Minor Franchise Permit: MFP19004173
IVR Number: 19004173
Permit Information
Permit Name: Puget Sound Energy - Electric
Address/Location:07/29/2019Application Date:0007200149Parcel Number: 375 RAINIER AVE S
Permit Type:08/02/2019Issue Date:Franchise
Permit Work Class:07/30/2021Expiration Date:Minor Utility
Job Number: 101117205Franchise Type:Electric
Description: REVISION: Raise conduit up 8" to 14" for clearance on new drain pipe. Restoration per City of Renton standards
Traffic control to park vehicles in ROW for work on private property.
Contacts
Name Address PhoneTypeBilling
Corrie Rydberg
Puget Sound Energy
6905 S 228TH St
KENT, WA 98032
C: (253) 905-5031ApplicantX
Vicki Henson
Potelco Inc
8001 212th St S
Kent, WA 98032
B: (253) 863-0484Contractor
Business License Number: BL.005109Electrical Contractor: POTELI*344O4
Construction Contractor: POTELI*227PL
CITY OF RENTON ROW 1055 S Grady Way
Renton, WA 98057-3232
Owner
General Conditions & Signature
Permission is hereby given for the work described on this permit according to the conditions hereon and according to the
approved plans and specifications pertaining thereto, subject to compliance with the Ordinance of the City of Renton.
Ÿ
This permit and plans must be posted at the job site at all times.Ÿ
I hereby certify that no work is to be done except as described above and in approved plans, and that work is to conform to
Renton Trench Restoration and Street Overlay Requirements.
Ÿ
Call 425.430.7203 or go to: https://permitting.rentonwa.gov one working day in advance to schedule an inspections and for ANY
work in the Right of Way.
Ÿ
Call 8 1 1 to locate underground utilities at least two full business days prior to any excavation.Ÿ
In accordance with RCW 19.122.033(4) the permit holder is required to contact (Williams Northwest Pipeline at 425.868.1010)
(Olympic Pipeline at 206.510.0575) (Puget Sound Energy at 425.375.3397) to request a consultation with the transmission
pipeline company prior to performing any construction or excavation activities. This requirement to consult with the
transmission pipeline company is in addition to the requirement to Call before You Dig as required in RCW 19.122.
Ÿ
(Date)(Signature)
Page 1 of 1THIS PERMIT AND PLANS MUST BE POSTED AT THE JOB SITE AT ALL TIMES
DEPARTMENT OF COMMUNITY
AND ECONOMIC DEVELOPMENT
Page 1 of 1 | Published: 1/2/2019
Planning Division | 1055 South Grady Way, 6th Floor | Renton, WA 98057 | 425-430-7200
Email: franchisepermits@rentonwa.gov Website: rentonwa.gov
FRANCHISE PERMIT APPLICATION
Published: 1/2/2019
TO THE APPLICANT: Submit an electronic copy of the plans with the Franchise Permit Application and the Site
Specific Traffic Control Application to franchisepermits@rentonwa.gov. Permit cost is $630.00. Inspection fee
for trenching more than 60 lineal feet or installation of 6 or more poles will be billed at $60.00 per hour.
Franchise Agency:
Franchise Job Number: Phone:
Contact Name: Email:
Job Site Address: Project Name:
Description of Work:
Please check all that apply:
տ New Construction տ Repair/Relocate տ Underground տ Overhead տ Sidewalk տ Street
տ Open Trench տ Bore # of feet:
Contractor Name: Phone:
State Contractors License #: City of Renton Business License #:
“I certify that I am the owner or applicant’s authorized agent and do hereby agree to abide to the terms and conditions set forth
under this permit and shall comply with the City of Renton’s Trench Restoration and Street Overlay Requirements. ”
Signature Date
INSPECTIONS SHALL BE REQUESTED 24 HOURS PRIOR TO COMMENCEMENT OF ALL WORK BY CALLING THE
INSPECTION LINE AT 425-430-7203 OR BY GOING TO MYBUILDINGPERMIT.COM
Jobs are required to be called in for job start, re-inspection and project final. Re-inspection fees are billed at
$125/hour. All Pre-Construction meetings shall be scheduled at a maximum of 14 days prior to the job start date.
