HomeMy WebLinkAboutEx02_Building_Elevations,_3D_Views_and_Floor_Plans1ST FLOOR
166' - 8"
2ND FLOOR
176' - 9 3/4"8' - 0"10' - 1 3/4"PLATE HT
184' - 9 3/4"
ROOF DECK
186' - 3"
5'0x3'0
5'0x3'0
4'0x4'6 6'0X4'02'6x3'0
5'0x2'0
2'6x3'0
SG
SG
SG 5'0x4'0
E
16"x8" CRAWL SPACE
VENT, TYP.5' - 0"7' - 0"4' - 0"3' - 0"5' - 0"8' - 0"5' - 0"5' - 0"3' - 6"4' - 0"EXISTING GRADE 3' - 0"5'0x4'0
18' - 1 3/4"8' - 2 1/2"
WALL AREA: 18.1' x 8.2' = 148.4 SF
PER IRC R302.1(1), 25% MAX OPENING IN WALL ALLOWED
WHEN WALL IS 3-5' TO PROPERTY LINE.
MAX ALLOWED: 148.4 X 0.25 = 37.1 SF
PROPOSED OPENING AREA: (5' x 4') + (5' x 3') = 35 SF --> OK
5'0x2'0
R 3' - 0"R 3' - 0"R 3' - 0"
1ST FLOOR
166' - 8"
2ND FLOOR
176' - 9 3/4"
PLATE HT
184' - 9 3/4"10' - 1 3/4"8' - 0"ROOF DECK
186' - 3"
4 " / 1 '-0 "
8'0x6'0
8'0x5'0 5'0x3'04'0x4'6
3'0x5'0 3'0x5'0
3'0x5'0 3'0x5'0
SG
E
1' - 10"TRANSPARENT FASCIA-MOUNT
CABLE RAILING, MIN 3' ABOVE
FINISHED FLOOR, TYP.8' - 0"3' - 0"3' - 6"4' - 0"2' - 0"3' - 0"EXISTING GRADE
1ST FLOOR
166' - 8"
2ND FLOOR
176' - 9 3/4"
AVG GRADE
164' - 3 3/8"
MAX RIDGE HT
194' - 3 3/8"8' - 0 1/4"1' - 5 1/4"8' - 0"10' - 1 3/4"MAX PLATE HT
188' - 3 3/8"6' - 0"24' - 0"PLATE HT
184' - 9 3/4"
ROOF DECK
186' - 3"
3 1 /2 " / 1 '-0 "
5'0x3'0
3'0x5'0 3'0x5'0
8'0x4'6
6'0x8'0
5'0x5'0 4'0x3'0
3'0x7'0
SG
SG
SG
SG
CRAWL SPACE ACCESS, MIN
OPENING OF 18" X 24", WITH 16"X8"
CRAWL SPACE VENT IN DOOR8' - 0"3' - 0"7' - 0"4' - 0"2' - 6"5' - 0"8' - 0"3' - 0"PROPOSED DOWNSPOUT
TO THE APPROVED POINT
OF DISCHARGE, TYP.
EXISTING GRADE
R 3' - 0"
R 3' - 0"
1ST FLOOR
166' - 8"
2ND FLOOR
176' - 9 3/4"
AVG GRADE
164' - 3 3/8"
MAX RIDGE HT
194' - 3 3/8"
MAX PLATE HT
188' - 3 3/8"6' - 0"24' - 0"PLATE HT
184' - 9 3/4"9' - 5 1/2"8' - 0"10' - 1 3/4"ROOF DECK
186' - 3"
4" / 1'-0"
3 1 /2 " / 1 '-0 "
3'0x8'01'0x8'0
16'0x8'0
6'0x5'0
5'0x5'09'0x7'0
1'0x8'0
EXISTING GRADE
PROPOSED GRADE
SG
SG SG SG
SG
E
E
6'0x5'0
E
3' - 0"8' - 0"3' - 0"8' - 0"3' - 0"1' - 6"
METAL SIDING
HARDIE PANEL
SIDING, TYP.
