November 4, 2016
File No. 201614
Mr. Wentian Lan
17630 - 108th Avenue SE
Renton, WA 98055
Subject: Infiltration Evaluation
Proposed Development
Infiltration Assessment
17630 - 108th Avenue SE, Renton, WA
Dear Mr. Lan,
As requested, PanGEO conducted field infiltration testing to evaluate infiltration
characteristics at the above site in the City of Renton, Washington. The following
sections documents the field infiltration testing procedure, the measured field infiltration
rates, subsurface conditions encountered at the test locations, and the recommended long-
term (design) infiltration rate.
SITE DESCRIPTION AND PROJECT UNDERSTANDING
The subject site is located at 17630 – 108th Avenue SE in the City of Renton, Washington
(see Vicinity Map, Figure 1). The site is bounded by 108th Avenue SE on the west, by
109th Avenue SE on the east, by a commercial building on the north, and by commercial
and residential buildings on the south (see Site and Exploration Plan, Figure 2). The site
is currently occupied by a one-story building surrounded by asphalt pavement and
landscaping. The site is practically flat.
Based on information provided to us, we understand that you plan to remodel and expand
the existing building. We also understand that the current drainage design will include
new permeable asphalt pavement and a detention tank. As such, evaluation of infiltration
feasibility of the on-site soils and infiltration rates is needed for the drainage design.
Infiltration Evaluation
Proposed Additions: 17630 – 108th Avenue SE, Renton, WA
November 4, 2016
201614 17630 108th Ave SE Infiltration Rpt Page 2 PanGEO, Inc.
SUBSURFACE EXPLORATIONS
Three Pilot infiltration tests (PIT-1 through PIT-3) were conducted on October 28, 2016,
to measure field infiltration rates at the site. The infiltration test pits were excavated with
hand tools. Additionally, three test pits (TP-1 through TP-3) were excavated on
November 3, 2016 to further explore soil conditions beneath the infiltration pit depth with
a backhoe. The approximate test locations were measured from existing structures and
site features (Figure 2). The test pits were excavated to about 7 feet below existing
ground surface and the infiltration test was completed at 2 feet depth.
An engineer from Cascade GeotechNW was present during the field explorations to
observe the test excavations and to describe and document the soils encountered in the
explorations. Summary logs of the test pit excavations are included in the Appendix A
to provide descriptions of the materials encountered, depths to soil contacts, and depths
of seepage or caving, if present, observed in the test excavation sidewalls. The relative
in-situ density of cohesionless soils, or the relative consistency of fine-grained soils, was
estimated from the excavating action of the excavator, probing the sidewalls with a ½-
inch diameter steel rod, and the stability of the test excavation sidewalls. Where soil
contacts were gradual or undulating, the average depth of the contact was recorded in the
log. After each test pit was completed, the excavation was backfilled with the excavated
soils and the surface was tamped and re-graded smooth.
IN-SITU INFILTRATION TESTING PROCEDURE
An engineer from Cascade GeotechNW conducted the field infiltration tests. The
infiltration tests were performed in general accordance with the guidelines of the King
County, Washington, Surface Water Design Manual Reference 6-A: Single-Ring
Percolation Test Procedure. The test results are summarized in Table 1 on pages 3 and
4. The test locations were selected based the input from the civil engineer, site conditions,
and the proposed drainage design. The approximate locations of the infiltration tests are
shown on Figure 2.
The infiltration testing consisted of excavating to approximately 2 feet below existing
grade, initially pre-socked overnight, then placing a 3-foot diameter ring at the bottom of
the excavation, seating the ring into the ground on the testing day. Water levels were
measured using a measuring tape with 1/16 inch increments. Plate 1 on page 3 shows the
Infiltration Evaluation
Proposed Additions: 17630 – 108th Avenue SE, Renton, WA
November 4, 2016
201614 17630 108th Ave SE Infiltration Rpt Page 3 PanGEO, Inc.
general infiltration test setup. As per the test requirements, the ring was filled with water
and a constant head of approximately 6
inches was maintained for a 4 hour pre-
soaking period on the test day.