Plan Review/Development Engineering Date Approved as submitted
Pre-Construction Meeting required
Site Construction Inspector Date Approved with comments or redlines
Camera inspection of utilities required
Development Engineering Manager Date
Puget Sound Energy - Electric
101117205
CORRIE RYDBERG
(253) 234-6410
CORRIE.RYDBERG@PSE.COM
361 RAINIER AVE S
Parking in city right of way at J01 (317776-165823) to remove and install PSE facilities/equipment
✔✔✔
Potelco, Inc. (253) 234-6410
POTELI#227PL BL005109
Corrie Rydberg Digitally signed by Corrie Rydberg Date: 2019.07.29 08:26:46 -07'00'7/29/19
MFP19004173
7/29/2019Nathan Janders
Scott Warlick 8/2/2019
CITY OF RENTON
TRAFFIC CONTROL PLAN
PROJECT NAME: PERMIT#
CONSTRUCTION COMPANY: PHONE#:
CONTACT NAME: PHONE#:
ADDRESS: CELL#:
E-MAIL ADDRESS: FAX#:
PROJECT LOCATION: N/E/S/W OF:
WORK TIME: APPROVED BY:
WORK DATE: APPROVAL DATE:
OFFICE COPY T-
CONTRACTOR
DEV. SERVICE, INSPECTION P. MILLER
DEV. SERVICE, PLAN REVIEW B. BANNWARTH
POLICE CHARLES KARLEWICZ
FIRE FIRE MARSHALL FS #13
Permit Holder agrees to all the following:
•Comply with all traffic regulations of the City of Renton and the State of Washington.
•Prepare a traffic control plan and obtain City approval of that plan. That plan shall be implemented for
all street and lane closures, and the plan shall be performed in compliance with the Manual on
Uniform Traffic Control Devices.
•Notify emergency services (253-852-2121) twenty-four (24) hours before any street or lane closures.
•Any lane or street closures not in conformance with the approved traffic control plan and/or without
notification of emergency services may result in receiving a citation for violation of R.C.W. 47.36.200
through 47.36.220, 9A.36.050 Reckless Endangerment, and other applicable State and City codes.
•Indemnify and hold harmless the City of Renton from any and all claims, actions, and judgments,
including all costs of defense and attorney’s fees incurred in defending against same, arising from and
related to implementation of the approved traffic control plans including claims arising from towing of
private vehicles and the acts of the Permit Holder’s agents and employees.
•The City of Renton shall be entitled, in its reasonable discretion, to settle claims prior to suit or
judgment, and in such event shall indemnify and hold harmless the City for any such claims paid,
including the City’s reasonable attorney’s fees and litigation costs incurred resulting from such claim.
•In the event any claim or suit is brought against City within the scope of this Agreement, Permit Holder
will pay for legal counsel chosen by the City to defend against same.
•Flagger and sign placement are subject to revision by the City Inspector on site, if needed to address
traffic or pedestrian safety or travel.
•By my signature herein, I acknowledge all the above requirements.
PRINT NAME: DATE:
SIGNATURE:
Reset FormPrint Form
101117205
Potelco, Inc
VAL BUZUNOV (425) 457-9938
6905 S 228th St, Kent, WA 98032
VAL.BUZUNOV@PSE.COM
361 RAINIER AVE S
TBD
TBD
CORRIE RYDBERG
7/29/19
Corrie Rydberg Digitally signed by Corrie Rydberg
Date: 2019.07.29 08:27:04 -07'00'
MFP19004173
Monday - Friday
8:00AM - 3:00PM Scott Warlick
8/2/2019
SKETCH
I
-- NORTH --
I
NOTES:
•Work Zone Traffic Control shall be in accordance with the Manual on Uniform Traffic Control Devices (MUTCD)
and shown by sketch or reference to WSDOT.
•The plan must be submitted to the City’s PW/Transportation Division for review and/or approval at least three
working days prior to work.
•Approved Temporary Traffic Control Plan must be at the work site during work hours.
•Contractor or entity must call Renton School District (425-204-4455) or any public/private agency to be affected
by a temporary lane or road closure.
•Complete assistance and accommodation shall be provided to all kinds of pedestrian traffic when sidewalk or
walkway is impeded.
•Total road closure lasting more than 24 hours is subject to the approval by the City Council.
•Any vehicle, equipment, barricade, or portable tow-away sign used within the work area must display a
company logo or any legally acceptable sign showing the company name, address, and telephone number at a
conspicuous place on the vehicle or equipment.
In the case of Temporary No Parking Zones, all the following apply in addition to previous:
•Contractor must complete form to show limits of Temporary No Parking Zone identifying barricade locations for
vacate parking or curb lane usage.
•Contractor must post notice of dates and time of Temporary No Parking Zone with at least two signs per block
72 hours in advance of effective date and time.
•The cover sheet of this Traffic Control Plan form must be attached to each Temporary No Parking Sign on the
project site.
•Temporary traffic control devices must be removed immediately when work is done or no construction activities
are going on. If deemed abandoned, City crews will remove and store them at the City’s maintenance shop
(3555 NE 2nd Street).
