DIBBLE ENGINEERS INC | 1029 Market Street, Kirkland WA 98033 | 425.828.4200 | dibbleengineers.com
December 29, 2021
Charter Construction
Attn: Jameson Griggs
980 South Harney Street
Seattle, WA 98108
Re: Sunset Oaks Street Lights – Street Lights Connection to Existing Foundation
2650 NE 10th St, Renton, WA 98056
DEI Project #: 21-452
Dear Mr. Griggs:
Dibble Engineers, Inc. (DEI) has completed a review of the street light’s retrofit connection to existing foundation
proposed for installation at the location above.
DEI calculated the wind and seismic loading for the street lights based on the dimensions provided. Based on our
review and calculations, street light connection to the existing foundation is acceptable for installation with the
dimensions and anchorage shown on the attached redlined detail sheets SD1. Note that the foundations were
previously installed by the contractor and DEI’s scope did not include review of the footings themselves.
Supplemental structural calculations for the street light’s anchorage are attached with this letter.
Please contact us with any questions, and we will be happy to assist.
Sincerely,
DIBBLE ENGINEERS, INC.
Suhib Hammad, EIT
Design Engineer
suhib@dibblenegineers.com
Travis S. Colliander, PE, SE
Associate
travis@dibbleengineers.com
Attachments: Redlined Detail Sheets SD1, Structural Calculations
12/30/2021
12"SET-3G W/ (4) 3/4" Ø 12"SD1
Dibble Engineers Inc JOB TITLE Sunset Oak Lights
1029 Market Street, Suite 200
Kirkland, WA 98033 JOB NO.SHEET NO.
(425) 828-4200 CALCULATED BY DATE
CHECKED BY DATE
Wind Loads - Other Structures:ASCE 7- 16 Ultimate Wind Pressures
Wind Factor =1.00
Gust Effect Factor (G) =0.85 98 mph
Kzt =1.00 Exposure =B
A. Solid Freestanding Walls & Solid Signs (& open signs with less than 30% open)
s/h =1.00 Case A & B
Dist to sign top (h)8.0 ft B/s =25.00 Cf = 1.30
Height (s)8.0 ft Lr/s =0.00 F = qz G Cf As =16.0 As
Width (B)200.0 ft Kz =0.575 As =10.0 sf
Wall Return (Lr) =qz =12.0 psf F =160 lbs
Directionality (Kd)0.85
Percent of open area Open reduction CaseC
to gross area 0.0%factor =1.00 Horiz dist from
windward edge Cf F=qzGCfAs (psf)
Case C reduction factors 0 to s 3.29 33.6 As
Factor if s/h>0.8 =0.80 s to 2s 2.07 21.1 As
Wall return factor 2s to 3s 1.59 16.2 As
for Cf at 0 to s =1.00 3s to 4s 1.31 16.0 As
4s to 5s 1.23 16.0 As
5s to 10s 0.78 16.0 As
>10s 0.44 16.0 As
B. Open Signs & Single-Plane Open Frames (openings 30% or more of gross area)
Height to centroid of Af (z) 15.0 ft Kz =0.575
Base pressure (qz) =12.0 psf
Width (zero if round)0.0 ft
Diameter (zero if rect)2.0 ft D(qz)^.5 =6.93 F = qz G Cf Af =16.0 Af
Percent of open area Î =0.65 Solid Area: Af =10.0 sf
to gross area 35.0%Cf = 1.1 F =160 lbs
Directionality (Kd)0.85
C. Chimneys, Tanks, & Similar Structures
Height to centroid of Af (z) 16.8 ft Kz =0.593
Cross-Section Square Base pressure (qz) =13.1 psf
Directionality (Kd)0.90 h/D = 11.17
Height (h) 16.8 ft
Width (D)1.5 ft
Type of Surface N/A
Square (wind along diagonal)Square (wind normal to face)
Cf =1.19 Cf =1.54
F = qz G Cf Af =16.0 Af F = qz G Cf Af =17.2 Af
Af =sf Af =4.1 sf
F =0 lbs F =71 lbs
D. Trussed Towers
Height to centroid of Af (z) 15.0 ft Kz =0.575
= 0.27 Base pressure (qz) =13.4 psf
Tower Cross Section triangle
Member Shape flat Diagonal wind factor =1
Directionality (Kd)0.95 Round member factor =1.000
Triangular Cross SectionCf =2.38
F = qz G Cf Af =27.1 Af
10.0 Solid Area: Af =10.0 sf
F =271 lbs
Ultimate Wind Speed =
Dibble Engineers Inc JOB TITLE Sunset Oak Lights
1029 Market Street, Suite 200
Kirkland, WA 98033 JOB NO.SHEET NO.