Following the 4-hour pre-soak period,
the water is turned off and the head is
allowed to drop for 30 minutes. After 30
minutes, the change in water level is
recorded and the ring is refilled to 6
inches depth. This procedure is repeated
until consecutive measurements vary by
no more than 1/16 inch. The field
infiltration rate is then calculated based on the final measured water level drop.
SUBSURFACE CONDITIONS
The test pits generally encountered 0.5 to 1 foot of brown, loose, very moist, silty sand
silt (Topsoil). Below the topsoil, approximately 1 to 1.5 feet of gray, loose, very moist,
fine to medium sand was encountered. Below the gray sand layer, the test pits
encountered brown-gray, moist to very moist, medium dense to dense, silty sand that
extended to the bottom of the test pits at 7 feet below the surface. No groundwater was
observed in the test pit at the time of excavation.
IN-SITU INFILTRATION TEST RESULTS
Infiltration testing data and results are summarized in Table 1 below.
Table 1 – Summary of Field Infiltration Test Data
Time Head Loss (Inches) Percolation Rate (Minutes/Inch)
PIT -1
11:45-12:15 11/16 43.6
12:15-12:45 10/16 48.0
12:45-13:15 9/16 53.3
Plate 1 – Infiltration test set-up at PIT-3
Infiltration Evaluation
Proposed Additions: 17630 – 108th Avenue SE, Renton, WA
November 4, 2016
201614 17630 108th Ave SE Infiltration Rpt Page 4 PanGEO, Inc.
13:15-13:45 9/16 53.3
13:45-14:15 9/16 53.3
14:15-14:45 9/16 53.3
PIT -2
11:50-12:20 12/16 40.0
12:20-12:50 11/16 43.6
12:50-13:20 10/16 48.0
13:20-13:50 10/16 48.0
13:50-14:20 10/16 48.0
14:20-14:50 10/16 48.0
PIT -3
12:00-12:30 10/16 48.0
12:30-13:00 9/16 53.3
13:00-13:30 8/16 60.0
13:30-14:00 8/16 60.0
14:00-14:30 8/16 60.0
14:30-15:00 8/16 60.0
Infiltration Evaluation
Proposed Additions: 17630 – 108th Avenue SE, Renton, WA
November 4, 2016
201614 17630 108th Ave SE Infiltration Rpt Page 5 PanGEO, Inc.
The last water level drop is used to calculate the field percolation rate. Based on three
infiltration tests, it is our opinion that a percolation rate of 60.0 minutes/inch may be
conservatively used. This percolation rate is equivalent to an infiltration rate of 1.0
inches/hour. For design purposes, the field infiltration rates must be reduced through
correction factors, as discussed in the following section.
DESIGN INFILTRATION RATE
The infiltration rates measured in the field should be reduced through correction factors
to account for uncertainties in the test method used, depth to the water table or
impervious strata, the geometry of the infiltration facility, and degree of influent control
to prevent siltation and bio-buildup. The simplified method outlined in the King County
Surface Water Design Manual (KCSWDM, 2009) was used to estimate the maximum
design infiltration rate. The simplified method equation is provided below:
Idesign = Imeasured x Ftesting x Fgeometry x Fplugging (KCSWDM Eq 5-11)
The following values were used to conservatively reduce the field infiltration rate:
Imeasured = 1.0 inches per hour
Ftesting = 0.35 (for small-scale testing)
Fgeometry = 1 (D=3 feet, W=3 feet)
Fplugging = 0.9 (for medium sands)
Therefore, we conservatively recommend a long-term (design) infiltration rate of 0.315
inches per hour for the proposed permeable pavement design. The infiltration testing was
performed at approximately 2 feet. For design purpose, the design infiltration trench
depth should be at 1.5-2 feet below the existing grade.