HARDIE LAP
SIDING, TYP.36" MIN., TYP.36" MIN., TYP.COMPOSITE SHINGLE ROOF OVER
(2) LAYERS 30# BLDG PAPER, TYP.
WINDOWS TO HAVE U-FACTOR 0.28
FIELD VERIFY THIS HIGHER STANDARD
1
DATE:
PROJECT NO:
SCALE:
DRAWN BY:
7209 Greenwood Avenue North
Seattle, Washington 98103
206-782-2911
Fax 782-5624
CB ANDERSON
ARCHITECTS
SHEET TITLEREVISIONS:
PLLC.NOT FOR CONSTRUCTION UNLESS CITY APPROVAL STAMP APPEARS ON THIS SHEETCOPYRIGHT CB ANDERSON ARCHITECTS. ALL RIGHTS RESERVED. NOT TO BE REPRODUCED WITHOUT PERMISSION. ORIGINAL SHEET SIZE 24" X 36".CLIENT:
CONSULTANT:
Equilibria Structural
Engineering
9999 Harbour Place, Suite
107
Mukilteo, WA 98275
360-386-9476
Straight Arrow Homes, LLC
12015 NE 8th Street, Suite 5
Bellevue, WA 98005
PR21000259
B21005267
1/4" = 1'-0"
A-5
AMSTRAIGHT ARROW N 35TH ST RENTONELEVATIONS1951.0
01 OCTOBER 20211218 N 35th StreetRenton, WA 98056SCALE: 1/4" = 1'-0"
EAST ELEVATION
SCALE: 1/4" = 1'-0"
NORTH ELEVATION
SCALE: 1/4" = 1'-0"
WEST ELEVATION
SCALE: 1/4" = 1'-0"
SOUTH ELEVATION
ROOF INSTALLATION NOTE PER IBC 1507.2.2
FOR ASPHALT SHINGLE INSTALLATIONS BETWEEN 2:12 AND
4:12 SLOPES, PROVIDE (2) LAYERS UNDERLAYMENT MEETING
AND CONFORMING TO CODE STANDARDS. FASTENERS &
FLASHING TO BE PER SBC 1507.
E EGRESS WINDOW MIN. 5.7 SF NET
OPENING (MIN. 24" HIGH, 20" WIDE)
SG SAFETY GLAZING
LEGEND
SIDING MATERIAL AND COLORS:
MANUFACTURED SIDING TO BE INSTALLED PER INDUSTRY BEST PRACTICE AND
MANUFACTURER’S RECOMMENDATIONS. FLATNESS TOLERANCE TO BE < 1/8” OVER 10’.
LAP SIDING
· 5/16” SMOOTH FIBER CEMENT LAP SIDING
· MANUFACTURER: JAMES HARDIE
· 4” EXPOSURE
· PAINT: BENJAMIN MOORE CHELSEA GRAY HC-168
PANEL SIDING W/ REVEALS
· 5/16” SMOOTH FIBER CEMENT PANELS
· MANUFACTURER: JAMES HARDIE
· PAINT: BENJAMIN MOORE BLACK IRON 2120-20
· PANEL TRIM BY FRY REGLET, OR APPROVED EQUAL PER OWNER
PLATE HEIGHT NOTES:
MAX HEIGHT FROM AVERAGE GRADE LEVEL (SEE
CALCULATIONS SHEET A-1.0) TO PLATE HEIGHT IS 24'-0" PLUS
6' ADDITIONAL FOR A PITCHED ROOF W/ MIN 4:12 SLOPE.
CONTRACTOR IS RESPONSIBLE TO MONITOR
CONSTRUCTION & COMPLETION TO ENSURE COMPLIANCE.
