240V
JOB SITE
ASPHALT
SHOULDER
STORM DRAIN
4' X 4'
WORK PIT
3/4 YARD
OF SAND
N 37TH STN 37TH ST
3'
10'
15'
BORE
±60'
4' X 4'
WORK PIT
4 'X 4'
WORK PIT
5' X 6'
WORK PIT
4' X 6'
BORE PIT
DRIVEWAY-CUSTOMER TO INSTALL 1-3"SCH'L
80 CONDUIT, ±145'
-PSE TO INSTALL 1-RUN 350KCMIL
UG TPX, ±145'
-PSE TO INSTALL 1-RUN OF 4/0
KCMIL UG TPX TAIL, ±10'
-CUSTOMER TO INSTALL 1-3"SCH'L
80 CONDUIT, ±210'
-PSE TO INSTALL 1-RUN 350KCMIL
UG TPX, ±210'
-PSE TO INSTALL 1-RUN OF 4/0
KCMIL UG TPX TAIL, ±10'
WHITE LINE
C:\Users\tinguy\AppData\Local\Temp\NM_16_1_GG_9353eb06-2255-438e-8ac1-e5e71a4fbf40.png
JOB SITE
SITE PLAN
POWER GENERAL NOTES - RESIDENTIAL PROJECT
N
Vicinity Map
N/A
Owner / Developer Contact Info
officeATTN:
ALI KIMIAI
1201 N 37TH ST
RENTON, WA 98056
ALI KIMIAI 425-919-1809
OVERHEAD CIRCUIT MAP
SCALE: 6" = 1 MILESCALE: NONE
CIRCUIT ONE-LINE DIAGRAM
CIRCUIT LOADING TABLE
AS OF
EXIST. PEAK LOAD
EST. NEW LOAD
TOTAL
CIRCUIT:
A PHASE B PHASE C PHASE
HAZ-15
2017
201 261 240
-3.95 -
201 264.95 240
OH TRF Removal
Perm. Service
Superior
ORDER#NOTIF#
PWR
PROJECT PHASE
104296642505017596
108103039
101108129505017544
108103038
101108127
CABLE TV
PHONE
FOREMAN (CHECK BOX WHEN COMPLETED)
PSE Equipment LOCKED/SECURED & Work Area left in CLEAN/SAFE Condition.
Grid, Cable, and Switch numbers INSTALLED & VERIFIED.
Field Changes RED-LINED on As-built.
Indicate correct FUSE SIZE on As-built & VERIFY proper PHASE.
Foreman's Signature _______________________________________________
Print Name ___________________________________ Date ______________
Material VERIFIED and CHANGES noted on Paperwork.
Total PRIMARY Cable noted on As-built.
Company ID#'s RECORDED in correct location on As-built.
Deviations noted on the As-built and their reason.
I certify that the work performed meets PSE's standards and procedures
and that all quality requirements are met.
10.
7.
6.
5.
4.
3.
2.
1.All materials to be installed in accordance with Puget Sound Energy's (PSE) standards. Any deviation from
this work sketch must be AUTHORIZED by PSE's Project Manager and NOTED on the Foremans' Copy.
All switching arrangements and/or outage arrangements are to be made with the Project Manager at least
three (3) working days in advance.
Contact the Utilities Underground Location Center (1-800-424-5555) at least 48 hours prior to commencing
work to get the underground facilities located.
STAKING: The customer will provide all staking (transformer, handhole, trench, grade, lot, pole, sidewalk,
etc.). See sketch and details for locations. Equipment locations must be approved by the Project Manager.
SITE PREPARATION: The work area will be at or near finished grade, clear of trench spoils or construction
materials which would restrict construction and/or equipment access, before work can begin.
Roads shall be paved or have a compacted , crushed rock base in place.
CLEARANCES: Transformers require a minimum of 6 feet from fire fighting equipment, 10 feet from
combustible walls, overhangs, doors, and windows, and a minimum of 5 feet from the back of curb (or guard
posts will be required per PSE standards). All conduits and vaults are to be at least 5 feet away from water,
storm and sewer lines when paralleling them in the right of way, and at least 1 foot when crossing them.
All work is to be done in accordance with local municipal and county permit requirements as applicable.
Inclement weather conditions may cause delays in construction times and dates.