LIMITATIONS
This report has been prepared for the exclusive use of Mr. Wentian Lan and his other
consultants for specific application to the proposed development. This report is intended
to provide infiltration feasibility and recommendations based on a site reconnaissance,
field infiltration testing, and our understanding of the project. The study was performed
using a mutually agreed-upon scope of work.
Infiltration Evaluation
Proposed Additions: 17630 – 108th Avenue SE, Renton, WA
November 4, 2016
201614 17630 108th Ave SE Infiltration Rpt Page 6 PanGEO, Inc.
Variations in soil conditions may exist between the locations of the explorations and the
actual conditions underlying the site. The nature and extent of soil variations may not be
evident until construction occurs. If any soil conditions are encountered at the site that
are different from those described in this report, we should be notified immediately to
review the applicability of our recommendations. Additionally, we should also be
notified to review the applicability of our recommendations if there are any changes in
the project scope.
The scope of our work does not include services related to construction safety
precautions. Our recommendations are not intended to direct the contractors’ methods,
techniques, sequences or procedures, except as specifically described in our report for
consideration in design. Additionally, the scope of our work specifically excludes the
assessment of environmental characteristics, particularly those involving hazardous
substances. We are not mold consultants nor are our recommendations to be interpreted
as being preventative of mold development. A mold specialist should be consulted for all
mold-related issues.
This report has been prepared for planning and design purposes for specific application to
the proposed project in accordance with the generally accepted standards of local practice
at the time this report was written. No warranty, express or implied, is made.
This report may be used only by the client and for the purposes stated, within a
reasonable time from its issuance. Land use, site conditions (both off and on-site), or
other factors including advances in our understanding of applied science, may change
over time and could materially affect our findings. Therefore, this report should not be
relied upon after 24 months from its issuance. Cascade Group should be notified if the
project is delayed by more than 24 months from the date of this report so that we may
review the applicability of our conclusions considering the time lapse.
It is the client’s responsibility to see that all parties to this project, including the designer,
contractor, subcontractors, etc., are made aware of this report in its entirety. The use of
information contained in this report for bidding purposes should be done at the
contractor’s option and risk. Any party other than the client who wishes to use this report
shall notify Cascade GeotechNW of such intended use and for permission to copy this
report. Based on the intended use of the report, Cascade GeotechNW may require that
Infiltration Evaluation
Proposed Additions: 17630 – 108th Avenue SE, Renton, WA
November 4, 2016
201614 17630 108th Ave SE Infiltration Rpt Page 7 PanGEO, Inc.
additional work be performed and that an updated report be reissued. Noncompliance
with any of these requirements will release Cascade Group from any liability resulting
from the use this report.
CLOSURE
We appreciate the opportunity to be of service and trust that the information outlined in
this letter meets your need at this time. Please call if you have any questions.
Sincerely,
H. Michael Xue, P.E.
Principal Geotechnical Engineer
Enclosures:
Figure 1 Vicinity Map
Figure 2 Site and Exploration Plan
Appendix A Summary Test Pit Logs
A-1 thr. A-3 Logs of Test Pits TP-1 through TP-3
Infiltration Evaluation
Proposed Additions: 17630 – 108th Avenue SE, Renton, WA
November 4, 2016
201614 17630 108th Ave SE Infiltration Rpt Page 8 PanGEO, Inc.
REFERENCES:
Booth, D. B., Troost, K. A., and Wisher, A. P., 2007, The Geologic Map of King County,
Washington: scale 1:100,000.
King County Department of Natural Resources and Parks, Surface Water Design
Manual, 2009.