ELEVATION NOTES:
1. PROVIDE FLASHING AT ALL DOORS,
WINDOW AND HORIZONTAL TRIM
TRANSITIONS, TYP. FLASH AT ALL ROOF
VALLEY CONDITIONS, ALL WALL TO ROOF
AND WALL TO DECK CONDITIONS, DECK
WATERPROOFING TO BE WARRANTED,
TYP.
2. INSTALL MANUFACTURED SIDING PER
MANUFACTURER'S GUIDELINES AND
CEDAR SIDING PER WESTERN RED CEDAR
LUMBER ASSOCIATION GUIDELINES, TYP.
3. GUTTERS & DOWNSPOUTS TO LEAD TO
TIGHTLINE CONNECTION TO CITY
APPROVED DRAINAGE SYSTEM
CASEMENT OR AWNING WINDOWS USED FOR
EGRESS MUST INCLUDE HARDWARE THAT
ALLOWS THE WINDOW TO OPEN A MINIMUM
OF 90 DEGREES AND PROVIDES FULL WIDTH
CLEARANCE IN FULLY OPEN POSITION.
GUARDRAIL NOTE:
- GUARDS DESIGNED TO RESIST A 200 LB CONCENTRATED
LOAD ON THE TOP RAIL AND 50 PSF ON ALL GUARDRAIL
INFILL COMPONENTS, TYP.
- PROVIDE GUARD RAIL IF THERE IS MORE THAN 30" LEVEL
CHANGE, GUARD RAIL HEIGHT TO BE 36" MIN. W/ LESS
THAN 4" BTWN BALUSTERS, TYP.
EXHAUST DUCT OUTLETS MUST TERMINATE NOT LESS
THAN 3' FROM OPENINGS INTO BUILDINGS, TYP.
METAL SIDING
· 24 GAUGE STEEL, FLAT SHEET
· MANUFACTURER: THE BRYER COMPANY
· PAINT: NIGHT SKY, NATURAL FX COATING
SOFFIT
· CEDAR T&G W/ CLEAR COAT
FASCIA
· PAINT: BENJAMIN MOORE BLACK IRON 2120-20
Notes: - Follow all installation instructions per manufactures.
1 27 DECEMBER 2021
RECEIVED
Clark Close 01/24/2022
PLANNING DIVISION
Exhibit 2
DocuSign Envelope ID: BE699953-BA0C-4D42-93F9-BAF4560A83BC
DATE:
PROJECT NO:
SCALE:
DRAWN BY:
7209 Greenwood Avenue North
Seattle, Washington 98103
206-782-2911
Fax 782-5624
CB ANDERSON
ARCHITECTS
SHEET TITLEREVISIONS:
PLLC.NOT FOR CONSTRUCTION UNLESS CITY APPROVAL STAMP APPEARS ON THIS SHEETCOPYRIGHT CB ANDERSON ARCHITECTS. ALL RIGHTS RESERVED. NOT TO BE REPRODUCED WITHOUT PERMISSION. ORIGINAL SHEET SIZE 24" X 36".CLIENT:
CONSULTANT:
Equilibria Structural
Engineering
9999 Harbour Place, Suite
107
Mukilteo, WA 98275
360-386-9476
Straight Arrow Homes, LLC
12015 NE 8th Street, Suite 5
Bellevue, WA 98005
PR21000259
B21005267
A-6
AMSTRAIGHT ARROW N 35TH ST RENTON3D VIEWS1951.0
01 OCTOBER 20211218 N 35th StreetRenton, WA 980563D View 3
3D View 1 3D View 2
3D View 4
DocuSign Envelope ID: BE699953-BA0C-4D42-93F9-BAF4560A83BC
UP
SMOKE DETECTOR
EXHAUST FAN WITH
CFM CALL-OUT BELOW
SD
EGRESS WINDOW MIN. 5.7 SF
NET OPENING (MIN. 24"
HIGH, 20" WIDE)
E
SAFETY GLAZINGSG
CLOSETCLST.