EXCAVATION: The customer is to provide all trenching, backfill, vault excavations, compaction and
restoration per this sketch and per PSE standards. A minimum protective cover of 36" is required over
PSE's primary voltage equipment and 24" is required of PSE's secondary voltage equipment. The customer
will provide any and all shoring or they will side slope the trench to 1:1.
8.
9.
E-Mail:
Cell Phone:
Project Manager Contact Information:
Manager:FABIAN GOMEZ
206-573-0031
FABIAN.GOMEZ@PSE.COM
PSE
No
No
No
Yes
Yes
Yes
No
YesDeveloper
"Flagging Required"
"Outages Required"
"Locates Required"
Installed at site:
Grid Number:
kVA Rating:
Foreman to redline the following information
TRANSFORMER INSTALLATION
Company ID#:
Primary phase connected to:
Tested Secondary Voltage
Material ID#:
P01
319449-166190
37.5 KVA 120/240V
6211300
SCALE: 1" = 50'105086571THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL 811 TWO BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
105086571
593188626
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
FABIAN GOMEZ 206-573-0031 10/2/17
FABIAN GOMEZ 206-573-0031 10/2/17
N/A N/A N/A
TIN NGUYEN 253-244-4303 10/2/17
EASEMENT RENTON
ALI KIMIAI
OH TO UG CONVERSION /W POLE REM & OH TRF UPGRADE
1201 N 37TH ST, RENTON WA 98056
N/A N/A
N/A 105086571
N/A 1/2
KING N/A N/A CSPSKEIN
NW32-24N-05E N/A N/A
2405E126 2405E136 2405E126 HAZ-15
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A N/A N/A
N/A N/A N/A
N/A N/A N/A
504858529
LRC:
% V. Drop:
% Flicker:
Sq. Footage:
Panel Size:
Heat Type:
Est. Demand:
2780 SQ.
200 AMPS
ELECTRIC
14 KW
115 A
3.3 %
3.3 %
SITE SPECIFIC NOTES
P01 GRID# 319449-166190:
-REMOVE EXISTING B/O 40' POLE
-INSTALL 1-45' CL-3 DISTRIBUTION POLE W/GNDS
-INSTALL 1-POLE TOP PIN
-REMOVE EXISTING 15KVA 120/240 OH TRF
-INSTALL 37.5KVA 120/240 OH TRF
-INSTALL LB C/O FUSE @15T & TAP BØ
-INSTALL 1-STIRRUP BOLT
-INSTALL 2-RIGID CLEVIS (NORTH & SOUTH)
-TRANSFER OH SERVICE "1114", "1202", "1115"
-COMMUNICATIONS TO TRANSFER
-INSTALL NEW GRID# 319437-166190
HH1:
-INSTALL 17"X30" SECONDARY HANDHOLE
-INSTALL 3-6 POSITION FARGO BARS
M01:
-INSTALL 1-200AMP METER
M02:
-INSTALL 1-200AMP METER
SPAN SPECIFIC NOTES
P01/X01-HH1:
-BORE AND INSTALL 1-3" RED POLY CONDUIT, ±75'
-INSTALL 1-RUN OF 350KCMIL UG TPX, ±110'
P01-"1201":
-REMOVE EXISTING OH SEC CONDUCTOR & EXISTING METER
HH1 - M01:
-CUSTOMER TO INSTALL 1-3" SCH'L 80 CONDUIT, ±145'
-PSE TO INSTALL 1-RUN OF 350KCMIL UG TPX, ±155'
-PSE TO INTERCEPT & INSTALL 1-RUN OF 4/0KCMIL UG TPX TAIL, ±10'
HH1 - M02:
-CUSTOMER TO INSTALL 1-3" SCH'L 80 CONDUIT, ±210'
-PSE TO INSTALL 1-RUN OF 350KCMIL UG TPX, ±220'
-PSE TO INTERCEPT & INSTALL 1-RUN OF 40/KCMIL UG PTX TAIL, ±10'
CUSTOMER DEVELOPMENT NOTES
CUSTOMER IS RESPONSIBLE FOR ALL TRENCHING, SELECT BACKFILL,
COMPACTION & RESTORATION PER PUGET SOUND ENERGY STANDARDS.