Figure No.Project No.201614
Infiltration Evaluation
17630 - 108th Avenue SE
Renton, Washington
1file.grf w/ file.dat 11/4/16 (10:18) SDDBase Map: Google Maps
VICINITY MAP
SITE
Cascade GeotechNW
Not to Scale
Infiltration Evaluation17630 - 108th Avenue SERenton, WashingtonSITE AND EXPLORATIONS PLAN2016142Original Contours.grf 11/4/16 (11:20) AAEProject No. Figure No.Note:Basemap modified from Civil Utility Plan prepared by Tatu Consulting Engineers dated July 2016.Approx. PIT LocationApprox. Test Pit LocationLegend:Appro. Scale:1" = 30'TP-3TP-2TP-3PIT-1TP-1PIT-3PIT-2PIT-1Cascade GeotechNW
APPENDIX A
SUMMARY TEST PIT LOGS
201614 17630 108th Ave SE Infiltration Rpt Page A-1 Cascade GeotechNW
Test Pit TP-1
Approximate ground surface elevation: N/A
Ground Surface Conditions: Bark
Depth (ft) Material Description
0 – 1 Loose, brown-dark brown, silty SAND (SM), very moist (Topsoil)
1 - 2 Loose, gray, fine to medium SAND (SP), very moist
2 – 7 Medium dense to dense, brown, silty SAND (SM), trace gravel, moist
to very moist
Test Pit terminated approximately 7 feet below ground surface.
No caving and groundwater/seepage observed in the test pit.
201614 17630 108th Ave SE Infiltration Rpt Page A-2 Cascade GeotechNW
Test Pit TP-2
Approximate ground surface elevation: N/A
Ground Surface Conditions: Grass
Depth (ft) Material Description
0 – 0.5 Loose, brown, silty SAND (SM), trace roots, very moist (Topsoil)
0.5 - 2 Loose, gray, fine to medium SAND (SP), very moist
2 – 7 Medium dense to dense, brown-gray, silty SAND (SM), trace gravel,
moist to very moist
Test Pit terminated approximately 7 feet below ground surface.
No caving and groundwater/seepage observed in the test pit.
201614 17630 108th Ave SE Infiltration Rpt Page A-3 Cascade GeotechNW
Test Pit TP-3
Approximate ground surface elevation: N/A
Ground Surface Conditions: Grass
Depth (ft) Material Description
0 – 1 Loose, brown-dark brown, silty SAND (SM), trace roots, very moist
(Topsoil)
1 - 2 Loose, gray, fine to medium SAND (SP), very moist
2 – 7 Medium dense to dense, gray-brown, silty SAND (SM), trace gravel,
moist to very moist
Test Pit terminated approximately 7 feet below ground surface.
No caving and groundwater/seepage observed in the test pit.
Date Test Pits Excavated: November 3, 2016
Test Pits Logged by: HX
N ( blows/ft ) Approximate Consistency N (blows/ft ) Approximate
Relative Density (%) Undrained Shear
Strength (psf)
0 to 4 0 - 15 Very Soft 0 to 2 < 250
5 to 10 16 - 35 Soft 3 to 4 250 - 500
11 to 30 36 - 65 Medium Stiff 5 to 8 501 - 1000
31 to 50 66 - 85 Stiff 9 to 15 1001 - 2000
over 50 86 - 100 Very Stiff 16 to 30 2001 - 4000
Hard over 30 > 4000
CASCADE GEOTECHNW Project No. 201612 Figure A-4
KEY:
Indicates 3-inch OD Dames & Moore Sample.
Indicates 2-inch OD Split Spoon Sample (SPT).
Indicates Disturbed Sample.
Indicates No Recovery.
Indicates Bag Sample.
Indicates Shelby Tube Sample.
COMPONENT DEFINITIONS
COMPONENT SIZE RANGE
Boulders
CobblesGravel
Coarse gravel
Fine gravel
Sand
Coarse sand
Medium sand
Fine sand
Silt and Clay
Larger than 12 in
3 in to 12 in
3 in to No 4 (4.5mm )
3 in to 3/4 in
3/4 in to No 4 ( 4.5mm )No. 4 ( 4.5mm ) to No. 200 ( 0.074mm )
No. 4 ( 4.5 mm ) to No. 10 ( 2.0 mm )
No. 10 ( 2.0 mm ) to No. 40 ( 0.42 mm )
No. 40 ( 0.42 mm ) to No. 200 ( 0.074 mm )
Smaller than No. 200 ( 0.074 mm )
DESCRIPTIVE TERMS RANGE OF PROPORTION
Trace or little
Some
Clayey, silty, sandy,
gravellyAnd
1 - 5%
6 - 12%
13 - 30%
31 - 50%
COMPONENT PROPORTIONS
MOISTURE CONTENT
DRY
DAMP
MOIST
WET
Absence of moisture, dusty,
dry to the touch.Some perceptible
moisture; below optimum
No visible water; near optimum
moisture content
Visible free water, usually
soil is below water table.
