TEE OF APPROPRIATE SIZE USE ROMAC COUPLING OR
APPROVED EQUAL WHEN
60" MIN. CONNECTING TO AN EXISTING
° FOR NEW
SEWER MAIN
•r c > MANHOLES
�� •�• 1-
•
• (\
SEE NOTE 7
"RELINER" BRAND STAINLESS
•
•: �` STEEL ADJUSTABLE CLAMPING
•
•
BRACKETS OR APPROVED EQUAL
90' BEND EMBEDDED IN CONCRETE
•'r
S 7.R 17-------1/2 THE DIAMETER OF
+' ! THE DOWNSTREAM PIPE
NOTES:
1. SANITARY SEWER DROPS ARE ONLY TO BE USED UPON APPROVAL BY THE WASTEWATER
UTILITY SECTION.
2. DROP PIPES AND FITTINGS SHALL BE PVC SDR 35 WHEN CONNECTING TO ALL EXISTING
SEWER MAIN MATERIALS EXCEPT DUCTILE IRON. USE AWWA C900 PIPE AND AWWA C907
FITTING WHEN CONNECTING TO DUCTILE IRON SEWER MAINS.
3. MINIMUM SIZE MANHOLE FOR INSIDE DROP CONNECTION SHALL BE 60" DIAMETER.
4. CONNECTIONS TO MANHOLE SHALL BE CORE DRILLED AND USE KOR—N—SEAL BOOTS
OR APPROVED EQUAL.
5. USE ROMAC COUPLING OR APPROVED EQUAL WHEN CONNECTING TO AN EXISTING MAIN.
6. WITHIN A 60" DIAMETER MANHOLE, THE MAXIMUM ALLOWABLE DIAMETER OF THE INSIDE
DROP PIPING IS 12". INSIDE DROPS EXCEEDING 12" IN DIAMETER OR MULTIPLE DROPS
SHALL BE REVIEWED BY THE WASTEWATER UTILITY AND MAY REQUIRE A LARGER
DIAMETER MANHOLE.
7. "RELINER" BRAND STAINLESS STEEL ADJUSTABLE CLAMPING BRACKETS OR APPROVED
EQUAL SHALL BE INSTALLED WITHIN 6" OF BOTH BELL AND SPIGOT ENDS OF EACH
DROP PIPE. IF DROP PIPE LENGTH EXCEEDS 5 FEET THEN CENTER STRAPS SHALL BE
INSTALLED WITH A MAXIMUM SPACING OF 4 FEET ON CENTER. BRACKETS SHALL BE
ATTACHED UTILIZING STAINLESS STEEL EXPANSION BOLTS, MIN. 2 EACH AT
CONNECTION POINTS.
8. MANHOLE CONE SECTION AND ACCESS LADDER MAY NEED TO BE RELOCATED TO ALLOW DROP.
v o,� �^Mrr�e TE. PLAN -402.2
y
• PUBLIC WORKS INSIDE DROP CONNECTION APPROVED:
DEPARTMENT FOR SANITARY MANHOLE Martin Pastuch o/26/2000 1:
AFNiOa
Public
u...
vonuc won,Administrator DATE