#6750.6500
**DEVELOPER NEEDS TO FOLLOW ALL TRENCH DETAILS ON SELECT
BACKFILL**
-CUSTOMER IS REQUIRED TO PROVIDE A 4' X 4' WORK PIT AT P01.
-CUSTOMER IS REQUIRED TO PROVED A 4' x 6' BORE PIT ON P01 SIDE.
-CUSTOMER IS REQUIRED TO PROVIDE A 5' X 6' WORK PIT AT HH1.
-CUSTOMER IS REQUIRED TO PROVIDE A 4' X 4' WORK PIT & 3/4 YARD OF
SAND AT M01.
-CUSTOMER IS REQUIRED TO PROVIDE A 4' X 4' WORK PIT & 3/4 YARD OF
SAND AT M02.
-CUSTOMER TO BORE & INSTALL ±75' OF 1-3" DISCONTINUOUS RED POLY
CONDUIT FROM P01-HH1.
-CUSTOMER TO EXCAVATE & INSTALL ±145' OF 1-3" DISCONTINUOUS SCH'L
80 GRAY PVC CONDUIT FROM HH1-M01.
--CUSTOMER TO EXCAVATE & INSTALL ±210' OF 1-3" DISCONTINUOUS SCH'L
80 GRAY PVC CONDUIT FROM HH1-M02.
-CUSTOMER IS REQUIRED TO PROVIDE AND INSTALL A 3/8" NON-POLY PULL
ROPE IN CONDUIT.
-CUSTOMER MUST HAVE A COPY OF PSE PROVIDED PERMIT ON SITE
DURING ANY DIGGING IN RIGHT OF WAY.
-CUSTOMER IS REQUIRED TO INSTALL METER BASE ON FRONT 1/3 OF
BUILDING.
ALL TRENCHING WILL REQUIRE AN INSPECTION BY PSE BEFORE FINAL
BACKFILL
ALL TRENCH AND L&I INSPECTION MUST BE COMPLETED 72HRS BEFORE
CONSTRUCTION
583057918
OUTAGE LIST
1115 N 37TH ST, RENTON WA 98056
1201 N 37TH ST, RENTON WA 98056
1114 N 37TH ST, RENTON WA 98056
1202 N 37TH ST, RENTON WA 98056
CIRCUIT FEET ADDED: 0'
LRC:
% V. Drop:
% Flicker:
Sq. Footage:
Panel Size:
Heat Type:
Est. Demand:
1600 SQ.
200 AMPS
ELECTRIC
13 KW
80 A
3.5 %
2.6 %
HH1-M02
Removed at site:
Grid Number:
kVA Rating:
Foreman to redline the following information
TRANSFORMER REMOVAL
Company ID#:
Primary phase connected to:
Tested Secondary Voltage
P01
319449-166190
15KVA 120/240V
Standoff Bracket
15" Min Length
Conduit Clamp
Conduit Field Face
Quadrant
Climbing
SpaceRoad Face
Quadrant
Climbing
Space
5" Min
CL LCDirection of Vehicular Traffic
CONDUIT RISER PLACEMENT DETAIL
TOP VIEW
Not to Scale
186050040
P01-HH1 HH1-M01
LRC:
% V. Drop:
% Flicker:
Sq. Footage:
Panel Size:
Heat Type:
Est. Demand:
SQ.
AMPS
27 KW
A
2.8 %
2.3 %
New Handhole/Pole
Pole Removal
OH Misc
Purchase Conduit
Perm. Service
Ex. Svc Removal
POLE RETIREMENT TABLE TEMP TRANSFERS ST. LIGHT TRANSFERS
SITE
#
POLE DATA POLE
TEL TV FIBER TRAN RMVD ID NUMBER
GRID #HEIGHT CLASS YEAR TOPPED RMVD
P01 319449-166190 40 1956
POLE TABLE (NEW)
Site
#
Pole Data
Grid #Height Class Year Remarks / Location Ref.
P01 319449-166190 45 3 2017 PSE Equip #8974503
WIRE REMOVAL TABLE
Location
Wire Size & Type Quantity
Length
(per
conductor)RemarksFromTo
P01 M01 UNK 1 85 FT
MFP20000149
ARE TO BE INSTALLED, CROSS SECTION DETAILS OF THE TYPICAL EROSION
STRUCTURES, & SPECIAL REQUIREMENTS FOR WORK IN SENSITIVE AREAS.)