SDC COMBINED SMOKE DETECTOR &
CARBON MONOXIDE ALARM
HEAT DETECTORHD60' - 0"50' - 0"7' - 0"26' - 6"13' - 6"
19' - 0 1/2"8' - 3 1/2"6' - 8 1/2"11' - 5 1/2"5' - 6"7' - 3 1/2"3' - 6"3' - 6"22' - 8 1/2"7' - 7"4' - 6"9' - 0"16' - 11"9' - 0"7' - 0"
40' - 0"12' - 0"5' - 11"6' - 0"29' - 1"1' - 0"
1' - 6"
4' - 3"12' - 0"4' - 3"
2' - 3"9' - 0"2' - 3"
1' - 4"
GARAGE
OFFICE/ JUNIOR
SUITE
LIVING
DINING
KITCHEN
UP
UP
6R
DN
COAT
5' - 6"4' - 6"
4' - 8 1/2"
BATHROOMPOWDER
2' - 1"2' - 7"
COVERED PATIO
3' - 7"19' - 1 1/2"STORAGE
19' - 6 1/2"17' - 7"30"
PANTRY
A
A-4
COV. PORCH CABINETRYCONCRETE
36" REF.30" DW13' - 6"5' - 0"1' - 0"
WOOD FRAME
ROOF ABOVE
DECORATIVE OR
STRUCTURAL BEAMS ABOVE
CONCRETE
3' - 6"1/4" / FOOT SLOPEDECK EDGE ABOVE
1' - 6"20' - 1"8' - 2 1/2"28' - 8 1/2"1' - 6"2' - 6"6' - 0"10' - 11"4' - 0"5' - 3 1/2"1' - 7 1/4"5' - 0"1' - 7 1/4"2' - 6"2' - 6"6' - 7"5' - 0"3' - 6"1' - 6"6' - 0"1' - 6"
2' - 0"16' - 0"2' - 7 1/2"5' - 3"7 1/2"
2' - 0"8' - 0"2' - 0"
3' - 3 3/4"3' - 0"3 1/2"3' - 0"3 1/2"3' - 0"3 1/2"3' - 0"3' - 3 3/4"1' - 4"6' - 0"1' - 8"1' - 3"3' - 0"1' - 8"10' - 6"5' - 0"9' - 4"3' - 0"1' - 3"4' - 0"WHTANKLESS
WATER HEATER
50
FACTORY BUILT FIREPLACE TO BE UL LISTED,
LABELED AND INSTALLED WITH
CONDITIONS OF LISTING. FACTORY BUILT
FIREPLACE MUST BE TESTED IN
ACCORDANCE WITH UL 127, WASHINGTON
CERTIFIED GAS FIREPLACE.
SEPARATE GARAGE
FROM LIVING SPACE
WITH * NOTE THIS SHEET.
R-21 INSUL. AT WALL
AND R-38 INSUL. AT
CEILING BTWN.
GARAGE & HEATED
SPACE, TYP.
*
SLAB ON
GRADE
1/8" SL/FT.EXHAUST DUCT
OUTLETS AT 1ST
FLOOR TERMINATE
OUT WALL, TYP.
CRAWL SPACE ACCESS, MIN
OPENING OF 18" X 24", WITH 16"X8"
CRAWL SPACE VENT IN DOOR
50
100
2'10X6'8
2'6x6'82'6x6'82'6x6'8
3'0x8'01'0x8'0
16'0x8'0
6'0x5'0 5'0x3'05'0x3'03'0x5'03'0x5'04'0x4'62'6x6'88'0x6'0
6'0X4'02'6x3'02'6x6'86'0x8'01'0x8'0
3'0x5'0 3'0x5'0 3'0x5'0 3'0x5'0
3' sill @ landingCLST.
*SGSGSGSG SGE
SDC
SD
MIN 36" HIGH
GUARDRAIL, TYP.
SG
B
A-4 19' - 6"1/4" / FT. SLOPE16"x8" CRAWL SPACE
VENT, TYP.