(425) 828-4200 CALCULATED BY DATE
CHECKED BY DATE
Wind Loads - Other Structures:ASCE 7- 16 Ultimate Wind Pressures
Wind Factor =1.00
Gust Effect Factor (G) =0.85 98 mph
Kzt =1.00 Exposure =B
A. Solid Freestanding Walls & Solid Signs (& open signs with less than 30% open)
s/h =1.00 Case A & B
Dist to sign top (h)8.0 ft B/s =25.00 Cf = 1.30
Height (s)8.0 ft Lr/s =0.00 F = qz G Cf As =16.0 As
Width (B)200.0 ft Kz =0.575 As =10.0 sf
Wall Return (Lr) =qz =12.0 psf F =160 lbs
Directionality (Kd)0.85
Percent of open area Open reduction CaseC
to gross area 0.0%factor =1.00 Horiz dist from
windward edge Cf F=qzGCfAs (psf)
Case C reduction factors 0 to s 3.29 33.6 As
Factor if s/h>0.8 =0.80 s to 2s 2.07 21.1 As
Wall return factor 2s to 3s 1.59 16.2 As
for Cf at 0 to s =1.00 3s to 4s 1.31 16.0 As
4s to 5s 1.23 16.0 As
5s to 10s 0.78 16.0 As
>10s 0.44 16.0 As
B. Open Signs & Single-Plane Open Frames (openings 30% or more of gross area)
Height to centroid of Af (z) 15.0 ft Kz =0.575
Base pressure (qz) =12.0 psf
Width (zero if round)0.0 ft
Diameter (zero if rect)2.0 ft D(qz)^.5 =6.93 F = qz G Cf Af =16.0 Af
Percent of open area Î =0.65 Solid Area: Af =10.0 sf
to gross area 35.0%Cf = 1.1 F =160 lbs
Directionality (Kd)0.85
C. Chimneys, Tanks, & Similar Structures
Height to centroid of Af (z) 16.8 ft Kz =0.593
Cross-Section Round Base pressure (qz) =13.9 psf
Directionality (Kd)0.95 h/D = 11.17
Height (h) 16.8 ft D(qz)^.5 = 5.58
Width (D)1.5 ft
Type of Surface Moderately smooth
Round
Cf =0.62
F = qz G Cf Af =16.0 Af
Af =5.8 sf
F =93 lbs
D. Trussed Towers
Height to centroid of Af (z) 15.0 ft Kz =0.575
= 0.27 Base pressure (qz) =13.4 psf
Tower Cross Section triangle
Member Shape flat Diagonal wind factor =1
Directionality (Kd)0.95 Round member factor =1.000
Triangular Cross SectionCf =2.38
F = qz G Cf Af =27.1 Af
10.0 Solid Area: Af =10.0 sf
F =271 lbs
Ultimate Wind Speed =
Dibble Engineers Inc JOB TITLE Sunset Oak Lights
1029 Market Street, Suite 200
Kirkland, WA 98033 JOB NO.SHEET NO.
(425) 828-4200 CALCULATED BY DATE
CHECKED BY DATE
Seismic Loads - cont. :Strength Level Forces Seismic Design Category (SDC)=D
Ie =1.00
CONNECTIONS Sds =1.113
Force to connect smaller portions of structure to remainder of structure
Fp = 0.133Sdswp =0.148 wp
or Fp = 0.05wp =0.05 wp Use Fp =0.15 wp wp = weight of smaller portion
Beam, girder or truss connection for resisting horizontal force parallel to member
FP = no less than 0.05 times dead plus live load vertical reaction
Anchorage of Structural Walls to elements providing lateral support
Fp = not less than 0.2KaIeWp Flexible diaphragm span Lf =
Enter Lf to calculate Fp for flexible diaphragm
Fp =0.4SdskaIeWp = 0.445 Wp, but not less than 0.2Wp (rigid diaphragm)ka= 1 Fp =0.445 Wp
but Fp shall not be less than 5 psf
MEMBER DESIGN
Bearing Walls and Shear Walls (out of plane force)
Fp = 0.4SdsIeWw =0.445 ww
but not less than 0.10 ww Use Fp =0.45 ww
Diaphragms
Fp = (Sum Fi / Sum Wi)Wpx + Vpx =(Sum Fi / Sum Wi)Wpx + Vpx
need not exceed 0.4 SdsIeWpx + Vpx =0.445 Wpx + Vpx
but not less than 0.2 SdsIeWpx + Vpx =0.223 Wpx + Vpx
ARCHITECTURAL COMPONENTS SEISMIC COEFFICIENTS
Architectural Component : Signs and Billboards
Importance Factor (Ip) : 1.0
Component Amplification Factor (ap) =2.5 h=16.8 feetComp Response Modification Factor (Rp) =3 z=0.0 feet z/h =0.00
Over-Strength Factor (Ωo) =2
Fp = 0.4apSdsIpWp(1+2z/h)/Rp =0.371 Wp
not greater than Fp = 1.6SdsIpWp =1.781 Wp
but not less than Fp = 0.3SdsIpWp =0.334 Wp use Fp =0.371 Wp
MECH AND ELEC COMPONENTS SEISMIC COEFFICIENTS Seismic Design Category D & Ip=1.0, therefore
see ASCE7 Section 13.1.4 for exceptions
Mech or Electrical Component : Wet-side HVAC, boilers, furnaces, atmospheric tanks and bins, chillers, water heaters, etc
plus other mechanical components constructed of high-deformability materials.