EROSION & SEDIMENT CONTROL REQUIREMENTS
NOTES DETAILING WHERE EROSION OR SEDIMENT CONTROL STRUCTURES
(LOCAL JURISDICTIONS MAY HAVE ADDITIONAL REQUIREMENTS INCLUDING
0150.3200 TECHNIQUES FOR TEMPORARY EROSION & SEDIMENT CONTROL
EROSION & SEDIMENT CONTROL SHALL BE PER PSE STANDARD PRACTICE
& ANY ADDITIONAL LOCAL JURISDICTION REQUIREMENTS.UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
FABIAN GOMEZ 206-573-0031 10/2/17
FABIAN GOMEZ 206-573-0031 10/2/17
N/A N/A N/A
TIN NGUYEN 253-244-4303 10/2/17
EASEMENT RENTON
ALI KIMIAI
OH TO UG CONVERSION /W POLE REM & OH TRF UPGRADE
1201 N 37TH ST, RENTON WA 98056
N/A N/A
N/A 105086571
N/A 2/2
KING N/A N/A CSPSKEIN
NW32-24N-05E N/A N/A
2405E126 2405E136 2405E126 HAZ-15
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A N/A N/A
N/A N/A N/A
N/A N/A N/A
TV & TEL Electric Service Cable in Conduit
3" Schedule 80 Grey PVC
Excavated Dirt Pile
Final Grade
24" Min
24" Min
to
36" Max
Cover Separation
12" Min
20" Min
JOINT TRENCH DETAIL
Electric Service Cable in Conduit (NTS)
To Excavated Dirt Pile
36" MINIMUM COVER
IN RIGHT OF WAY
Backfill for In Conduit - The backfill layer shall be soil that is free from construction debris,
glass, sharp rocks, frozen clods, and rocks larger than 8" in diameter.
Backfill for Conduit
Free of rocks
larger than 8"
in diameter)
FLOW DIRECTION
LAY 8" BOTTOM SKIRT ON TOP OF NATIVE SOIL,
SECURE WITH PEA GRAVEL BAGS (MID 9995692).
6'
3'
8"
TECHNIQUES FOR EROSION AND SEDIMENT CONTROL
FILTER FENCE DETAIL
Not to Scale 0150.3200
UTILITY POLE EROSION CONTROL DETAIL
TOP VIEW
DRY DRAINAGE DITCH or DRY VEGETATED SITE
SLOPE
Place gravel bags for
Sediment Trap
Place straw mulch
on disturbed areaExcavated or
Augered Hole
Pole
SLOPE
Not to scale Drainage ditches or Dry vegetated sites
32"
Typical
24"
Min
24"-36"
24"-36"
4'Top View
Electric & Joint Utility
Work Pit Dimensions
36"
Min
Drainage Pipe
12" Minimum Clearance
from Gas Service Lines
Conduit Depth
24" to 36" Max
Regulator Vent
Gas Meter Assembly
Utility Provided
48"
4'8"
Service (Permanent Detail:)
Not to Scale
Seal
Conduit
Ends
Closed
4'8"
24" Min
36" Typical
3'
To Trench
Property Line
Conduit Stakes
Customer Provided
3" Schedule 80 Grey PVC
Power Cable Conduit
Customer Provided
Gas Service Line Conduit
Sch 40 White PVC
Customer Provided
3" Conduit Service Riser
Customer Provided
Elec. Mtr Base
Elec Mtr
utility provided
Gas Meter
Relief Vent
Building Wall
Elec. Mtr
PERMANENT METER DETAIL AT M01 & M02
SCALE: NONE
BORE PIT DETAIL
Electric Service Cable in Conduit
Final Grade
24" Min
24" Min
to
36" Max
Cover
12" Typical
(6" Min)
36" MINIMUM COVER
IN RIGHT OF WAY
To Excavated Dirt Pile
3" Red Polyethelene
SCALE: NONE
Customer's
service
conductors27-1/4"
18"
Captive L-Bolt
Lock Cover, 10 lbs
40-1/2"
Conductors enter from
beneath and shall be
folded back with handhole
SIDE VIEW
2"
30"
Approx
Approx
17"
TOP VIEW
6'
5'
SINGLE PHASE SECONDARY HANDHOLE AT HH1
SCALE: NONE 6050.2000
MFP20000149