(E) UTILITY POLE-
CHELAN AVE NE
CATVANDPHONE 111, Tl
RVICE AERIAL CABLING
E6
+
07T4C 7
f�E3
CHELAN PL. NE
P V,
ZHEAD
&ElzkTAlc=qAlTA
(E)OVERHEAD
SERVICE - CAW
2" SCHEDULE 40 PVC
CONDUIT TO IM POLE WITH
t F4j"PyK
Ile
4 PF 'tww
FFlow
0
+
0
UFFILITY POLE Wi IF
H CATV RISER
+
V
VAULTSCHEDULE
VAULT DIMENSIONS
VAULT TYPE
MANUFACTURER
VAULT MODEL
COVER MODEL
COVER
RATING
COVER LABEL
RISERS
NOTES
(LXWXD)
Tl
OLDCASTLE
"'ILLA,
�-332P
MEDIUM DUTY:
H-20 OFF STREET
CENTURYLINK
3X2'X3'
T2
OLDCASTLE
444-LA
44-332P
MEDIUM DUTY:
H-20 OFF STREET
COMCAST
N? ��
�X
T3
OLDCASTLE
"'ILLA
44-332P
MEDIUM DUTY:
H-20 OFF STREET
WAN
3' X 2� 3
T4
OLDCASTLE
233-LA
23-2436P
MEDIUM DUTY
H-20 OFF STREET
COMMUNICATIOW
SIX ZX 3'
NOTES
1.
PROVIDE CABLE RACKING
2.-
3.-
\-@(MOF)
NEW RENTON
ELEMENTARY
SCHCOL#16
E5
L- - - J L- - - -
DUVALL AVE. NE
IN
SHEET NOTES:
1. REFER TO CIVIL, LANDSCAPE AND SURVEY DRAWINGS FOR ADDITIONAL INFORMATION.
2. COORDINATE PLACEMENT OF SITE LIGHTING, VAULTS AND RACEWAY WITH DIVISION 31, CIVIL AND DIVISION 32,
LANDSCAPE CONTRACTORS. COORDINATE WITH TREE PROTECTION PLANS AND AVOID CRITICAL ROOT ZONES OF
EXISTING TREES. CONFLICTS SHALL BE COMMUNICATED TO THE ARCHITECT FOR RESOLUTION PRIOR TO
COMMENCEMENT OF SITE WORK.
2. REFER TO LANDSCAPE SHEETS TP1.00 AND TP1.01 FOR TREE PROTECTION & REMOVAL PLANS. ELECTRICAL
EQUIPMENT, RACEWAY AND VAULTS ARE TO BE LOCATED ANDIOR ROUTED OUTSIDE OF TREE PROTECTION FENCE
BOUNDARIES.
3. INSTALLATION OF CONDUITS AND VAULTS SHALL INCLUDE BUT NOT LIMITED TO TRENCHING, BACKFILL, TAMPING
OF EARTH, DETECTABLE MARKER TAPE AND WHERE INDICATED CONCRETE ENCASEMENT.
4. CONDUITS SHALL BE ENCASED WITH CONCRETE WHERE PASSING UNDER BUILDING FOUNDATIONS AND AT
STREET/ PARKING LOT CROSSINGS. EXTEND ENCASEMENT 60" ON EACH SIDE OF CROSSING.
5. WATERTIGHT SEAL SHALL BE PROVIDED FOR EACH CONDUIT INSIDE THE VAULT AND WITHIN THE BUILDING AFTER
BACKBONE DEMARC CABLING HAS BEEN INSTALLED. SEE SPECIFICATION SECTION 271100 FOR ADDITIONAL
INFORMATION.
6. COORDINATE TELEPHONE AND OWNER WAN SERVICE ENTRANCE CONDUITS WITH SERVICE PROVIDER PRIOR TO
COMMENCING WORK. CONTACT JASON TESDAL W/ CENTURYLINK 206.345.3488 TO COORDINATE PHONE SERVICE
ENTRANCE.
7. COORDINATE CONNECTION OF STORM SEWER TO TELECOMMUNICATIONS SYSTEM VAULTS WITH CIVIL TO AVOID
WATER INFILTRATION INTO INTERIOR TELECOMMUNICATIONS ROOMS.
8. INSTALL UNDERGROUND CONDUIT PER TRENCHING DETAIL. REFER TO DETAIL 3, SHEET E7.03.
9. REFER TO VAULT SCHEDULE ON THIS SHEET FOR VAULT AND HANDHOLE TYPES.
FLAG NOTES:
PROVIDE (4) 4" SCHEDULE-40 PVC CONDUITS WITH MULE TAPE
TO THE MDF AT 36" BELOW GRADE SERVICE ENTRANCE
CONDUITS ARE AS FOLLOWS'
(1)4"CTELEPHONE
(1)4'C CATV
(1)4"C WAN
(1)4'C SPARE
PROVIDE 10'.0" GALVANIZED RIGID STEEL SERVICE ENTRANCE
RISER CONDUITS ON (E) UTILITY POLE WITH STANDOFF
BRACKETS AND CAP. SERVICE ENTRANCE CONDUITS ARE AS
FOLLOWS:
(1)4"C TELEPHONE
(1)4"C CATV
(1)4'C WAN
(1)4"C SPARE
D�> PROVIDE THE FOLLOWING SCHEDULE 40 PVC CONDUITS WITH
MULE TAPE AT 36" BELOW GRADE
(1)4"C TELECOMMUN ICATIONS W/ (3) 1" IN NERDUCTS
(1)4"C INTERCOM I CLOCK
(1)4"C SECURITY
(1)4"C SPARE
PROVIDE PENCELL PEM-12-12-PC GRADE LEVEL BURIED
HANDHOLE WITH MINIMUM 6"GRAVEL BASE. INSTALL PER
MANUFACTURER RECOMMENDATIONS.
PROVIDE THE FOLLOWING SCHEDULE 40 PVC CONDUITS WITH
MULE TAPE AT 36" BELOW GRADE:
(2)2"C TELECOMMUN ICATIONS
FROM DIE THE FOLLOWING SCHEDULE 40 PVC CONDUITS WITH
MULE TAPE AT 36" BELOW GRADE:
(1)2"C TELECOMMUN ICATIONS
PROVIDE (1)1-C TO LIGHT POLE FOR FUTURE IF CAMERA.
COORDINATE LIGHT POLE TYPE AND LOCATION WITH
ELECTRICAL DRAWINGS.
I I �111� wn 'm
i lmlwl� 1" 40'-0" H OL lqaVlwl
VR
VR DATUM
�01
VR IF NCYF � 1�
NO, REVISION BY DATE APPR vP�D .�
T-41921 0
—9
7
IN
0)
00
N
,It
c:)
IN COMPLIANCE WITH CITY OF RENTON STANDARDS
cl)
z
w
2
:D
ILL 0
0
CITY OF NEW ELEMENTARY NO. 16 0
PENTON CHELAN AVE NE
RENTON, WA 98059
Planning/Building/Public Works Dept. TELECOM SITE PLAN