RELATIVE DENSITY OR CONSISTENCY VERSUS SPT N -VALUE
COHESIONLESS SOILS COHESIVE SOILS
Density
Very Loose
Loose
Medium Dense
Dense
Very Dense
ATD: At Time of Drilling
BGS: Below Ground Surface
MAJOR DIVISION GRAPHIC LETTER TYPICAL DESCRIPTIONS
SYMBOL SYMBOL
WELL-GRADED GRAVELS, GRAVEL-
SAND MIXTURES, LITTLE OR NO FINESGW
GP
POORLY-GRADED GRAVELS,GRAVEL-SAND MIXTURES, LITTLE
OR NO FINES
GM SILTY GRAVELS, GRAVEL-SAND-
SILT MIXTURES
GC CLAYEY GRAVELS, GRAVEL-SAND-
CLAY MIXTURES
CLEAN GRAVELS
(LITTLE OR
NO FINES)
GRAVELS
WITH FINES
(APPRECIABLE
AMOUNT OF
FINES)
CLEAN SAND
(LITTLE OR NO
FINES)
SANDS WITH
FINES
(APPRECIABLE
AMOUNT OF
FINES)
SW
SP
SM
SC
WELL-GRADED SANDS, GRAVELLY
SANDS, LITTLE OR NO FINES
SILTY SANDS, SAND-SILT
MIXTURES
CLAYEY SANDS, SAND-CLAY
MIXTURES
ML
CL
OL
MH
CH
OH
PT
SILTS
AND
CLAYS
LIQUID LIMIT
LESS THAN 5O
SILTS
AND
CLAYS
LIQUID LIMIT
GREATER THAN
5O
INORGANIC SILTS AND VERY FINESANDS, ROCK FLOUR, SILTY ORCLAYEY FINE SANDS OR CLAYEYSILTS WITH SLIGHT PLASTICITY
INORGANIC CLAYS OF LOW TO MEDIUM PLASTICITY, GRAVELLYCLAYS, SANDY CLAYS, SILTYCLAYS, LEAN CLAYS
ORGANIC SILTS AND ORGANIC
SILTY CLAYS OF LOW PLASTICITY
INORGANIC SILTS, MICACEOUS OR
DIATOMACEOUS FINE SAND OR
SILTY SOILS
INORGANIC CLAYS OF HIGH
PLASTICITY, FAT CLAYS
ORGANIC CLAYS OF MEDIUM TOHIGH PLASTICITY, ORGANIC SILTS
PEAT, HUMUS, SWAMP SOILS WITH
HIGH ORGANIC CONTENTSHIGHLY ORGANIC SOILS
NOTE: DUAL SYMBOLS ARE USED TO INDICATE BORDERLINE SOIL CLASSIFICATIONS
UNIFIED SOIL CLASSIFICATION SYSTEM
GRAVEL
AND
GRAVELLY
SOILS
MORE THAN 50% OF COARSE FRACTION RETAINED ON NO. 4 SIEVE
COARSE
GRAINED
SOILS
MORE THAN
50% OF
MATERIAL
IS LARGER
THAN NO.
200 SIEVESIZE
MORE THAN 50% OF COARSE FRACTION PASSING NO. 4 SIEVE
SAND
AND
SANDY
SOILS
FINE
GRAINED
SOILS
MORE THAN
50% OF MATERIAL
IS SMALLER
THAN NO.
200 SIEVE
SIZE
POORLY-GRADED SANDS,
GRAVELLY SANDS, LITTLE
OR NO FINES
CASCADE GEOTECHNW Project No. 201614 Figure A-5