Importance Factor (Ip) : 1.0
Component Amplification Factor (ap) =1 h=16.8 feet
Comp Response Modification Factor (Rp) =2.5 z=50.0 feet z/h =1.00
Over-Strength Factor (Ωo) =2
Fp = 0.4apSdsIpWp(1+2z/h)/Rp =0.534 Wp
not greater than Fp = 1.6SdsIpWp =1.781 Wp
but not less than Fp = 0.3SdsIpWp =0.334 Wp use Fp =0.534 Wp
-
I~
~R PROJECTNAME Surue,,t ();..ks y hts SHEET# i / j_
DE I PROJECT# j
DIBBLE ENGINEERS INC a_ \-L\ 5 6' DATE
=sus-=JEc=---1 -----'-.,----------------
W1<\ 0\ A Se,;srnic.. 1x_'Si~n sv 8~H -------
1), ameJ-tJ -of-I\~\\\--vol-<.., : 5 '' CY
+ w, t\ c}
VJ\n~ ~\ Ju_tt. 61\ l,~ nr ! ps f :
\b'-c(
1 ov We.'j'n \---_ 3) ~
i\)O\<.. Ut(jj~ \-'.
To+al Loa.o:
I j
I
• I • I
WEIGHTS CALCULATED PER STREET LIGHT SHOP DRAWINGS
17.2
VLL = 200 # (live load)
Alight= 18"/12 * (33"/12) = 4.125 ft2
Wind = 17.2 PSF * 4.125 ft2 = 71 #
Apole= 14' * (5"/12) = 5.83 ft2
Wind = 5.83 ft2 * 16psf = 93 #
VE = 352.77# * 0.371 = 130.88 #
MWIND=(71#)*(15.4')+(93#)*(7')
= 1,744 #-'
ME=0.371*[(31#)*(15.4')+(322#)*(7')] = 1,013 #-'
VWIND=71#+93# = 164 #
LL:
Vu = (200#)*1.6 = 320#
Mu = W*H = (320#)*(16'-9") = 5,360 #-ft
LL GOVERNS
PROJECT NAME
PROJECT #
SUBJECT
SHEET #
BY
DATE
SS
D/2S/2*√2FOOTING
BASE PLATE
ANCHOR BOLT D/2 - S/2*√ (EDGE DIST)2BOLT EDGE DISTANCE CALCULATIONS
24 7.41 6.76
SSH
Sunset Oaks Lights
Bolt Spacing Diameter = 10 1/2"
Bolt Spacing = [Diameter / (2* (2)^.5)] * 2 = 7.42"
Company:Date:12/27/2021
Engineer:Page:1/6
Project:
Address:
Phone:
E-mail:
Anchor Designer™
Software
Version 3.0.7947.7
1.Project information
Customer company:
Customer contact name:
Customer e-mail:
Comment:
Project description:
Location:
Fastening description:
2. Input Data & Anchor Parameters
GeneralDesign method:ACI 318-14
Units: Imperial units
Anchor Information:
Anchor type: Bonded anchor
Material: F1554 Grade 36
Diameter (inch): 0.750
Effective Embedment depth, hef (inch): 12.000Code report: ICC-ES ESR-4057
Anchor category: -
Anchor ductility: Yes
hmin (inch): 13.75
cac (inch): 21.46
Cmin (inch): 1.75
Smin (inch): 3.00
Base MaterialConcrete: Normal-weight
Concrete thickness, h (inch): 36.00
State: Cracked
Compressive strength, f’c (psi): 4000
Ψc,V: 1.0
Reinforcement condition: B tension, B shear
Supplemental reinforcement: Not applicable
Reinforcement provided at corners: NoIgnore concrete breakout in tension: No
Ignore concrete breakout in shear: No
Hole condition: Dry concrete
Inspection: Continuous
Temperature range, Short/Long: 150/110°F
Ignore 6do requirement: Not applicable
Build-up grout pad: No
Base Plate
Length x Width x Thickness (inch): 11.00 x 11.00 x 0.25
Recommended Anchor
Anchor Name: SET-3G - SET-3G w/ 3/4"Ø F1554 Gr. 36
Code Report: ICC-ES ESR-4057
5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.comSimpson Strong-Tie Company Inc.
