HomeMy WebLinkAbout03-21-16 PSE Talbot - Mech Permit SetMECHANICAL GENERAL NOTES
1.FOR TRANSFER DUCT DETAIL SEE DETAIL 2 SHEET M2-1. ALL TRANSFER DUCTS
SHALL BE INTERNALLY LINED.
2.DUCTWORK SHALL BE CONSTRUCTED IN ACCORDANCE WITH SECTION 23 33 00.
3.CONTRACTOR SHALL CAREFULLY COORDINATE WORK W/ ALL OTHER TRADES,
ESPECIALLY IN CEILING SPACES WHERE SPACE IS TIGHT. SHEET METAL
CONTRACTOR SHALL HAVE PRIORITY OVER OTHER MECHANICAL TRADES IN
CEILING SPACE WHERE CONFLICTS OCCUR.
4.ALL DUCTWORK SHOWN IS SCHEMATIC, CONTRACTOR SHALL PROVIDE ALL
OFFSETS/ELBOWS AS REQ'D TO ALLOW ROUTING AROUND STRUCTURE,
ELECTRICAL, & OTHER INTERFERENCES.
5.IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO COORDINATE & SELECT
FINAL LOCATIONS OF ALL AIR INLETS/OUTLETS. SHIFT AIR INLETS/ OUTLETS
FROM LOCATIONS SHOWN AS REQ'D TO AVOID CONFLICTS W/ STRUCTURE,
LIGHTS, & OTHER ITEMS. SUCH SHIFTS SHALL MAINTAIN SYMMETRY OF AIR
TERMINALS & SHALL HAVE PRIOR APPROVAL OF ARCHITECT/ENGINEER.
6.FOR SUSPENDED EQUIP. SUPPORTS, SEE DETAIL 1 SHEET M2-1.
7.UNSIZED DUCTS SHALL MATCH THE SIZE OF THE LARGEST ADJACENT DUCT
THAT IS SIZED. WHERE THE ADJACENT DUCT SIZE IS NOT SHOWN, PROVIDE THE
FOLLOWING SIZED DUCTS (OR EQUIVALENT RECTANGULAR).
8.VERIFY LOCATIONS OF ITEMS INSTALLED IN CEILINGS WITH ARCHITECTURAL
REFLECTED CEILING PLANS PRIOR TO BEGINNING WORK. NOTIFY ARCHITECT
OF DISCREPANCIES.
INLETS/OUTLETS
DUCTS TO AIRCFM OTHER
DUCT
901 - 1200
1201 - 1500
1501 - 2000
2001 - 2400
>2401
----
----
----
151 - 250
251 - 400
401 - 500
501 - 700
701 - 900
101 - 150
00 - 100
SIZE BASED ON
0.1"/100' P.D.
SIZE BASED ON
500 FPM
1.LOAD CALCULATIONS HAVE BEEN PERFORMED IN ACCORDANCE WITH WSEC
C403.2.1.
2.EQUIPMENT HAS BEEN SELECTED PER WSEC C403.2.2.
3.VENTILATION AND THE ABILITY TO REDUCE OUTSIDE AIR TO IMC MINIMUMS SHALL BE
PROVIDED PER WSEC C403.2.5.
4.MOTORS 1 HP AND LARGER SHALL BE ENERGY EFFICIENT TYPE PER WSEC C403.2.13;
MOTORS 1/12 HP TO 1 HP SHALL BE ECM TYPE OR MEET MINIMUM EFFICIENCY
REQUIREMENTS PER WSEC C403.2.10.3.
5.HEAT PUMPS SHALL INCLUDE MICROPROCESSOR CONTROLS THAT MINIMIZE
SUPPLEMENTAL HEAT USAGE DURING START-UP, SET-UP, AND DEFROST
CONDITIONS. THESE CONTROLS SHALL ANTICIPATE THE NEED FOR HEAT AND
PROVIDE COMPRESSION HEAT AS THE FIRST STAGE. PROVIDE A VISUAL INDICATION
WHEN SUPPLEMENTAL HEAT IS IN USE AND A CONTROL LOCK-OUT OF
SUPPLEMENTAL HEAT FOR OUTSIDE AIR TEMPERATURES ABOVE 40 DEG F PER
WSEC C403.2.4.1.1.