1113 11
11111111
1111
1111111111192313 11
11 11 11
11
11
ONLYONLY1615151111
11 11 11
11
11
11 11
11 11 11
#361 RAIN
IER
AVE
S
SW SUNSET BLVD
S 3RD
P
L
ONL
YONL
Y1313
12JO11111
ONLYONLY1111
ROADWORKAHEADW20-1
350'RIGHT LANECLOSEDAHEADW20-5RW4-2LROADWORKAHEADW20-1350'ROADWORKAHEADW20-1350'
ROAD
WORK
AHEAD W20-1350'
BUSINESS(ES) WILL BE INFORMED
OF POSSIBLE TEMPORARY
DRIVEWAY CLOSURE
ARRW-BRD
N PSE PUGETSOUNDENERGY
JOB#506097303
361 Rainier Ave S Renton WA
1st May, 2019
prachi.joshi@pse.com
425-424-7806
SHEET 1 of 1
Puget Sound Energy
Traffic Control Supervisor:
Gregory Harwood
Card No. 008997
Card Exp. 08/13/2019
gregory.harwood@pse.com
(425)424-6425
TEMPORARY TRAFFIC CONTROL PLAN
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 11' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place between 9 a.m. and 4 p.m
unless otherwise specified. All work for arterials
and major roadways will be from 9 a.m. to 3 p.m.
LEGEND
28" TRAFFIC CONE
SIGN LOCATION
TRAFFIC FLOW
UG/BOX/VAULTJO1
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
ROW ROW
MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
MFP19004173
D
D
D
D
D
D
D
D
D
D
D
F317802-165827
317799-165828
317793-165825
317802-165818
317804-165805
U386317802-165805
U0382
317803-165805
317801-165805
25kVA 120/240V
317780-165838
112.5kVA 120/208V
317785-165834
317776-165806
317774-165814
317775-165832
317765-165835
317769-165839
317763-165841
"300"
"330"
"351"
317776-165823
"107"
"111"
S 3R
D
P
L
RAIN
IER
AVE
SRAIN
IER
AVE
S
"330"
EAR
17
317778-165801
300kVA 120/208V
317786-165812
300kVA 120/208V
500kVA 120/208V
S 3RD ST
S 3R
D
P
L
Curb
Curb
Curb
Curb
Curb
317776-165823
317786-165812
300kVA 120/208V
500kVA 120/208V
100'
100'
90°, R=5'
NOTE: PSE TO PROVIDE AND INSTALL ALL
PRIMARY CONDUITS.
100'
317776-165823
317786-165812
300kVA 120/208V
500kVA 120/208V
100'
100'
90°, R=5'
NOTE: PSE TO PROVIDE AND INSTALL
ALL PRIMARY CABLES.
PSE TO INSTALL ±230' OF 1/0
AL JKT PRIMARY CABLES
SITE PLAN
Owner / Developer Contact Info
officeATTN:
CHICK-FIL-A, INC.
15635 ALTON PARKWAY, SUITE 350
IRVINE, CA 92618
DON IKELER 404-305-4407 101117205THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
OVERHEAD CIRCUIT MAP
SCALE: 6" = 1 MILE
FOREMAN (CHECK BOX WHEN COMPLETED)
PSE Equipment LOCKED/SECURED & Work Area left in CLEAN/SAFE Condition.
Grid, Cable, and Switch numbers INSTALLED & VERIFIED.
Field Changes RED-LINED on As-built.
Indicate correct FUSE SIZE on As-built & VERIFY proper PHASE.
Foreman's Signature _______________________________________________
Print Name ___________________________________ Date ______________
Material VERIFIED and CHANGES noted on Paperwork.
Total PRIMARY Cable noted on As-built.
Company ID#'s RECORDED in correct location on As-built.
Deviations noted on the As-built and their reason.
I certify that the work performed meets PSE's standards and procedures
and that all quality requirements are met.
CIRCUIT LOADING TABLE
AS OF
EXIST. PEAK LOAD
EST. NEW LOAD
TOTAL
CIRCUIT:
A PHASE B PHASE C PHASE
EAR-17
2018
156 128 163
5.98 5.98 5.98
161.98 133.98 168.98
506097303 101117205
108110938
584044004
506894568 587029377
506894569 3000012300
PROJECT PHASE
PWR
NOTIF#ORDER#
Superior
Vault Removal
UG Xfmr Removal
Connect 3Ø Svc
Set & Install Meter
NOT TO SCALE
UNDERGROUND CIRCUIT MAP
POWER GENERAL NOTES - COMMERCIAL PROJECT
8.
EXCAVATION: The customer is to provide all trenching, backfill, vault excavations, compaction and
restoration per this sketch and per PSE standards. A minimum protective cover of 36" is required over
PSE's primary voltage equipment and 24" is required of PSE's secondary voltage equipment. The customer
will provide any and all shoring or they will side slope the trench to 1:1.
All materials to be installed in accordance with Puget Sound Energy's (PSE) standards. Any deviation from
this work sketch must be AUTHORIZED by PSE's Project Manager and NOTED on the Foremans' Copy.
All switching arrangements and/or outage arrangements are to be made with the Project Manager at least
three (3) working days in advance.
