STA. 14+68.3 6.51T HIGH AVE S
STA. 15+27 52'RTf HIGH AVE S
" � REMOVE PIG LAUNCH AND INSTALL: INSTALL:
CONNECT TO EX. 6 TEE. INSTALL: 2 — 4" DI SPOOL 1 — CONC. DEADMAN BLOCK
1 — 6" SPOOL CL-52 DI 1 — 4" AWWA C-900 PVC SPOOL
1 — 6"w 4" REDUCER (M✓xM✓) 2 — TRANS177ON COUPLING
1 — 4 SPOOL CL-52 DI 3 G
1 — 4" 45' BEND (M✓xM✓) W/ CONC. SEE DETAIL THIS SHEET co 'Oio
o THRUST BLOCKo-
1 — 4" CAP (M✓)
1 — 40CAP (M✓) ��cO
1 — 2" BLOW=OFF \ \ A
1 — TEMPORARY THRUST BLOCKINGIF TI-1
\ G�
041
m
W \ W \ 2
Q
m
3 5 3r 4 I ho
^ 3 >
3 � %_01 so D
TESTING DETAIL CONNECTION DETAIL TESTING DETAIL
AMERICAN SURVEYING & ENVIRONMENTAL, LLC (ASE)
CONDUCTED AN AS —BUILT SURVEY TO LOCATE ALL WATER
VALVES AND HYDRANTS. AS —BUILT DRAWING REDLINE
MARKUPS WERE MAINTAINED BY LASER UNDERGROUND &
EARTHWORKS, INC. BY THE ON —SITE CONSTRUCTION
FOREMAN AND PROVIDED TO ASE TO PREPARE THE FINAL
RECORD DRAWINGS. THE RECORD DRAWINGS REFLECT THE
AS —CONSTRUCTED CONDITIONS BASED ON A COMBINATION
OF FIELD SURVEY DATA AND THE AS —BUILT REDLINE
MARKUP DRAWINGS PROVIDED BY LASER UNDERGROUND &
EARTHWORKS, INC. AND SHOULD BE FIELD VERIFIED FOR
ANY FUTURE USE. ALL WATER VALVES AND HYDRANTS
WERE FIELD SURVEYED IN THEIR AS —BUILT LOCATIONS AND
EX. 6"GV
6" Of DPOOL
6"x4" REDUCER (M✓XM✓)
4" SPOOL
hhI
ACCURATELY REFLECTED HEREON. I
FINISH GRADE
III 1-1111-
NEW OR PROTECTED
PIPELINE TERMINALS
1 —#8 AND 1 —#12
AWG COPPER
WIRES WITH BLUE
INSULATION
NEW OR
PROTECTED
PIPELINE —
NOTES
1'-6" SQUARE
CONCRETE SLAB
6" THICK
JOINT BOND ALL PIPING FROM
EAIS71NG GA7E VALVE TO
7RANSl770N COUPLING.
CONNECTION DETAIL
STA. 15+27 HIGH AVE. S.
SCALE: 1 "=10' / 1 "=5' (DETAIL)
IIII-1111
EXISTING OR
UNPROTECTED
PIPELINE TERMINALS
1—#8 AND 1—#12
AWG COPPER
WIRES WITH GREEN
INSULATION
EXISTING OR
UNPROTECTED
PIPELINE
WIRE CONNECTION,
TYP, SEE DETAIL
SH
1. INSTALL ALL TEST WIRES IN 1" PVC CONDUIT
WITH 24" MINIMUM BURIAL DEPTH
2. INSTALL GALVANIC ANODE 1'-0" BELOW
PIPE INVERT AND 1'-6" FROM EDGE OF PIPE
TYPE FI - FLUSH MOUNTED
TEST STATION REPLACE INSULA71NG JOINT W17H
NTS AWWA C-900 PVC SPOOL AND
ONE- CA L L REFER
1 800- 424- 55 ��TI
PRIOR
dig.
NG UTILITIES ARE SHOWN FOR
ENCE ONLY. CONTRACTOR
FIELD LOCATE ALL EXISTING
ES A MINIMUM OF 72 HOURS
TO CONSTRUCTION.