6.TEMPERATURE CONTROL SYSTEM SHALL HAVE A MINIMUM DEAD BAND OF 5
DEGREES AS REQUIRED BY WSEC C403.2.4.2.
7.HVAC SYSTEMS SHALL BE EQUIPPED WITH AUTOMATIC CONTROLS CAPABLE OF
PROVIDING NIGHT SETBACK, SEVEN DIFFERENT DAILY SCHEDULES, AND OPTIMUM
START PER THE REQUIREMENTS OF WSEC C403.2.4.3.
8.OUTSIDE AIR INTAKES, EXHAUST OUTLETS, AND RELIEF OUTLETS SHALL BE
PROVIDED WITH DAMPERS THAT COMPLY WITH WSEC C403.2.4.4. DAMPER SHALL
AUTOMATICALLY CLOSE WHEN SYSTEM OR SPACES SERVED ARE NOT IN USE OR
DURING WARM-UP, COOL-DOWN, AND SETBACK. DAMPER MAXIMUM LEAKAGE RATE
SHALL NOT EXCEED MAXIMUM ALLOWED BY WSEC C402.4.5.2.
9.ALL DUCTWORK SHALL BE CONSTRUCTED AND SEALED IN ACCORDANCE WITH IMC,
WSEC C402 AND IBC REQUIREMENTS PER WSEC C403.2.7.
10.DUCTWORK SHALL BE INSULATED TO THE APPROPRIATE R-VALUE AS REQUIRED BY
WSEC C403.2.7.
11.PROVIDE DIFFERENTIAL DRY BULB HIGH LIMIT SHUT-OFF CONTROL OF ECONOMIZER
COOLING PER TABLE C403.3.1.1.3(2).
12.ECONOMIZER DAMPERS SHALL BE CAPABLE OF BEING SEQUENCED WITH
MECHANICAL COOLING EQUIPMENT.
13.AIR SYSTEMS SHALL BE BALANCED AS REQUIRED IN SECTION C408.2.2.1 AND
C408.2.2.2 OF THE WSEC.
14.PROVIDE COMMISSIONING PLAN & REPORT REQUIREMENTS FOR PRELIMINARY AND
FINAL COMMISSIONING PER SECTION C408.1. PROVIDE SEQUENCE OF OPERATIONS
AND TEST PROCEDURES PER SECTION C408.1.2 AND SUBMIT COMPLIANCE
CHECKLIST PER SECTION C408.1.3.4 OF THE WSEC TO THE BUILDING OFFICIAL UPON
SUBSTANTIAL COMPLETION.