Contact the Utilities Underground Location Center (1-800-424-5555) at least 48 hours prior to commencing
work to get the underground facilities located.
STAKING: The customer will provide all staking (transformer, handhole, trench, grade, lot, pole, sidewalk,
etc.). See sketch and details for locations. Equipment locations must be approved by the Project Manager.
SITE PREPARATION: The work area will be at or near finished grade, clear of trench spoils or construction
materials which would restrict construction and/or equipment access, before work can begin.
Roads shall be paved or have a compacted , crushed rock base in place.
CLEARANCES: Transformers require a minimum of 6 feet from fire fighting equipment, 10 feet from
combustible walls, overhangs, doors, and windows, and a minimum of 5 feet from the back of curb (or guard
posts will be required per PSE standards). All conduits and vaults are to be at least 5 feet away from water,
storm and sewer lines when paralleling them in the right of way, and at least 1 foot when crossing them.
All work is to be done in accordance with local municipal and county permit requirements as applicable.
Customer/Developer is responsible to provide, install and maintain all secondary service cables, conduits
and crossings from the individual unit's meter base to the designated connection point.
Inclement weather conditions may cause delays in construction times and dates.
1.
2.
3.
4.
5.
6.
7.
9.
11.
10.
PSE
No
No
No
Yes
Yes
Yes
No
YesDeveloper
"Flagging Required"
"Outages Required"
"Locates Required"
E-Mail:
Cell Phone:
Project Manager Contact Information:
Manager:VAL BUZUNOV
425-457-9938
VAL.BUZUNOV@PSE.COM
N
Vicinity Map
N/A
SCALE: 1" = 50'
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
VAL BUZUNOV 425-457-9938 06/24/19
JUSTIN HANG 253-508-7880 06/24/19
N/A N/A N/A
JUSTIN HANG 253-508-7880 06/24/19
RW-113382 CITY OF RENTON
CHICK-FIL-A, INC.
RELOCATE NEW PRI L/E, UPGRADE EX. XFMR, & SET 3Ø METER
361 RAINIER AVE S, RENTON, WA 98055
N/A N/A
N/A 101117205
AS NOTED 1/2
KING COUNTY N/A N/A CSPSKEIN
T23N, R05E, SEC 18 SE N/A N/A
2305E072 2305E076 2305E072NW EAR-17
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
LRC:
% V. Drop:
% Flicker:
Sq. Footage:
Panel Size:
Heat Type:
Est. Demand:
3,647 SQ.
1200AMPS
N/A
118KW
570A
1.0%
2.0%
CIRCUIT FEET ADDED: 0'SPAN SPECIFIC NOTES
J01 GRID NUMBER 317776-165823:
-EXISTING VAULT TO REMAIN
-REMOVE 3 - EXISTING 12kV ELBOWS W/ CABLE TAGS AØADM271, BØADM272, & CØADM273
-INSTALL 3 - 12kV ELBOW KITS (6041.1000, ELB10J)
-INSTALL CABLE TAGS AØEIH678, BØEIH678, & CØEIH678
PV1 GRID NUMBER 317774-165814:
-REMOVE EXISTING 504 SQUARE VAULT & EQUIPMENT
V01 GRID NUMBER 317786-165812:
-EXISTING 504 SQUARE VAULT TO REMAIN
-REMOVE 3 - EXISTING 12kV ELBOWS W/ CABLE TAGS AØADM271, BØADM272, & CØADM273
-REMOVE EXISTING 300kVA 120/208V PADMOUNT XFMR
-REMOVE EXISTING 4'8" X 5'6" X 6" COVER
-INSTALL 8' SQUARE CONCRETE COVER W/ 24" X 60" ACCESS (MID: 9996109)
-INSTALL 500kVA 120/208V PADMOUNT XFMR (MID: 6258250)
-INSTALL 3 - 12kV ELBOW KITS
-INSTALL CABLE TAGS AØEIH678, BØEIH679, & CØEIH680
-INSTALL 4 - 4POS #2 TO 500kCMILL CONNECTOR BARS (MID: 7651002)
-INSTALL 12 - MOUNTING BOLTS (MID: 7651008)
-CONNECT 4 - RUNS OF CUSTOMER PROVIDED, OWNED, & MAINTAINED 350kCMIL QUAD SVC
M01:
-PSE DEPARTMENT TO INSTALL 1 - 1200A CT'S & METER
CUSTOMER DEVELOPMENT NOTES
A PRE CONSTRUCTION MEETING IS REQUIRED WITH YOUR PROJECT MANAGER PRIOR TO STARTING ANY SITE WORK.
CUSTOMER IS RESPONSIBLE FOR ALL TRENCHING, SELECT BACKFILL, COMPACTION & RESTORATION PER PUGET
SOUND ENERGY STANDARDS & LOCAL MUNICIPALITY.
