Utility Specifications
Water Utility Notes and Specifications
THESE NOTES SHALL APPEAR ON PROJECTS FOR THE WATER UTILITY.
1. All work material shall be in conformance with the standards and specifications of the
City of Renton Planning/ Building/ Public Works Department and the latest edition of the
WSDOT/ APWA Standards and Specifications, as approved and modified by the City of
Renton in the Renton Standard Plans & Specifications. A set of approved plans shall be
kept on site at all times during construction.
2. The hours of work in the street right of way shall be limited to 8:30 AM to 3:30 PM
on
weekdays unless otherwise approved in writing by the Public Works Department at
425) 430-7301. The Police Department, Fire Department, and 911 shall be notified 24
hours in advance of any work in the right of way.
3. All locations of existing utilities shown are approximate and it shall be the contractor's
responsibility to verify the true and correct location so as to avoid damage or
disturbance. For utility locates call 48-hour locators 800-424-5555.
4. An approved Traffic Control Plan is required to be submitted at the Pre -Construction
meeting.
5. Datum for Vertical Control shall be North American Vertical Datum 1988 Meters, and
for
Horizontal Control shall be North American Datum 1983/1991 Meters unless otherwise
approved by the City of Renton Public Works Department. Reference benchmark and
elevations are noted on the plans.
6. All watermain pipe is to be cement lined ductile iron pipe conforming to AWWA C110
and C111 or latest revision, thickness Class 52. Cement mortar lining and seal coating
shall conform to AWWA C104 or latest revision. Pipe joints to be push -on or mechanical
joint. Bedding to be Class C. All ductile iron pipe and fittings shall be polyethylene
wrapped per ANSI/AWWA C105/ A21.5-93 Standards.
7. Cast iron and ductile iron fittings shall be cement lined, pressure rated as noted on
plans, and in accordance with ANSI/AWWA C110/ A21.10-87. Cement lining shall be in
accordance with ANSI/AWWA C104/ 421/ 4-90. If fittings are 3 to 12 inches in diameter
and have mechanical joints, the fittings shall in accordance with either ANSI/AWWA
C110-A21.10-87 or ANSI/AWWA C153/ A21.53-94. Three ( 3) inch to 12 inch diameter
fittings, which have mechanical joints and/ or flanged joints, shall be in accordance with
ANSI/AWWA C110/A21.10.87 or a combination of ANSI/AWWA C110/A21.10.87 and
ANSI/AWWA C153/ A21.53-94 such that the portion of the fitting with a mechanical
joint(s) may be with ANSI/AWWA C153/ A21.53-94 and that portion of the fitting with
flanged joint(s) shall be in accordance with AWWA C110/A21.10-87. Acceptance testing
in accordance with section 53.53 of ANSI/AWWA section 10-4.3 of ANSI/AWWA
C110/ A21.10-87 shall be obtained by the contractor and transmitted to the owner.
8. Gate valves shall be iron body, bronzed -mounted, double disc with bronze wedging
device and 0-ring stuffing box (AWWA C500) or of resilient seated type (AWWA C509).
Valves shall be designed for a minimum water operating pressure of 200 psi. Gate
valves shall be Clow List 14, Mueller Company NO. A2380 or M & H.
9. Fire hydrants shall be Corey type (opening with the pressure) or compression type
opening against pressure) conforming to AWWA C-502-85 with a 6 inch mechanical
joint inlet and a main valve opening ( M.V.O.) of 5-1/4 inch, two 2-1/2 inch hose
nozzles
with National Standard Threads 7-1/2 threads per inch and one 4 inch pumper nozzle
with the new Seattle Pattern 6 threads per inch, 60 degrees V. Threads: outside
diameter of male thread 4.875 and root diameter 4.6263. Hydrants shall have a 1-1/4
inch pentagon operating nut opened by turning counter clockwise ( left).
10. The two 2-1/2 inch hose nozzles shall be fitted with cast iron threaded caps with
operating nut of the same design and proportions as the hydrant stem nut. Caps shall
be fitted with suitable neoprene gaskets for positive water tightness under test
pressures.
11. The 4 inch pumper nozzle shall be fitted with a Storz adapter, 4 inch Seattle Thread
x 5
inch Storz. Storz adapter shall be forged and/ or extruded 6061-T6 aluminum alloy,
hardcoat anodized. Threaded end portion shall have no lugs and two set screws 180
degrees apart. Storz face to be metal, no gasket to weather. Storz cap to have
synthetic molded rubber gasket, and shall be attached to hydrant adapter with 1 /8 inch,
coated, stainless steel, aircraft cable.