15.THESE "ENERGY CODE NOTES" ARE LISTED TO SATISFY THE BUILDING
DEPARTMENT'S REQUIREMENT THAT CERTAIN INFORMATION BE PLACED ON THE
PLANS, BUT DO NOT DIMINISH THE FULL PROJECT REQUIREMENTS. PROVIDE ITEMS
IN EXCESS OF CODE WHERE NOTED ON DRAWINGS AND IN SPECIFICATIONS. FOR
OTHER ADDED REQUIREMENTS, SEE SPECIFICATIONS, INCLUDING BUT NOT LIMITED
TO THE FOLLOWING:
ITEM SECTION#
AS-BUILT DOCUMENTS 20 05 00
O&M MANUALS 20 02 00
DUCT INSULATION 20 07 00
DUCTWORK SEALING & TESTING 23 31 00
CONTROLS 23 09 00
ENERGY CODE NOTES
MANUFACTURERMFR
SHEET ON WHICH SECTION IS SHOWN
SECTION IDENTIFICATION LETTER
DETAIL IDENTIFICATION NUMBER
SHEET ON WHICH DETAIL IS SHOWN
A
M3.1
M3.1
2 W/WITH
WET BULBWB
VOLTS, VOLTAGEV
TRANSFER DUCT
UNLESS NOTED OTHERWISE
TRANSFER GRILLE
TYPICAL
UNO
TD
TYP
TG
TEMP TEMPERATURE
ELBOW WITH TURNING VANES
WALL OUTLET (OR INLET)
T THERMOSTAT
SIZE,SYMBOL
SIZE,SYMBOL
CFM
CFM
CEILING INLET
FLEXIBLE CONNECTION
RATED LOAD AMPS
REVOLUTIONS PER MINUTE
REQUIREDREQ'D
RLA
RPM
PRESSURE DROP
PHASE
OUTSIDE AIROA
PH
PD
OPPOSED BLADE DAMPER
NOT TO SCALENTS
OBD
THOUSAND BTUH
MINIMUM CIRCUIT AMPS
MINIMUM
MECHANICAL
MCA
MECH
MIN
MBH
ARROW IN DIRECTION OF FLOW
DUCT SECTION (EXHAUST OR RETURN)
LINED DUCT (DIM. FOR NET FREE AREA)
DUCT (FIRST FIGURE, SIDE SHOWN)
20/12L
RISE (R) OR DROP (D)
20/12
HORSE POWERHP
EXTERNAL STATIC PRESSURE
FEET PER MINUTEFPM
ESP
ENERGY EFFICIENCY RATIOEER
EACH
DRY BULB
EA
DB
DEGREE FAHRENHEIT
DIAMETER
DEG F, F
',$
DRAWINGDWG
BUILDINGBLDG
CUBIC FEET PER MINUTECFM
CAPACITYCAP
ARCHITECTURALARCH
DESCRIPTIONSYMBOL
MECHANICAL LEGEND
DESCRIPTIONABBREV.
NOTE:SEE SYMBOL LIST & SCHEDULES FOR EXPLANATION
OF ADDITIONAL SYMBOLS & ITEM CALLOUTS.
R(D)
COMBINATION FIRE/SMOKE DAMPER
general@hultzbhu.com
Phone: (253) 383-3257
1111 Fawcett Ave Suite 100
e n g i n e e r s i n c
HULTZ
Fax: (253) 383-3283
Job Number:
Tacoma, WA 98402
BHU
15-190 HOUSE
3 21 16 0
PERMIT SET
BHM
111022315
SCALE: VARIES FILE NO:
SHEET:
REV NODRAWING NO
12345678
A
B
C
D
E
A
B
C
D
E
CADD NO:
CLASS:
DATE (M/D/Y)SUBSTATION
ENGINEERING
DEPARTMENT$DATE$$USER$CODE:
ENGINEER
REVIEWED
REVISION DESCRIPTION:
CAD
APPROVED
WO NUMBER:
OF:
CONTROL HOUSE
TALBOT SUBSTATION
31TR
D-18740BS
SIGNED
3/21/2016
3 21 16
M1-1 Mechanical Legend & Notes
23
HEAT PUMP SCHEDULE - PACKAGED TYPE
SYMBOL
SPECIFIED
MANUFACTURER AND
SERIES NO.
