HomeMy WebLinkAboutR-4214471A
LOCATION MAP
w w w
0
—T—T T T
PSESECONDARY
JUNCTION BOX 244
PER PSE Z.
#123TC, 2-#8, #8G �
PSE UNDERGROUND
TRANSFORMER VAULT
ELECTRICAL WIRING SCHEMATIC
#12-3TC
#BG
LLJ
U
Q Z
0 � v
LU Z
TALBOT RD S
LU w (TAL-B-LINE)
J F-
w
-w IE w w w w w
LU 4 \� 1 1 STATION 60361 (IB) 3
8 4 TIER 1
1Y\ o
SD
v
- — — —r cn-=l 477-171V- — — — — —
— T 717V
SS SS� PEXISTNG PSE ,�1— —UNDERGROUND PSE SECONDARY 2 3 1 3 5 1 METRO TECH PYLONVAULFORMER I JUNCTION BOX
METRO RAPIDRIDE
SHELTER
WIRING SCHEDULE
RUN NO.
ACONDUIT
SIZE
SHELTER LIGHTS
TECH PYLON
GROUND
SERVICE
PULL TAPE
REMARKS
1
2" RGS METRO SERVICE
244
2" RGS METRO ELEC.
#12JTC
248
#8G
2
2" RGS METRO ELEC.
1
SPARE
3
3/4" RGS METRO ELEC.
#12-3TC
LABEL CONDUCTORS WITH "SHELTER
LIGHTS"
4
1"RGS METRO ELEC.
2-#8
#8G
LABEL CONDUCTORS WITH "TECH
PYLON"
5
1.5' PVC METRO ITS
1
SPARE
6
2" PVC METRO ITS
1
SPARE
7
PER PSE
PER PSE
60% SUBMITTAL Jacobs
V�' o4Tvggpi C$
2F92
g
REVISION
Aconcord
BY APP'N DATE �fWVAL�
ENGINEERING
IB STATION
PANEL: #
VOLTAGE RATING: 120 VOLTS,1 PHASE, 2 WIRE
BUS RATING: 100 AMPS
MAIN BREAKER: 60 AMPS
FEED: BOTTOM
FAULT CURRENT: AMPS
INTERRUPTING CAPACITY: 22,000 AMPS
CIRCUIT DESCRIPTION
VA
CKT
BRKR
TECH PYLON
84
1
1120
SHELTER LIGHTS
20
2
1120
SPACE
3
SPACE
4
SPACE
5
SPACE
6
GFCI
180
7
1
1/20
CONNECTED LOAD = (84+20+180) = 284 VA= 2,367 AMPS AVERAGE
CONTINUOUS LOAD = ((84+20)'1.25+180) = 310 VA =
2.583 AMPS AVERAGE
L1 King County
METRO
GENERALNOTES
1. THE 60% DESIGN REFLECTS THE ASSUMPTION THAT PSE WILL
PROVIDE CONDUIT(S) FROM THE PRIMARY SERVICE POINT TO A
SECONDARY SERVICE JUNCTION BOX FOR STATION SERVICE
CONNECTIONS PRIOR TO I LINE RAPIDRIDE CONSTRUCTION.
2. HAND DIGGING OR EXCAVATION BY VACTOR MAY BE REQUIRED FOR
CONDUIT INSTALLATION IN AREAS WHERE EXISTING UNDERGROUND
UTILITIES AND/OR TREE ROOTS ARE PRESENT,
3. SEE 1S1.20 FOR STATION PLANS AND AMENITIES DETAILS.
CONSTRUCTION NOTES
OTRENCH AND INSTALL CONDUIT. ADJUST ROUTING OF TRENCH
AND CONDUIT TO AVOID UTILITIES.
OBORE AND INSTALL CONDUIT. ADJUST BORE TO AVOID UTILITIES
AS NEEDED. RESTORE AREA DISTURBED BY BORING OPERATIONS
BACK TO PRECONSTRUCTION CONDITION.
OPROVIDE AND INSTALL 60A, 120V METRO NON -METERED ELECTRICAL
SERVICE PEDESTAL, SEE 1E2.01 FOR MOUNTING AND FOUNDATION
DETAIL. THE FRONT DOOR OF THE CABINET SHALL BE ORIENTED AS
SHOWN BY "F" ON THE PLANS.
O4 PROVIDE AND INSTALL WSDOT TYPE 2 JUNCTION BOX PER WSDOT
STANDARD PLAN J40.1D-04. LABEL JUNCTION BOX "METRO".
LEGEND
Q
METRO ELECTRICAL SERVICE PEDESTAL
F
Q
JUNCTION BOX TYPE 2
-----
BURIED I CONCEALED CONDUIT
METRO BUS SHELTER
A
METRO TECHNOLOGY PYLON
0' 10, 20'
SCALE: 1' =10'
METRO TRANSIT CAPITAL DIVISION DATE.
RAPIDRIDE 1 LINE NOVEMBER 2021
RENTON SEGMENT DMWNGNO
ELECTRICAL SITE PLAN 1E1.04
ID# 60361 MEETNO
OF
471 XXXX
T-4214171
R-4214471