12. Fire hydrants shall be painted with two coats of paint. Preservative paint number 43-
655 safety yellow or approved equal.
13. Pumper connection to face roadway assembly.
14. Fire hydrants shall be installed per City of Renton Standard Detail for fire hydrants,
latest revision.
�1
Abbey Road Group
Land Development
Services Company, LLC
2102 E MAIN AVE, SUITE 109
PUYALLUP, WA 98372
P.O. Box 1224, Puyallup, WA 98371
(253) 435-3699, Fax (253) 446-3159
A PORTION OF THE NW 1/4 OF THE NE 1/4 OF SECTION 08,
TOWNSHIP 23 NORTH, RANGE 05 EAST, WILLAMETTE MERIDIAN
CITY OF RENTON, COUNTY OF KING, STATE OF WASHINGTON
WATER NOTES & DETAILS
15. All watermains 10 inches and smaller to maintain a minimum cover of 36 inches
below
finish grade. All watermain 12 inches and larger shall be at a minimum of 48 inches
below finish grade. Where utility conflicts occur, watermains are to be lowered to clear.
16. All watermains 6 inches and larger in diameter shall be cleaned with pipe cleaning
PIGS"prior to disinfection. The "Poly pigs"shall be Girard Industries Aqua Swab -AS or
approved equal, 2 lb/cu. ft. density foam with 90A durometer urethane rubber coating
on the rear of `PIG"only.
17. "PIGS"shall be cylinder shaped with bullet nose or square end. The contractor will
perform the cleaning operation.
18. All watermains and services shall be pressure tested to a minimum of 200 psi or
150 psi
over operating pressure, in accordance with the specifications of the City of Renton and
the Washington State Health Department. All pressure testing shall be done in the
presence of a representative of the City of Renton. The quantity of water lost from the
main shall not exceed the number of gallons per hour as listed in City of Renton
Standard Plans & Specifications 7-11.3(11). The loss in pressure shall not exceed 5 psi
during the 2 hour test period.
19. All watermains and services shall be disinfected by the injection of a 50 ppm
(minimum
concentration) chlorine/water solution. Dry Calcium Hypochlorite shall NOT be placed in
the pipe as laid. Chlorine shall be metered/ injected in accordance with Section 7-
11.3(12)E or 7-11.3(12)F of the Standard Specifications referenced above.
20. A pre -construction conference is required prior to any construction. A minimum of
five
5) working days notice is required for scheduling.
21. Twenty-four (24) hours notice will be required prior to starting new construction.
22. It shall be the contractor's responsibility to secure all necessary permits prior to
starting
construction.
23. Installation of corporate stops, water services, lines and meters shall not be done
until
all service agreements, meter applications, construction permits, and payment of fees
have been made to the City of Renton.
24. All connection to existing mains is to be accomplished by the City of Renton, except
wet
taps, which may be made by approved wet tap contractors with prior approval from the
Public Works Department. All necessary excavation and materials are to be supplied by
the contractor and be on -site prior to City notifications.
25. Inspection will be accomplished by a representative of the City of Renton. It shall be
the contractor's responsibility to notify Development Services twenty four (24) hours in
advance of backfilling all construction. The contractor, as well as the engineers, shall
keep as -built drawings.
26. Contractor to provide plugs and temporary blow -off assemblies for testing and purity
acceptance prior to final tie-in.
27. All joint restraint systems ( shackle rods, nuts, bolts, etc.) shall be as manufactured
by
the Star Manufacturing Company of Columbus Ohio, or equal, approved in writing by the
Public Works Department.
28. Asphalt and concrete street paving shall be sawcut to a minimum depth of two (2)
inches. Oil mat streets may be spade cut. All surface concrete, pavement, sidewalks,
curb, gutters, and driveway approaches shall be sawcut to a minimum depth of two (2)
inches or removed to an existing expansion joint.
29. A temporary cold mix asphalt patch shall be placed on the day of initial excavation
with
a permanent, sealed patch to be placed, to City of Renton policy, within 10 days. Call
for subgrade inspection prior to placement of final patch.
30. For City projects such as telemetry conduit, the PVC pipe used shall be All chemical
process lines shall be schedule 80 PVC pipe. Schedule 40 in unimproved areas and
schedule 80 PVC pipe under improved areas.