ONE PIPE
DIA MINIMUM,
2'-0" MAXIMUM —
THERMITE WELD
CAP, SEE NOTE 4,
TYP
FILE OR GRIND
WELD AREA TO
BRIGHT METAL —
4" 45' BEND (M✓xM✓)
4" Of SPOOL
4" AWWA C-900 PVC SPOOL (FOR
ISOLA710N)
2 — 7RANS17101V COUPLING
NEW 4" CL-52 Of
® WIRE SIZE VARIES, TWO
WIRES REQD FOR TEST
NORTH STA INSTALLATIONS
ONLY
4>
THERMITE WELD
WIRE CONNECTION
STEEL OR DUCTILE
IRON PIPELINE
NOTES:
1. COPPER SLEEVE REQUIRED FOR THERMITE WELDING OF
#10 AWG AND SMALLER WIRE.
2. USE COPPER SLEEVE ON #2 AWG JOINT BONDING WIRES.
3. WELDER AND CARTRIDGE SIZE VARIES ACCORDING TO
WIRE SIZE AND PIPE MATERIAL, CONSULT WELDER
MANUFACTURER FOR RECOMMENDED WELDER AND CARTRIDGE.
4. COAT WELD AREA AND FILL RECESS ON THERMITE WELD
CAP WITH COLD APPLIED COAL TAR MASTIC AND APPLY
CAP TO WELD.
WIRE CONNECTION FOR STEEL
AND DUCTILE IRON PIPE
NTS
INSTALL:
1 — 87CAP (M✓)
1 — 2" BLOW —OFF
1 — TEMPORARY THRUST BLOCKING
1 — 8" 45' BEND W/ CONCC, THRUST
BLOCK
THERMITE WELD
CAP, TYP
CONNECTION DETAIL
BOG
s'OG FG65,ZaN
-
•
F ZF STA.HIGH AVE. S
G
F INSTALL:
B x6" TEE (M✓xM✓)
2— 81GV (MJxMJ)
1 — 6"GV (M✓xM✓)
2 — 8" SPOOL
1 — 8" SLEEVE
1 — 6" SPOOL
1 — 6" SLEEVE
1 — 8" AWWA C-900 SPOOL
—4 — 8" 7RAN977ON COUPLING
SEE DETAIL BELOW
CUT AND CAP EX. 60CI
ca
I °i
CU & CAP E . 6" C1 3
FINAL CONNECTION DETAIL
STA. 14+64 HIGH AVE S
SCALE: 1 "=10' / 1 "=5' (DETAIL)
#2 AWG INSULATED
STRANDED COPPER
WIRE 24" LONG
FLEXIBLE OR
EXPANSION
COUPLING
#2 AWG INSULATED
STRANDED COPPER WIRE
THERMITE WELD
WIRE CONNECTION,
NOTE: TYP, SEE DETAIL THIS SHEET
1. TWO BOND WIRE ASSEMBLES REQUIRED AT EACH 16" PIPE JOINT
AND ONE ASSEMBLY ON SMALLER PIPE JOINTS.
2. PUSH —ON JOINT SHOWN. BOND SIMILAR FOR FLANGED JOINT.
PUSH -ON AND FANGED
JOINT BOND
NTS
SURVEYED: SCALE:
BRH HORIZONTAL N D 11983/1991
DESIGNED: AS NOTED
AW
DRAWN:
AW
ONE INCH DATUM
CHECKED: AT FULL SCALE
AW, AG IF NOT ONE INCH
NO. REVISION BY DATE APPR APPROVED: SOALE ACCORDINGLY
AG
(1)
NORTH
WIRE CONNEC77ON AND
rA 77ON. EX. SPU WIRES
-W C.O.R. WIRES TO
17E AT SAME 7EST STA770N.
TAIL THIS SHEET.
#12 AWG INSULATED
STRANDED COPPER
WIRE, TYP OF 2
THERMITE WELD CAP, THERMITE WELD
WIRE CONNECTION,
TYP EACH WELD,
OTHERS NOT SHOWN TYP, SEE DETAIL
THIS SHEET
NOTE:
SEE SPECIFICATIONS FOR NUMBER OF BOND WIRES
REQUIRED AT EACH PIPE JOINT.
FLEXIBLE JOINT BOND
NTS
CITY OF
RENTON
Planning/Building/Public Works Dept.
RENTON HILL UTILITY REPLACEMENT PROJECT 10/25/18
CATHODIC PROTECTION OF 8"W AND 4"W FIELOBOOK:
PAGE:
AT INTERSECTION OF BEACON AVE S & HIGH AVE S DRAWING NO:
W-14A
SHEET: OF:
22A f
W03g24