**DEVELOPER NEEDS TO FOLLOW ALL TRENCH DETAILS ON SELECT BACKFILL**
CUSTOMER IS RESPONSIBLE FOR THE FOLLOWING:
VAULTS & WORK PITS.
-CUSTOMER TO EXCAVATE AROUND VAULT COVER AND PROVIDE AN 11' X 11' OF CLEARANCE FOR NEW VAULT
COVER AT V01.
JOB SITE READINESS.
-JOB SITE NEEDS TO BE 100% READY FOR INSPECTION 5 BUSINESS DAYS PRIOR TO
CONSTRUCTION DATE.
-ALL TRENCH, AND LOCAL ELECTRICAL MUNICIPALITIES AKA "L&I, CITY", INSPECTIONS MUST BE COMPLETED 5
BUSINESS DAYS PRIOR TO SCHEDULED CONSTRUCTION DATE.
-REQUIRED TO HAVE EXCAVATION EQUIPMENT AND BE ON SITE THE DAY OF CONSTRUCTION TO COMPLETE
BACKFILLING.
-IF A SECOND INSPECTION IS REQUIRED, ADDITIONAL FEE'S WILL BE APPLIED.
-PLEASE REVIEW THE CITY OR KING COUNTY TRENCHING REQUIREMENTS UNDER THE PERMIT.
REMOVE PRIMARY CABLE TABLE
CABLE
NO.
SAP
EQUIP
LOCATIONS CABLE
(LF) EST
EXISTING CABLE
MFG. NAME
EXISTING CABLE
MFG. DATE
CABLE
REPLACED?FROM TO
ADM271 11469487 J01 V01 260'
ADM272 11469650 J01 V01 260'
ADM273 11469651 J01 V01 260'
TOTAL 780'
Primary Cable & Conduit Table (Forman to Complete)
LOCATION CONDUIT PRIMARY CABLE QTY OF LUBE
(gal.)
From To Size
(in)
Qty
Design
Length
(ft)
Actual
Length
(ft)
TYPE BENDS PULL
(lbs)
PULL
Rev
(lbs)
Cable
Size
Design
Length
(ft)
Actual
Length
(ft)
CABLE NUMBERS MANUFACTURING INFORMATION
DB120 90°45°22°11°A B C Manufacturer Compound Year Design As Built
J01 V01 4 1 200 YES 1 ---1/0 AL 230 EIH678 EIH679 EIH780
DEDICATED FACILITIES
SITE SPAN ADDITIONAL REMARKS LABOR UNITS
#FROM TO FOOTAGE
-J01 V01 200 DED. CONDUIT & WIRE 2-36, 2-55
V01 ---UPGRADE 300KVA TO 500KVA -
TOTAL FT=200
CONDUIT DIAGRAM
NOT TO SCALE
CABLE DIAGRAM
NOT TO SCALE
JOB SITE
JOB SITE
JOB SITE
MFP19004173
ARE TO BE INSTALLED, CROSS SECTION DETAILS OF THE TYPICAL EROSION
STRUCTURES, & SPECIAL REQUIREMENTS FOR WORK IN SENSITIVE AREAS.)
EROSION & SEDIMENT CONTROL REQUIREMENTS
NOTES DETAILING WHERE EROSION OR SEDIMENT CONTROL STRUCTURES
(LOCAL JURISDICTIONS MAY HAVE ADDITIONAL REQUIREMENTS INCLUDING
0150.3200 TECHNIQUES FOR TEMPORARY EROSION & SEDIMENT CONTROL
EROSION & SEDIMENT CONTROL SHALL BE PER PSE STANDARD PRACTICE
& ANY ADDITIONAL LOCAL JURISDICTION REQUIREMENTS.
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
VAL BUZUNOV 425-457-9938 06/24/19
JUSTIN HANG 253-508-7880 06/24/19
N/A N/A N/A
JUSTIN HANG 253-508-7880 06/24/19
RW-113382 CITY OF RENTON
CHICK-FIL-A, INC.
RELOCATE NEW PRI L/E, UPGRADE EX. XFMR, & SET 3Ø METER
361 RAINIER AVE S, RENTON, WA 98055
N/A N/A
N/A 101117205
AS NOTED 2/2
KING COUNTY N/A N/A CSPSKEIN
T23N, R05E, SEC 18 SE N/A N/A
2305E072 2305E076 2305E072NW EAR-17
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
CUSTOMER-SUPPLIED TRENCH FOR PRIMARY CABLE
SCALE: NONE
Phone & TV Primary Power Cable
Direct Buried or in PSE provided
Excavated Dirt Pile
Final Grade
24" Min
48"
Max
18"
Backfill for DB 120 Conduit/Direct Buried Cable
12" Min
Separation
6" or 12" of sand, 5/8" minus
3" of sand, 5/8" minus, or clean backfill bedding
JOINT TRENCH DETAIL
36"
Min
Cover
ROADSIDE
Typical To Excavated Dirt Pile
(No Rocks over 10" Diameter)
or clean backfill shading
DB120 Grade Conduit
Primary-Direct Buried or DB 120 (NTS)
- A 6" layer of sand, 5/8" minus, or clean shading is allowed when excavated native material
contains rocks no larger than 8" in diameter.
Trench and backfill requirements for primary electric line extension trenches (No PSE gas)
- A 12" layer of sand, 5/8" minus, or clean shading is required when excavated native material
contains rocks up to 10" in diameter.
FLOW DIRECTION
LAY 8" BOTTOM SKIRT ON TOP OF NATIVE SOIL,
SECURE WITH PEA GRAVEL BAGS (MID 9995692).
6'
3'
8"
TECHNIQUES FOR EROSION AND SEDIMENT CONTROL
SILT FENCE DETAIL
Not to Scale 0150.3200
COOLING
5' MIN
5' MIN
10' MIN
5'
MIN
FINS
ACCESS
CONCRETE PAD
MIN. CLEARANCES FOR PADMOUNT TRANSFORMER & VAULT AT V01
CURB OR EDGE OF PAVEMENT
CURB OR EDGE OF PAVEMENT
5' MIN
ROAD OR
PARKING AREA
TYP. PAD
& TRANS-
FORMER
1.5' MIN
DOOR
ACCESS
DOOR
REQUIRED
WORK SPACE
AREA
Not to scale
1.5' MIN
3'
MIN
3' MIN
3' MIN
10' MIN3'
MIN
6"6"
MIN
GUARD POST INSTALLATION
MIN
CONCRETE 2'-6"
PAINTED
YELLOW
3'-6"
6'-0"
The following styles of guard posts are approved for Puget Sound Energy transformers:
- 6 ft x 4 in. diameter Schedule 40 or better galvanized steel pipe filled with concrete.
The concrete shall have a minimum compressive strength of 3000 psi after 28 days.
The exposed portion of the post shall be painted traffic yellow.
- 6 ft x 9 in. diameter precast steel-reinforced concrete post.
Available from Utility Vault Company, Auburn, WA; or Hanson Inc., Tacoma, WA.
The exposed portion of the post shall be painted traffic yellow.
LENGTH
GUARD POST INSTALLATION AT V01
Not to scale 0700.1600-03
18"
PAD &
GUARD POST LOCATIONS
XFMR
FRONT
GUARD
POSTS 3'
MIN
MIN
5'
MAX
5'
MAX
TYPICAL
3' MIN 5'
MAX
5'
MAX
5'
MAX
18"
MIN
5'
MAX
5'
MAX
5'
MAX
5'
MAX
5'
MAX
Cables should enter the vault so that all of
the cables will lay in the same direction.
TOP VIEW
J- BOX CABLE ENTRY DETAIL
Not to scale
Excavation - 10-1/3 cubic yards
SIDE VIEW
Rock
Crushed
6"
4'-4"
2"
4'-8"
3'-6"
4'-8"
Not to scale 6045.5000-1
3,600 lbs
VAULT & EXCAVATION DETAIL AT V01
8'-0"8'-0"8"
11'
11'
TOP VIEW
MFP19004173
PSE TO PROVIDED & INST. (1) 4" SCH80 GRAY PVC
DISCONTINUOUS CONDUIT IN CUST. PROVIDE TRENCH
317776-165823
37.5 kVA 120/240V (A)
317802-165805
CUST. PROVIDED
40' X 4' WORKPIT
SPARE SCH80 GRAY PVC CONDUIT
300
307
351
317802-165827
317799-165828
317793-165825
317802-165818
317804-165805
U386
317802-165805
U0382
317803-165805
317801-165805
25kVA 120/240V
317780-165838
112.5kVA 120/208V
317785-165834
317763-165841RAIN
IER
AVE
S
"361"
317778-165801
300kVA 120/208V
S 3RD ST
317774-165814
317776-165823
317775-165832
317769-165839
317765-165835
100'EAR17317776-165823
37.5 kVA 120/240V (A)
J
J
JPSE TO INST. 1-RUN 3PH 1/O SOL AL UG, ±320',
INST. CABLE TAGS A#EIH048,B#EIH049,C#EIH050
317776-165823
37.5 kVA 120/240V (A)
317802-165805
N
Vicinity Map
N/A
CUSTOMER-SUPPLIED TRENCH FOR PRIMARY CABLE
FOREMAN (CHECK BOX WHEN COMPLETED)
PSE Equipment LOCKED/SECURED & Work Area left in CLEAN/SAFE Condition.
Grid, Cable, and Switch numbers INSTALLED & VERIFIED.
Field Changes RED-LINED on As-built.
Indicate correct FUSE SIZE on As-built & VERIFY proper PHASE.
Foreman's Signature _______________________________________________
Print Name ___________________________________ Date ______________
Material VERIFIED and CHANGES noted on Paperwork.
Total PRIMARY Cable noted on As-built.
Company ID#'s RECORDED in correct location on As-built.
Deviations noted on the As-built and their reason.
I certify that the work performed meets PSE's standards and procedures
and that all quality requirements are met.101137099THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL 811 TWO BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
Excavated Dirt Pile
Final Grade
24" Min
Backfill for Schedule 40 Conduit
(NO Rocks over 10" Diameter
or foreign objects)Separation
12" Min
18" Min
JOINT TRENCH DETAIL
Primary-Schedule 80 (NTS)
48"
Max
36"
Min
Cover
Phone & TV Primary Power Cable
in Customer Provided
Schedule 80 Conduit
ROADSIDE
To Excavated Dirt Pile
JOB SITE
ARE TO BE INSTALLED, CROSS SECTION DETAILS OF THE TYPICAL EROSION
STRUCTURES, & SPECIAL REQUIREMENTS FOR WORK IN SENSITIVE AREAS.)
EROSION & SEDIMENT CONTROL REQUIREMENTS
NOTES DETAILING WHERE EROSION OR SEDIMENT CONTROL STRUCTURES
(LOCAL JURISDICTIONS MAY HAVE ADDITIONAL REQUIREMENTS INCLUDING
0150.3200 TECHNIQUES FOR TEMPORARY EROSION & SEDIMENT CONTROL
EROSION & SEDIMENT CONTROL SHALL BE PER PSE STANDARD PRACTICE
& ANY ADDITIONAL LOCAL JURISDICTION REQUIREMENTS.
CIRCUIT FEED ADDED: 0'
00 1"2"
00 50'100'
FLOW DIRECTION
LAY 8" BOTTOM SKIRT ON TOP OF NATIVE SOIL,
SECURE WITH PEA GRAVEL BAGS (MID 9995692).
6'
3'
8"
TECHNIQUES FOR EROSION AND SEDIMENT CONTROL
SILT FENCE DETAIL
Not to Scale 0150.3200
SITE PLAN
SCALE: 1" = 50'
POWER GENERAL NOTES - COMMERICAL PROJECT
1.All materials to be installed in accordance with Puget Sound Energy's (PSE) standards. Any deviation from this work
sketch must be AUTHORIZED by PSE's Project Manager and NOTED on the Foremans' Copy.
2.All switching arrangements and/or outage arrangements are to be made with the Project Manager at least three (3)
working days in advance.
3.Contact the Utilities Underground Location Center (1-800-424-5555) at least 48 hours prior to commencing work to get the
underground facilities located.
4.STAKING: The customer will provide all staking (transformer, handhole, trench, grade, lot, pole, sidewalk, etc.). See
sketch and details for locations. Equipment locations must be approved by the Project Manager.
5.SITE PREPARATION: The work area will be at or near finished grade, clear of trench spoils or construction materials
which would restrict construction and/or equipment access, before work can begin.
6.Roads shall be paved or have a compacted , crushed rock base in place.
7.CLEARANCES: Transformers require a minimum of 6 feet from fire fighting equipment, 10 feet from combustible walls,
overhangs, doors, and windows, and a minimum of 5 feet from the back of curb (or guard posts will be required per PSE
standards). All conduits and vaults are to be at least 5 feet away from water, storm and sewer lines when paralleling them
in the right of way, and at least 1 foot when crossing them.
8.All work is to be done in accordance with local municipal and county permit requirements as applicable.
9.Customer/Developer is responsible to provide, install and maintain all secondary service cables, conduits and crossings
from the individual unit's meter base to the designated connection point.
10.Inclement weather conditions may cause delays in construction times and dates.
11.EXCAVATION: The customer is to provide all trenching, backfill, vault excavations, compaction and restoration per this
sketch and per PSE standards. A minimum protective cover of 36" is required over PSE's primary voltage equipment and
24" is required of PSE's secondary voltage equipment. The customer will provide any and all shoring or they will side
slope the trench to 1:1.
OVERHEAD CIRCUIT MAP
SCALE: 6" = 1 MILE
SCALE: NONE
CONDUIT ONE-DIAGRAM
SITE SPECIFIC NOTES:
S01 - EXISTING #317802-165805
-EXISTING VAULT AND EQUIPMENT TO REMAIN
-DISCONNECT PRI. CABLE #AGJ056,#AGJ057, #AGJ058
-INST. (3) 12KV ELBOW KIT PER STD 6041.1000 (ELB10J)
-INST. CABLE TAGS #EIH048,#EIH049,#EIH050
V01 - EXISTING #317775-165823
-EXISTING VAULT AND EQUIPMENT TO REMAIN
-DISCONNECT PRI. CABLE #AGJ056,#AGJ057, #AGJ058
-INST. (3) 12KV ELBOW KIT PER STD 6041.1000 (ELB10J)
-INST. CABLE TAGS # EIH048,EIH049,EIH050
SPAN NOTE:
S01 TO V01
-REMOVE 1-RUN OF 3Ø 1/O UG JKT CABLE, ±320' _____' ACTUAL
-BREAK SCH80 CONDUIT AND RAISE 8" TO 14" TO 12" CLEARANCE NEW DRAIN PIPE
- BREAK SPARE SCH80 CONDUIT AND RAISE 8" TO 14" TO 12" CLEARANCE NEW DRAIN PIPE
-PSE TO INSTALL SCH80 GRAY PVC DISCONTINUOUS CONDUIT TO PROPER DEPTH TO MAINTAIN PROPER MIN. 12"
CLEARANCE OF NEW DRAIN PIPE.
-INST. 1-RUN OF 3Ø 1/O UG JKT CABLE, ±320' _____' ACTUAL
- INST. CABLE TAGS # EIH048,EIH049,EIH050
DEVELOPER & CUSTOMER NOTES:
A PRE CONSTRUCTION MEETING IS REQUIRED WITH YOUR PROJECT MANAGER PRIOR TO STARTING ANY SITE WORK.
CUSTOMER IS RESPONSIBLE FOR ALL TRENCHING, SELECT BACKFILL, COMPACTION & RESTORATION PER PUGET
SOUND ENERGY STANDARDS & LOCAL MUNICIPALITY.
**DEVELOPER NEEDS TO FOLLOW ALL TRENCH DETAILS ON SELECT BACKFILL**
CUSTOMER IS RESPONSIBLE FOR THE FOLLOWING:
VAULTS & WORK PITS
TRENCHING
-CUSTOMER TO PROVIDE 40' X 4' TRENCH TO MODIFY EXISTING CONDUITS FROM @ V01
-REQUIRED TO PROVIDE AND INSTALL A 3/8" NON-POLY PULL ROPE IN ALL OF THE CONDUITS.
JOB SITE READINESS
-JOB SITE NEEDS TO BE 100% READY FOR INSPECTION 5 BUSINESS DAYS PRIOR TO CONSTRUCTION DATE.
-ALL WORK IN RIGHT OF WAY MUST BE COORDINATED WITH PROJECT MANAGER AND LOCAL MUNICIPALITY.
-ALL TRENCH, AND LOCAL ELECTRICAL MUNICIPALITIES AKA "L&I, CITY", INSPECTIONS MUST BE COMPLETED 5
BUSINESS DAYS PRIOR TO SCHEDULED CONSTRUCTION DATE.
-REQUIRED TO OPERATE AND PROVIDE EQUIPMENT TO PUMP OUT WATER FOR WORK PITS, VAULTS & TRENCH AT
ALL TIMES.
-REQUIRED TO HAVE EXCAVATION EQUIPMENT AND BE ON SITE THE DAY OF CONSTRUCTION TO COMPLETE
BACKFILLING.
-IF A SECOND INSPECTION IS REQUIRED, ADDITIONAL FEE'S WILL BE APPLIED.
-PLEASE REVIEW THE CITY OR KING COUNTY TRENCHING REQUIREMENTS UNDER THE PERMIT.
-IF A PRE-CON IS REQUIRED BY THE CITY, COUNTY OR WSDOT, A PSE PROJECT MANAGER WILL SET-UP AND
SCHEDULE A MEETING WITH THE MUNICIPALITY BEFORE ANY EXCAVATION OR INSTALLATION BEGINS .
UNDERGROUND CIRCUIT MAP
SCALE: 1" = 100'
SCALE: NONE
CABLE ONE-DIAGRAM
Superior
ORDER#NOTIF#
PWR
PROJECT PHASE
PSE
No
No
No
Yes
Yes
Yes
No
YesDeveloper
"Flagging Required"
"Outages Required"
"Locates Required"
101137099510865473
108127222
594141417
N/A
N/A
N/A
E-Mail:
Cell Phone:
Project Manager Contact Information:
Manager:
Tin.Nguyen@pse.com
(253) 244-4303
Tin Nguyen
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
SIGNATURE
Fabian Gomez 206-573-0031 12/05/19
Justin Hang 253-508-7880 12/05/19
N/A N/A N/A
Justin Hang 253-508-7880 12/05/19
RW-113382 CITY OF RENTON
CHICK-FIL-A, INC.
MISC UG
361 RAINIER AVE S, RENTON, WA 98055
N/A N/A
N/A 101137099
AS NOTED 1/1
KING COUNTY N/A N/A CSPSKEIN
T23N.R05E.SE18 N/A N/A
2305E072 2305E076 2305E072NW EAR-17
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Owner / Developer Contact Info
officeATTN:
CHICK-FIL-A, INC.
15635 ALTON PARKWAY, SUITE 350
IRVINE, CA 92618
DON IKELER 404-305-4407
Cable Removal
Misc UG