1-HOUR RATED WALL
ASSEMBLY WITHIN 2-5'
FROM PROPERTY LINE
1-HOUR RATED WALL ASSEMBLY WITHIN 2-5' FROM PROPERTY LINEPRE-CAST
CONCRETE STAIR
TREADS, WOOD
STRINGERS PER
STRUCTURAL, TYP.
16"x8" CRAWL SPACE
VENT, TYP.
6' - 5"3' - 10"
WALL ABOVE
A-8
10
A-8
9
A-9
3
A-9
7
A-8
11
HD 5'0x4'0 SGA-8
10
TYP.3' - 0"DN
14' - 4 1/2"19' - 2 1/2"
12' - 7 1/2"11' - 5 1/2"5' - 6"WD19' - 6"9' - 3"9' - 0"2' - 3"1' - 6"MASTER
BEDROOM
COVERED DECK
BEDROOM 38' - 0"13' - 11"5' - 0"7' - 3 1/2"BATHR.
W.I.C.
MASTER
BATHROOM
LINEN
2' - 1"6' - 8"7' - 0"5' - 6"5' - 8 1/2"
13' - 3 1/2"
5' - 0"8' - 3 1/2"11' - 8 1/4"2' - 1"2' - 1"11' - 8 1/4"4' - 6"
3' - 0"4' - 6"
LINEN
BEDROOM 2
CLOSET
CLOSET
BEDROOM 1
LAUNDRY
CLOSET
COMMON SPACE/ DEN3' - 6"6' - 0"10' - 2"DN
3' - 1"6' - 4"5' - 0"4' - 0"
A
A-4
60" TUB
4'X6' SHOWER
5' - 0"7' - 7 1/2"10' - 1 1/2"3' - 6"2' - 1"1' - 9"
WALL BELOW
3' - 6"5' - 0"6' - 7"2' - 6"2' - 6"1' - 7 1/4"5' - 0"1' - 7 1/4"4' - 3 1/2"5' - 0"10' - 11"5' - 0"3' - 6"1' - 6"20' - 1"8' - 2 1/2"28' - 8 1/2"58' - 6"1' - 6"4' - 0"3' - 6"8' - 0"3' - 6"
19' - 6"20' - 6"
1' - 9"5' - 0"12' - 9"3' - 6"8' - 0"16' - 10"4' - 0"1' - 8"40' - 0"
1' - 5"5' - 0"2' - 10"1' - 6"6' - 0"1' - 6"11' - 0"34' - 0"1' - 5"5' - 0"2' - 7"9' - 0"2' - 0"9' - 0"8' - 6"
E
2'8x6'8
2'6x6'8
2'4x6'8
2'4x6'85'0x3'05'0x5'0 5'0x2'08'0x5'0
8'0x4'62'6x6'8
5'0x6'82'6x6'82'6x6'82'6x6'82'8x6'85'0x6'8
5'0x6'8
2'6x6'8
2'10x6'85'0x3'0 5'0x5'02'4x6'8
4'0x4'6
4'0x3'03'0x7'0
9'0x7'0 SG SG2'6x3'0SG
SG
SGSGE
EE
50
90
50
50
CONTINOUS WHOLE
HOUSE FAN
EXHAUST DUCT OUTLETS AT
2ND FLOOR TERMINATE
OUT ROOF, TYP.
SDC
SD
SD
SD
SD
MIN 22"X30"
ATTIC ACCESS W/ R-38
INSULATION PER
DETAILS
MIN 36" HIGH
GUARDRAIL, TYP.
ROOF ABOVE
ROOF ABOVE
1' - 4"
6'0x5'03' - 5"5'0x4'0B
A-4
1-HOUR RATED WALL
ASSEMBLY WITHIN 2-5'
FROM PROPERTY LINE
1/4" / FT. SLOPE5" FASCIA
GUTTER, TYP.