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
Company:Date:12/27/2021
Engineer:Page:2/6
Project:
Address:
Phone:
E-mail:
Anchor Designer™
Software
Version 3.0.7947.7
Load and Geometry
Load factor source: ACI 318 Section 5.3
Load combination: not set
Seismic design: No
Anchors subjected to sustained tension: No
Apply entire shear load at front row: No
Anchors only resisting wind and/or seismic loads: No
Strength level loads:
Nua [lb]: 0
Vuax [lb]: 320
Vuay [lb]: 0
Mux [ft-lb]: 0
Muy [ft-lb]: 5360
Muz [ft-lb]: 0
<Figure 1>
5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.comSimpson Strong-Tie Company Inc.
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
Moment:
Vu = 200 # * 1.6 = 320#
Mu = W * H = 320# * 16'-9" = 5360 #-ft
Company:Date:12/27/2021
Engineer:Page:3/6
Project:
Address:
Phone:
E-mail:
Anchor Designer™
Software
Version 3.0.7947.7
<Figure 2>
5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.comSimpson Strong-Tie Company Inc.
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
Bolt Spacing Diameter = 10 1/2"
Spacing = [Diameter / (2* (2)^.5)] * 2 = 7.42"
Company:Date:12/27/2021
Engineer:Page:4/6
Project:
Address:
Phone:
E-mail:
Anchor Designer™
Software
Version 3.0.7947.7
Shear load y,
Vuay (lb)
Anchor Tension load,
Nua (lb)
3. Resulting Anchor Forces
Shear load combined,
√(Vuax)²+(Vuay)² (lb)
Shear load x,
Vuax (lb)
0.01 80.0 80.00.0
0.02 80.0 80.00.0
3724.53 80.0 80.00.0
3724.54 80.0 80.00.0
320.0 0.0Sum7449.0 320.0
Maximum concrete compression strain (‰): 0.12
Maximum concrete compression stress (psi): 522
Resultant tension force (lb): 7449
Resultant compression force (lb): 7449
Eccentricity of resultant tension forces in x-axis, e'Nx (inch): 0.00Eccentricity of resultant tension forces in y-axis, e'Ny (inch): 0.00
Eccentricity of resultant shear forces in x-axis, e'Vx (inch): 0.00
Eccentricity of resultant shear forces in y-axis, e'Vy (inch): 0.00
<Figure 3>
4. Steel Strength of Anchor in Tension (Sec. 17.4.1)
Nsa (lb)f fNsa (lb)
19370 0.75 14528
5. Concrete Breakout Strength of Anchor in Tension (Sec. 17.4.2)
Nb = kclaÖf’chef1.5 (Eq. 17.4.2.2a)
kc la f’c (psi)hef (in)Nb (lb)
17.0 1.00 4000 9.840 33187
fNcbg =f (ANc / ANco)Yec,NYed,NYc,NYcp,NNb (Sec. 17.3.1 & Eq. 17.4.2.1b)
ANc (in2)ANco (in2)ca,min (in)Yec,N Yed,N Yc,N Ycp,N Nb (lb)f fNcbg (lb)
450.63 871.43 6.76 1.000 0.837 1.00 1.000 33187 0.65 9341
6. Adhesive Strength of Anchor in Tension (Sec. 17.4.5)
tk,cr = tk,crfshort-termKsat(f’c / 2,500)n
tk,cr (psi)fshort-term Ksat f’c (psi)n tk,cr (psi)
1310 1.00 1.00 4000 0.24 1466
Nba = l atcrpdahef (Eq. 17.4.5.2)
l a tcr (psi)da (in)hef (in)Nba (lb)
1.00 1466 0.75 12.000 41462
fNag = f (ANa / ANa0)Yec,NaYed,NaYcp,NaNba (Sec. 17.3.1 & Eq. 17.4.5.1b)
ANa (in2)ANa0 (in2)cNa (in)ca,min (in)Yec,Na Yed,Na Ycp,Na Nba(lb)f fNag (lb)
356.68 422.18 10.27 6.76 1.000 0.897 1.000 41462 0.65 20433
5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.comSimpson Strong-Tie Company Inc.