AREA SERVED
COOLING CAP *HEATING CAP *SUPPLEMENTARY
HEAT INDOOR FAN OUTDOOR FAN COMPRESSOR ELECTRICAL FILTERS MIN. OA
CFM
MAX
WEIGHT
LBS
REMARKS
TOTAL MBH EFFICIENCY MBH EFFICIENCY KW STAGES CFM ESP HP QTY HP (EA)QTY RLA (EA)MCA MOP VOLTS / PH TYPE MIN. SF
HP-1 BARD W48H2 CONTROL 100,
BATTERY 101 46 9.0 EER 44 3.0 COP 9 1 1550 0.2 1/2 1 1/3 1 13.6 56 60 230/3 2" PTA
MERV 8 20"X30"300 550
&22/,1*&$3$&,7<,6$5,5$7,1*$7)'%):%,1'225&2,/($7$1')287'225&2,/($7
+($7,1*&$3$&,7<,6$5,+,7(035$7,1*$7)'%,1'225($7$1')'%):%287'225&2,/($7
*** ON PLANS "A" DESIGNATES INDOOR UNIT, "B" DESIGNATES OUTDOOR UNIT. (E.G. HP-1B IS HP-1 OUTDOOR UNIT).
FAN SCHEDULE
SYMBOL
SPECIFIED
MANUFACTURER AND
SERIES NUMBER
TYPE AREA SERVED CFM ESP RPM WHEEL
DIA
ELECTRICAL
DRIVE CONTROL REMARKS
HP VOLTS / PH
EF-1 COOK TCN-B 100 TUBULAR INLINE
CENTRIFUGAL BATTERY 101 250 0.50"1490 -1/4 115/1 BELT TIME
SCHEDULE AMCA-A SPARK RESISTANT CONSTRUCTION
AIR INLET & OUTLET SCHEDULE
SYMBOL TYPE MANUFACTURER AND
SERIES NUMBER REMARKS
CEG CEILING EXHAUST
GRILLE TITUS SERIES 50F 1/2"x1/2"x1/2" CUBE CORE
CTG CEILING TRANSFER
GRILLE TITUS SERIES 50F 1/2"x1/2"x1/2" CUBE CORE
1.ALL AIR TERMINALS SHALL HAVE FACTORY FINISH, COLOR AS SELECTED BY
ARCHITECT.
2.SEE LEGEND FOR TERMINOLOGY USED IN AIR TERMINAL CALL-OUTS ON
DRAWINGS.
3.SEE ARCH. FINISH SCHEDULE FOR CEILING TYPES, PROVIDE AIR TERMINALS
TO MATCH CEILING CONSTRUCTION INSTALLED IN.
4.SEE SECTION 22 37 00 FOR SPECIFICATIONS.
AIR INLET & OUTLET SCHEDULE NOTES:
PROVIDE W/ 0 -100% OA DRY BULB ECONOMIZER
CONTROL, RETURN GRILLES, R-410A REFRIG & REMOTE
7-DAY PROGRAMMABLE THERMOSTAT.
1
1
general@hultzbhu.com
Phone: (253) 383-3257
1111 Fawcett Ave Suite 100
e n g i n e e r s i n c
HULTZ
Fax: (253) 383-3283
Job Number:
Tacoma, WA 98402
BHU
15-190 HOUSE
3 21 16 0
PERMIT SET
BHM
111022315
SCALE: VARIES FILE NO:
SHEET:
REV NODRAWING NO
12345678
A
B
C
D
E
A
B
C
D
E
CADD NO:
CLASS:
DATE (M/D/Y)SUBSTATION
ENGINEERING
DEPARTMENT$DATE$$USER$CODE:
ENGINEER
REVIEWED
REVISION DESCRIPTION:
CAD
APPROVED
WO NUMBER:
OF:
CONTROL HOUSE
TALBOT SUBSTATION
31TR
D-18740BS
SIGNED
3/21/2016
3 21 16
M1-2 Mechanical Schedules
24
MOUNTING CLIP FURNISHED W/ UNIT
NOTES:
SUSPENDED EQUIP. SUPPORT
NTS
EQUIPMENT
1.ALL SUSPENDED HVAC EQUIPMENT W/ ROTATING COMPONENTS
SHALL HAVE VIBRATION ISOLATORS AS SHOWN.
2.VIBRATION ISOLATORS SHALL BE SELECTED FOR 1" DEFLECTION.
3.SEE STRUCTURAL FOR ATTACHMENT TO STRUCTURE & OTHER ANCHORING
REQUIREMENTS.