FACE-MOUNTED METAL
GUARDRAIL PER STRUCTURAL,
MIN 36" ABOVE FFE, TYP.
MEMBRANE DECKING PER
DETAILS, SLOPE 1/4"/ FT. , TYP.
1-HOUR RATED EAVE REQ'D
WHEN LESS THAN 5' FROM
PROPERTY LINE, TYP.
7' - 4"3' - 10"
5" DN
A-9
5
A-10
2
CODE COMPLIANT PREFAB
METAL SPIRAL STAIRS BY
OTHERS, INSTALL PER
MANUFACTURER, SEE
NOTES ON SHEET A-43 1/2" / 1'-0"2'X4'
SKYLIGHTS
5'0x2'0MIN R-38 INSULATION
REQUIRED @ ROOF
A-8
7
DATE:
PROJECT NO:
SCALE:
DRAWN BY:
7209 Greenwood Avenue North
Seattle, Washington 98103
206-782-2911
Fax 782-5624
CB ANDERSON
ARCHITECTS
SHEET TITLEREVISIONS:
PLLC.NOT FOR CONSTRUCTION UNLESS CITY APPROVAL STAMP APPEARS ON THIS SHEETCOPYRIGHT CB ANDERSON ARCHITECTS. ALL RIGHTS RESERVED. NOT TO BE REPRODUCED WITHOUT PERMISSION. ORIGINAL SHEET SIZE 24" X 36".CLIENT:
CONSULTANT:
Equilibria Structural
Engineering
9999 Harbour Place, Suite
107
Mukilteo, WA 98275
360-386-9476
Straight Arrow Homes, LLC
12015 NE 8th Street, Suite 5
Bellevue, WA 98005
PR21000259
B21005267
1/4" = 1'-0"
A-3
AMSTRAIGHT ARROW N 35TH ST RENTONFLOOR PLANS1951.0
01 OCTOBER 20211218 N 35th StreetRenton, WA 98056LEGEND
NORTH
SCALE: 1/4" = 1'-0"
1ST FLOOR
SCALE: 1/4" = 1'-0"
2ND FLOOR
NORTH
WHOLE HOUSE FAN VENTILATION
CONTINUOUS WHOLE HOUSE FAN MIN 90 CFM
SEE SHEET A-2 VENTILATION & AIR QUALITY NOTES
GUARDRAIL NOTE:
- GUARDS DESIGNED TO RESIST A 200 LB CONCENTRATED LOAD ON THE
TOP RAIL AND 50 PSF ON ALL GUARDRAIL INFILL COMPONENTS, TYP.
- PROVIDE GUARD RAIL IF THERE IS MORE THAN 30" LEVEL CHANGE,
GUARD RAIL HEIGHT TO BE 36" MIN. W/ LESS THAN 4" BTWN BALUSTERS, TYP.
EXHAUST DUCT OUTLETS MUST TERMINATE NOT LESS THAN 3' FROM
OPENINGS INTO BUILDINGS, TYP.
SMOKE ALARMS:
- SMOKE ALARMS SHALL NOT LOCATED WITHIN 3' OF A DOOR OR OPENING OF
A BATHROOM OR SHOWER ROOM.
- IONIZATION SMOKE ALARMS SHALL NOT BE INSTALLED WITHIN 20 FEET OF A
PERMANENT INSTALLED COOKING APPLIANCE. THE DISTANCE IS CUT IN HALF TO
10 FEET FOR IONIZATION SMOKE ALARMS WITH AN ALARM-SILENCING SWITCH.
- PHOTOELECTRIC SMOKE ALARMS SHALL NOT BE INSTALLED WITHIN 6 FEET OF A
PERMANENT INSTALLED COOKING APPLIANCE.