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
Company:Date:12/27/2021
Engineer:Page:5/6
Project:
Address:
Phone:
E-mail:
Anchor Designer™
Software
Version 3.0.7947.7
8. Steel Strength of Anchor in Shear (Sec. 17.5.1)
Vsa (lb)fgrout f fgroutfVsa (lb)
11625 1.0 0.65 7556
9. Concrete Breakout Strength of Anchor in Shear (Sec. 17.5.2)
Shear perpendicular to edge in x-direction:
Vbx = min|7(le / da)0.2ÖdalaÖf’cca11.5; 9laÖf’cca11.5| (Eq. 17.5.2.2a & Eq. 17.5.2.2b)
le (in)da (in)la f’c (psi)ca1 (in)Vbx (lb)
6.00 0.750 1.00 4000 14.76 32278
fVcbgx = f (AVc / AVco)Yec,VYed,VYc,VYh,VVbx (Sec. 17.3.1 & Eq. 17.5.2.1b)
AVc (in2)AVco (in2)Yec,V Yed,V Yc,V Yh,V Vbx (lb)f fVcbgx (lb)
463.61 980.36 1.000 0.792 1.000 1.000 32278 0.70 8458
Shear parallel to edge in y-direction:
Vbx = min|7(le / da)0.2ÖdalaÖf’cca11.5; 9laÖf’cca11.5| (Eq. 17.5.2.2a & Eq. 17.5.2.2b)
le (in)da (in)la f’c (psi)ca1 (in)Vbx (lb)
6.00 0.750 1.00 4000 6.76 10004
fVcbgy = f (2)(AVc / AVco)Yec,VYed,VYc,VYh,VVbx (Sec. 17.3.1, 17.5.2.1(c) & Eq. 17.5.2.1b)
AVc (in2)AVco (in2)Yec,V Yed,V Yc,V Yh,V Vbx (lb)f fVcbgy (lb)
218.21 205.64 1.000 1.000 1.000 1.000 10004 0.70 14863
10. Concrete Pryout Strength of Anchor in Shear (Sec. 17.5.3)
fVcpg = f min|kcpNag ; kcpNcbg| = f min|kcp(ANa / ANa0)Yec,NaYed,NaYcp,NaNba ; kcp(ANc / ANco)Yec,NYed,NYc,NYcp,NNb| (Sec. 17.3.1 & Eq. 17.5.3.1b)
kcp ANa (in2)ANa0 (in2)Yed,Na Yec,Na Ycp,Na Nba (lb)Na (lb)
2.0 450.63 422.18 0.897 1.000 1.000 41462 39715
ANc (in2)ANco (in2)Yec,N Yed,N Yc,N Ycp,N Nb (lb)Ncb (lb)f
450.63 182.79 1.000 1.000 1.000 1.000 10286 25359 0.70
fVcpg (lb)
35502
11. Results
Interaction of Tensile and Shear Forces (Sec. 17.6.)
Tension Factored Load, Nua (lb)Design Strength, øNn (lb)Ratio Status
Steel 3724 14528 0.26 Pass
Concrete breakout 7449 9341 0.80 Pass (Governs)
Adhesive 7449 20433 0.36 Pass
Shear Factored Load, Vua (lb)Design Strength, øVn (lb)Ratio Status
Steel 80 7556 0.01 Pass
T Concrete breakout x+320 8458 0.04 Pass (Governs)
5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.comSimpson Strong-Tie Company Inc.
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
Company:Date:12/27/2021
Engineer:Page:6/6
Project:
Address:
Phone:
E-mail:
Anchor Designer™
Software
Version 3.0.7947.7
|| Concrete breakout y+160 14863 0.01 Pass (Governs)
Pryout 320 35502 0.01 Pass
Interaction check Nua/fNn Vua/fVn Combined Ratio Permissible Status
Sec. 17.6..1 0.80 0.00 79.7%1.0 Pass
SET-3G w/ 3/4"Ø F1554 Gr. 36 with hef = 12.000 inch meets the selected design criteria.
12. Warnings
- Designer must exercise own judgement to determine if this design is suitable.
- Refer to manufacturer’s product literature for hole cleaning and installation instructions.
5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.comSimpson Strong-Tie Company Inc.
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.