M2-1
1
HANGER ROD TO STRUCTURE, SEE
STRUCTURAL FOR ATTACHMENT.
COMBINATION SPRING & DOUBLE
DEFLECTION TYPE VIBRATION
ISOLATOR, MASON SERIES DNHS
OR APPROVED.
TRANSFER DUCT DETAIL
M2-1
2
T
21
AA
B
2
B
1
HP-1
12x12 CEG
EF-1
1
1
M2-1
10/10
10/10L 2
M2-1
12x12 CTG
PROVIDE HEIGHT AS NEEDED
TO CLEAR ADJACENT ITEMS
MIN 6"
LINED ELBOW - SAME SIZE
AS TRANSFER DUCT
TRANSFER GRILLE FINISHED CEILING
(TYP)
SCREEN
1.CEILING TYPE & AIR INLET FRAME STYLE MAY VARY FROM THAT DEPICTED.
2.SEE PLAN FOR SIZE OF TRANSFER DUCT.
3.PROVIDE FIRE/SMOKE DAMPERS AS SHOWN ON PLANS.
NOTES:
DUCT SUPPORT
2
16/16
12x8 WSG
250 (TYP)30/10
3
CONTROL
100
BATT.
101
WALL LOUVER
SEE ARCH.
general@hultzbhu.com
Phone: (253) 383-3257
1111 Fawcett Ave Suite 100
e n g i n e e r s i n c
HULTZ
Fax: (253) 383-3283
Job Number:
Tacoma, WA 98402
BHU
15-190 HOUSE
3 21 16 0
PERMIT SET
BHM
111022315
SCALE: VARIES FILE NO:
SHEET:
REV NODRAWING NO
12345678
A
B
C
D
E
A
B
C
D
E
CADD NO:
CLASS:
DATE (M/D/Y)SUBSTATION
ENGINEERING
DEPARTMENT$DATE$$USER$CODE:
ENGINEER
REVIEWED
REVISION DESCRIPTION:
CAD
APPROVED
WO NUMBER:
OF:
CONTROL HOUSE
TALBOT SUBSTATION
31TR
D-18740BS
SIGNED
3/21/2016
3 21 16
M2-1 Mechanical Floor Plan
FLOOR PLAN - MECHANICAL
SCALE: 1/8"=1'-0"NORTHKEYED NOTES:
1
GENERAL NOTES:
1.SEE GENERAL MECHANICAL NOTES ON PREVIOUS SHEET.
2.PROVIDE TRANSITIONS AT DUCT CONNECTIONS TO ALL HVAC
EQUIPMENT & AIR INLETS/OUTLETS TO MATCH CONNECTION SIZE.
3.LOCATE FIRE/SMOKE DAMPERS TO BE ACCESSIBLE.
4.PROVIDE DUCT & BLDG ACCESS DOORS AT ALL BDD'S DAMPERS
TO ALLOW ACCESS & INSPECTION.
5.BDD'S AT LOUVERS SHALL MATCH LOUVER DIMENSIONS.
6.SEE ARCHITECTURAL PLANS FOR WALL LOUVERS. PLENUMS AT
LOUVERS SHALL BE A MINIMUM OF 12" DEEP & SHALL HAVE 2"
THICK LINING.
INTERLOCK MOTORIZED DAMPER W/ EXHAUST FAN TO BE OPEN WHEN
FAN IS ON. LOCATE TO BE ACCESSIBLE FROM CONTROL 100.
LOCATE FAN TO BE ACCESSIBLE FOR MAINTENANCE FROM CONTROL
100; COORDINATE WITH CABLE TRAY LAYOUT.
PROVIDE DIFFERENTIAL PRESSURE DEVICE WITH CONTACTS THAT
CLOSE WHEN FAN IS OPERATING. CONTACTS TO BE USED BY E.C. FOR
FAN TROUBLE ALARM THROUGH FIRE ALARM PANEL. COORDINATE
WITH E.C.
25
2
3