ENERGY CODE NOTES:
PER ENERGY CREDIT OPTION 5.5:
ELECTRIC HEAT PUMP WATER HEATER MEETING THE STANDARDS FOR TIER I II
OF NEEA'S ADVANCED WATER HEATING SPECIFICATION
CRAWL SPACE VENT CALCULATION:
1500 SF / 300 = 5 SF X 144 IN. = 720 SQ IN / 72.5 SQ. IN. (16"X8" VENT) = 9.93
PROPOSED: (10) 16"X8" VENTS
GARAGE AREA SEPARATION NOTES
1. GARAGE SHALL BE SEPARATED FROM RESIDENCE BY 1/2"
TYPE 'X' GWB @ WALLS.
2. GARAGE BELOW HABITABLE ROOM SHALL BE SEPARATED
BY (2 LAYERS) 5/8" TYPE 'X' GWB FOR TJI FRAMING, (1
LAYER) 5/8" TYPE 'X' GWB FOR SOLID LUMBER.
3. STRUCTURE SUPPORTING FLOOR-CEILING ASSEMBLY
SHALL BE PROTECTED BY 1/2" TYP 'X' GWB.
4. 20 MINUTE OR SELF-CLOSING, TIGHT FITTING, 1 3/8"
SOLID CORE DOOR, TYP. AT GARAGE TO LIVING SPACE.
NOTES:
R303.7
INTERIOR STAIRWAYS SHALL BE PROVIDED WITH AN ARTIFICIAL LIGHT SOURCE TO
ILLUMINATE THE LANDINGS AND TREADS. THE LIGHT SOURCE SHALL BE CAPABLE OF
ILLUMINATING TREADS AND LANDINGS TO LEVELS OF NOT LESS THAN 1 FOOT-
CANDLE (11 LUX) AS MEASURED AT THE CENTER OF TREADS AND LANDINGS. THERE
SHALL BE A WALL SWITCH AT EACH FLOOR LEVEL TO CONTROL THE LIGHT SOURCE
WHERE THE STAIRWAY HAS SIX OR MORE RISERS.
R303.8
EXTERIOR STAIRWAYS SHALL BE PROVIDED WITH AN ARTIFICIAL LIGHT SOURCE
LOCATED AT THE TOP LANDING OF THE STAIRWAY. EXTERIOR STAIRWAYS PROVIDING
ACCESS TO A BASEMENT FROM THE OUTDOOR GRADE LEVEL SHALL BE PROVIDED
WITH AN ARTIFICIAL LIGHT SOURCE LOCATED AT THE BOTTOM LANDING OF THE
STAIRWAY.
R303.7.1
WHERE LIGHTING OUTLETS ARE INSTALLED IN INTERIOR STAIRWAYS, THERE SHALL BE A
WALL SWITCH AT EACH FLOOR LEVEL TO CONTROL THE LIGHTING OUTLET WHERE THE
STAIRWAY HAS SIX OR MORE RISERS. THE ILLUMINATION OF EXTERIOR STAIRWAYS
SHALL BE CONTROLLED FROM INSIDE THE DWELLING UNIT.
STAIR NOTE:
7-3/4" MAX. RISER HEIGHT AND MIN. 10" TREAD DEPTH
CONTINUOUS 1.5" DIA. HANDRAIL ON ONE SIDE
HANDRAIL NOTE:
1) LOCATION AT 34-38 INCHES ABOVE THE STAIR NOSING.
2) GRASP DIMENSION BETWEEN 1-1/4-2 INCHES.
3) PROVIDE CONTINUOUS HANDRAIL OR TERMINATE AT
NEWEL POSTS OR SAFETY TERMINAL.
*
NOTES:
R314.2.3
A HEAT DETECTOR OR HEAT ALARM RATED FOR THE AMBIENT OUTDOOR
TEMPERATURES AND HUMIDITY SHALL BE INSTALLED IN NEW GARAGES THAT ARE
ATTACHED TO OR LOCATED UNDER NEW AND EXISTING DWELLINGS. HEAT
DETECTORS AND HEAT ALARMS SHALL BE INSTALLED IN A CENTRAL LOCATION AND
IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS.