GENERAL NOTES "SITE"
A. ELECTICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING PLANS
FOR TEMPORARY POWER FOR OBTAINING PERMIT.PLANS SHALL INCLUDE
RISER DIAGRAM,GROUNDING,FAULT CURRENT CALCULATION AND SITE
PLAN SHOWING LOCATION OF ALL ELECTRICAL EQUIPMENT.
B. PROVIDE 8' OF SEPARATION BETWEEN THE SIDES OF THE TARGETS AND
ALL RACEWAYS.
C. POLE BASES FOR SITE LIGHTING FIXTURES SHALL BE PROVIDED BY
CONCRETE CONTRACTOR (LAYOUT INCLUDED). REFERENCE STRUCTURAL
DRAWINGS FOR POLE BASE STRUCTURAL REQUIREMENTS.
D. PROVIDE (1) 1" EMPTY PVC CONDUIT WITH PULL WIRE FROM PANEL LT TO
EACH TARGET MANHOLE.
E. PROVIDE MULE TAPE IN ALL DATA CONDUITS 1-1/2" AND GREATER.
F. REFERENCE E9.01 DETAIL PLAN FOR TARGET POWER AND DATA
REQUIREMENTS.
G. REFERENCE LV2.1 FOR LV CONDUIT REQUIREMENTS.
H. KEEP ALL ELECTRICAL BOXES 8" BELOW THE BOTTOM OF "C" CHANNEL IN
EACH TARGET.
I. ALL 277V CIRCUIT LENGTHS GREATER THAN 180 FT SHALL BE INCREASED
TO #10 AWG AND TO #8 AWG WHEN GREATER THAN 290 FT. INCREASE
CONDUIT SIZE FOR 40% FILL. ALL 120V CIRCUIT LENGTHS GREATER THAN
100 FT. SHALL BE INCREASED TO #10 AWG AND TO #8 AWG WHEN GREATER
THAN 250FT INCREASE CONDUIT SIZE FOR 40% FILL.
KEYED NOTES "POWER"
EP-12 PROVIDE OZ GEDNEY CABLE SEALS FOR SERVICE
ENTRANCE CONDUCTORS IN EACH SERVICE RACEWAY.
EP-57 PROVIDE (2) 2-1/2" PVC FROM "MSB" TO TLED FOR HD
SPECTACULAR POWER. PROVIDE CONCRETE PULLBOX EVERY
250'. USE 45 DEGREE BENDS FOR PVC CONDUIT. REFERENCE
E5.0.
EP-58 PROVIDE N3R DISCONNECT FOR PUMP CONTROLLER FBO/IBE
FED FROM MSB, IF PUMP CONTROLLER IS NOT FURNISHED.
PROVIDE 2-FUSIBLE N3R DICONNECTS 1 FOR EACH PUMP
ON SUPPORT RACK. ALL CONTROLS & CONTROL WIRING DONE
BY PUMP PROVIDER.
EP-59 PROVIDE 2" PVC WITH MULE TAPE FROM JUNCTION BOX AT
TRENCH TARGET TO SERVER ROOM. HD SPECTACULAR JOBS
ONLY.
EP-60 RECEPTACLES MOUNTED TO POLES 18" AFF TYPICAL OF (3).
REFERENCE DRAWING E7.01/08 FOR MORE INFORMATION.
CIRCUIT TO LT-26.
EP-61 REFERENCE HD SPECTACULAR DRAWINGS FOR ADDITIONAL
INFORMATION REGARDING LOCATION AND OUNTING FOR
PANELS.
EP-62 PROVIDE RED FLASHING OBSTRUCTION BEACON AT TOP OF
POLE. ONE SYSTEM PER POLE INCLUDES ONE L-864 BEACON.
LIGHT FIXTURE TO BE FURNISHED BY OWNER. COORDINATE
INSTALLATION OF LIGHTS AND CIRCUITING PRIOR TO ERECTION
OF POLE.
EP-63 PROVIDE AND INSTALL 100A/3P N3R DISCONNECT FOR
TRANSFORMER PRIMARY DISCONNECTING MEANS. VERIFY
EXACT REQUIREMENTS AND LOCATION OF DISCONNECT
PRIOR TO ROUGH IN. REFERENCE E5.00.
EP-64 PROVIDE AND INSTALL 225A/3P N3R DISCONNECT FOR
TRANSFORMER PRIMARY DISCONNECTING MEANS. VERIFY
EXACT REQUIREMENTS AND LOCATION OF DISCONNECT
PRIOR TO ROUGH IN. REFERENCE E5.00.
EP-66 PROVIDE(2) 4" DATA CONDUITS FOR TELE/DATA SERVICE
TO IT ROOM. REFER TO LOW VOLTAGE DRAWINGS FOR
PLACEMENT DIMENSIONS IN IT ROOM.
VERIFY EXACT REQUIREMENTS FOR MONUMENT SIGN WITH
GENERAL CONTRACTOR PRIOR TO ROUGH IN. PROVIDE LOCAL
CONTROL BY WAY OF PHOTOCELL FOR MONUMENT SIGN.
COORDINATE WITH SIGN CONTRACTOR FOR EXACT LOCATION
OF PHOTOCELL.
EP-68 EXISTING CIRCUIT IS 240V, SINGLE-PHASE, 20A.
EP-69 ELECTRICAL CONTRACTOR SHALL CONNECT PEDESTRIAN POLE
LIGHTING TO CIRCUIT USED FOR ROADWAY LIGHTING. REF.
DETAIL 1/E7.4 AND 2/E7.4 FOR INSTALLATION DETAILS.
SURVEYED: SCALE:
VERTICAL: NAVD 1988
HORIZONTAL: NAD 1983/1991
DESIGNED:
0 B.PATE
ODRAWN:
o B.PATE ONE INCH DATUM
`\ RECORD DRAWINGS FD 09/19/22 CHECKED:
F. D E R A S IF AT FULL SCALE \
NOT ONE INCH
N 0. REVISION BY DATE A P P R aPPRoveD: SCALE ACCORDINGLY \,
CITY OF
RENTON
Planning/Building/Public Works Dept.
FS;
FSG
2525 WALNUT HILL LANE
SUITE 100
DALLAS, TX 75229
PH: 214-357-5697
FAX: 214-357-5794
WWW.FSGI.COM
4tiC0
4.
09.19.2022
T-412303
IN COMPLIANCE WITH CITY OF RENTON STANDARDS
ARCO/MURRAY- TOPGOLFRENTON
780 LOGAN AVENUE NORTH
RENTON, WA 98057
SITE LIGHTING PLANS