IS
VA-''
V,
11/24/2021
ITY OF RENTON REDLINES 3.18.21
ITY OF RENTON REDLINES 5.24.21
ITY OF RENTON REDLINES 7.21.21
N0. 1 REVISION
HJ 4/16/2021 IGH
HJ 5/27/2021 JGH
HJ 17/27/2021 IGH
SURVEYED:
L. WALKER
DESIGNED:
J. BROWN
DRAWN:
H. JASTRZEMBSKI
CHECKED:
J. BROWN
APPROVED:
G. HULSMANN
13"x24" PLASTIC METER BOX EQUAL TO MID -STATES
INC. BCF SERIES MSBCF 1324-18 WITH 1.75" THICK C
IRON DIAMOND PLATE COVER EQUAL TO MID -STATES
INC. MSCBC-1324-R WITH READER LID AND 2 DRILLE
FOR TOUCHREAD PIT LID (SEE DETAIL A -A) -
9" MIN
FINISH GRADE 12" MA.
z
0
36" MIN COVER M c)
22-1/2'
'IEW DUCTILE
IRON
WATERMAIN
WATER PLAN GENERAL NOTES Standard Plan No. 300
1. ALL WORK AND MATERIALS SHALL BE IN ACCORDANCE WITH TH E LATEST EDITION OF THE CITY OF RENTON PUBLIC WORKS
STANDARD SPECIFICATIONS AND SPECIAL PROVISIONS AND WSDOT / APWA STANDARD SPECIFICATIONS, LATEST EDITION AS
AMENDED BY THE CITY OF RENTON. A SET OF CITY APPROVED PLANS SHALL BE KEPT AT THE JOB SITE WHENEVER CONSTRUCTION
IS IN PROGRESS. A PRE -CONSTRUCTION CONFERENCE SHALL BE HELD PRIOR TO THE START OF CONSTRUCTION. THE CONTRACTOR
AND OR DEVELOPER SHALL BE RESPONSIBLE FOR SECURING ALL NECESSARY PERMITS PRIOR TO CONSTRUCTION.
2. ALL EXISTING UTILITIES SHALL REMAIN IN SERVICE DURING CONSTRUCTION UNLESS OTHERWISE NOTED. THE CONTRACTOR SHALL
CALL 1-800-424-5555 TO VERIFY UTILITY LOCATIONS BEFORE BEGINNING EXCAVATION.
3. ALL MATERIALS USED FOR THE CONSTRUCTION OF WATER SYSTEM IMPROVEMENTS SHALL BE NEW AND UNDAMAGED, AND
"CATALOG CUTS" FOR ALL MATERIALS SHALL BE APPROVED IN WRITING BY THE CITY OF RENTON PRIOR TO BRINGING ANY
MATERIALS ON -SITE.
4. ALL WATER MAIN PIPE MATERIALS SHALL BE CEMENT LINED DUCTILE IRON PIPE, THICKNESS CLASS 52 PER AWWA C 151 AND C
104. PIPE JOINTS SHALL BE PUSH -ON OR MECHANICAL JOINT. CAST IRON OR DUCTILE IRON PIPE FITTINGS SHALL BE CLASS 250 AS
PER ANSI/AWWA C110/A21.10-82. ALL DUCTILE IRON PIPE AND FITTINGS SHALL BE WRAPPED WITH 8-MIL BLACK, TUBE -TYPE,
POLYETHYLENE PLASTIC PER AWWA C105 STANDARDS.
5. MINIMUM COVER FROM TOP OF WATER MAINS TO FINISHED GRADE SHALL BE 36 INCHES FOR PIPE DIAMETER OF 10-INCH OR LESS
AND 48 INCHES FOR PIPE DIAMETER OF 12-INCH AND LARGER. MAXIMUM COVER FOR ALL WATER MAINS SHALL BE 60INCHES.
ANY DEVIATIONS MUST BE APPROVED BY THE CITY OF RENTON PRIOR TO CONSTRUCTION. WHERE UTILITY CONFUCrS OCCUR,
THE PROFILE OF THE WATER MAIN SHALL BE ADJUSTED AS NECESSARY TO CLEAR CONFLICTS AND TO PROVIDE MINIMUM COVER.
PIPE DEFLECTION SHALL NOT EXCEED ONE-HALF OF PIPE MANUFACTURER'S SPECIFICATION FOR SIZE OF PIPE USED. ALL TRENCH
BACKFILL SHALL BE COMPACTED TO 95 PERCENT MAXIMUM DRY DENSITY AS DETERMINED BY THE MODIFIED PROCTOR TEST
METHOD (Moo) IN ROADWAYS, ROADWAY SHOULDERS, ROADWAY PRISM AND DRIVEWAYS, AND 85 PERCENT MDD IN UNPAVED
AREAS. ALL PIPE ZONE COMPACTION SHALL BE 95 MDD.
6. CONCRETE BLOCKING FOR WATER MAINS SHALL BE DESIGNED, INSTALLED AND POURED IN PLACE IN ACCORDANCE WITH CITY OF
RENTON STANDARD DETAILS AND SPECIFICATIONS AND SHALL BE INSTALLED AT ALL VERTICAL AND HORIZONTAL BENDS, FITTINGS
AND BASE OF HYDRANTS. MEGA -LUGS (OR SIMILAR PRODUCT) MAYBE REQUIRED ON ALL MECHANICAL JOINTS IN ADDITION TO
CONCRETE BLOCKING,
7. ALL NEW WATER MAIN PIPES AND FITTINGS SHALL HAVE A FOAM PIPE PIG RUN THROUGH THEM PRIOR TO BEING FLUSHED,
DISINFECTED, AND TESTED. CLEANING, PRESSURE AND PURITY TESTING SHALL BE DONE IN THE PRESENCE OF AND UNDER THE
SUPERVISION OF A CITY OF RENTON UTILITY INSPECTOR. THE CONTRACTOR SHALL SUPPLY, INSTALL AND REMOVE PLUGS,
CORPORATION STOPS, BLOW -OFF ASSEMBLIES, AND THRUST RESTRAINT / BLOCKING FOR TESTING AND PURITY ACCEPTANCE. NO
CONNECTION SHALL BE MADE BETWEEN THE NEW MAIN OR BETWEEN THE NEW WET -TAP VALVE TO AN EXISTING MAIN UNTIL
THE NEW PIPING HAS BEEN FOAM -PIGGED, DISINFECTED, FLUSHED, AND PASSED BOTH PRESSURE AND PURITY TESTING.
8. NEW WATER MAINS INCLUDING SERVICE LATERALS SHALL BE TESTED AT A STATIC PRESSURE OF 150 PSI ABOVE WORKING
PRESSURE WITH A MINIMUM OF 225 PSI TEST PRESSURE FOR 120 MINUTES WITH A MAXIMUM OF 5 PSI PRESSURE DROP DURING
THE ENTIRE TEST PERIOD. UPON SATISFACTORY COMPLETION OF THE PRESSURE TEST, THE LINE SHALL BE DISINFECTED, FLUSHED,
AND THEN WATER SAMPLES SHALL BE TAKEN FOR PURITY TESTING BY THE PUBLIC WORKS INSPECTOR.
9. THE CONTRACTOR SHALL NOTIFY THE CITY OF RENTON WATER UTILITY AND MAINTENANCE DEPARTMENTS AT LEAST 10 WORKING
DAYS PRIOR TO MAKING CONNECTIONS TO THE EXISTING WATER SYSTEM. THE CONTRACTOR SHALL EXPOSE THE EXISTING WATER
MAIN AND FITTINGS AT THE CONNECTION POINT BEFORE ORDERING THE NECESSARY ADAPTORS AND FITTINGS REQUIRED FOR
THE FINAL CONNECTION. THE CONTRACTOR SHALL EXCAVATE, REMOVE ALL SURFACE MATERIALS, AND PROVIDE SHORING AND
ALL MATERIALS REQUIRED FOR THE CITY OF RENTON TO PERFORM THE CONNECTION TO THE EXISTING WATER SYSTEM. THE
CONTRACTOR SHALL PROVIDE AND INSTALL BACKFILL, CONCRETE BLOCKING, AND COMPLETE SURFACE RESTORATION.
PUBLIC WORKS STD. PLAN - 300.0
� �'•` � DEPARTMENT WATER PLAN GENERAL NOTES
MARCH 2O10
8
CITY PRIVATE
PIPING PIPING
7I IN UNIMPROVED RIGHT OF ?
WAY INSTALL METER BOX AT
IF SERVICE LINE TO HOUSE IS 3/4" OR 1"
TO BE INSTALLED IN THE FUTURE GALVANIZED
INSTALL FORD C14-33 OR 44 "PT
PLUG
x COMPRESSION COUPLING
� PROPERTY LINE WITH 12"
�
w LONG COPPER TAILPIECE.
w
aI SIDEWALK
a
J
TOUCHREAD WATER
METER TO BE
12
SUPPLIED BY THE
CITY
I
z Q �
� g>
TYPE "K"
COPPER
SOFT
TUBING
o �'
L-LOOP DOWN TO CENTERLINE
OF WATER MAIN TO
PROVIDE SLACK IN COPPER COPPERSETTER FOR 5/B%3/4" METER: FORD
SERVICE LINE TO METER. VBH72-15W-44-33G, OR McDONALD BRASS: 21-215W00033, OR
MUELLER: 3/4-B-2470-2 WITH ANGLE BALL VALVE ON INLET AND
SINGLE CHECK VALVE ON OUTLET
CORPORATION STOP WITH BALL VALVE. FORD COPPERSETTER FOR 1" METER: FORD VSH72-15W-44-44G, OR
TAPERED THREAD (CC). QUICK JOINT McDONALD BRASS: 21-415WC0044, OR MUELLER: 1-3-2470-2
(3/4" FB1000-3-0) OR AY MCDONALD 4701B BOTH INLET AND OUTLET WITH QUICK JOINT. PADLOCK WINGS ON
(1" F81000-4-Q) OR AY MCDONALD 4701B INLET ANGLE BALL VALVE AND SINGLE CHECK VALVE ON OUTLET.
ALL FITTINGS SHALL BE WITH QUICK JOINT.
NOTE:
ALL METER BOXES INSTALLED WITHIN CONCRETE OR PAVED DRIVEWAYS SHALL BE
CAST-IRON EQUAL TO OLYMPIC FOUNDARY, EXPANSION JOINTS MUSH BE INSTALLED ON
BOTH SIDES OF METER BOX.
A- A DRILL 2" DIA. HOLE FOR AMR (AUTOMATIC
METER READ) TOUCHREAD DEVICE
-7
2-1/2" MIN. FROM NEAREST
AND FRONT EDGE OF PIT LID
��
TYPICAL
RIB
NOTE:
THE CENTER OF THE HOLE MUST BE AT LEAST 1" FROM
UNDERNEATH RIBS UNLESS THE RIB SPACING ALLOWS THE
NUT TO TIGHTEN AGAINST THE OPEN SIDE OF MORE THAN
ONE RIB.
� PUBLIC WORKS
34" AND 1" WATER SERVICE STD. PLAN - 320.1
DEPARTMENT
NOVEMBER 2009
SCALE:
ONE INCH
AT FULL SCALE
IF NOT ONE INCH
SCALE ACCORDINGLY
VERTICAL: NAVD 1988
HORIZONTAL: NAD 1983/1991
DATUM
,� CITY OF
RENTON
•
Planning/Building/Public Works Dept.
INSIDE HOUSE
PREFERRED CONFIGURATION
�yJ 5
2
3 10 8 10 4 2
FLU
THE CONTRACTOR SHALL VERIFY THE LOCATION
OF ALL EXISTING UTILITIES PRIOR TO ANY
CONSTRUCTION. AGENCIES INVOLVED SHALL BE
NOTIFIED WITHIN A REASONABLE TIME PRIOR TO
THE START OF CONSTRUCTION.
CALL BEFORE YOU DIG (811)
WWW.WASH I NGTON811.COM
ADJACENT TO WATER METER
PROPERTY
LINE
SAWDUST
5
6 9 5
FILL
24" MIN
7
7
7
6„
FROM
6••
PEA TYRAV L
WATER
METER
1 10
3 10 8 10 4
O2
FLOW
2
OUTSIDE FOUNDATION
5 fi 9 5 SAWDUST FILL
24" MIN. "
6"
6- PEA( T,PAVEL
2 10 3 10 B 10 4 2
FLOW
FOR 3/4" AND 1" SERVICE (3/4" SHOWN)
#
ITEM
AMT
1
90' GALVANIZED STEEL ELBOW
4 EA.
2
3/4" PACKING JOINT COUPLING W/MALE IRON PIPE
2 EA.
THREAD FOR COPPER PIPE SERVICE: FORD C84-33 OR
EQUIVALENT FOR GALVANIZED PIPE SERVICE:FORD C85- 33
OR EQUIVALENT
3
PRESSURE REDUCING VALVE W/STRAINER - 3/4"
1 EA.
WITH UNION COUPLINGS AT INLET AND OUTLET,
WILKINS 600 SERIES OR EQUAL (WITH INTERNAL BYPASS
AND STRAINER)
4
3/4" CLOSE UNION - BRASS (M X F)
1 EA.
5
3/4" BRASS VALVE
VARIABLE
6
12" STANDARD METER BOX W/SOLID COVER
1 EA.
CONCRETE: 17 1/4 X 28 5/8 INSIDE DIMENSIONS, EQUAL TO
FOG TITE METER SEAL CO. +2 PLASTIC: 13 X 24 J INSIDE
DIMENSIONS, EQUAL TO BROOKS METER BOX
7
3/4" GALVANIZED STEEL PIPE, THREADED, LENGTH AS
VARIABLE
REQUIRED
8
3/4" X 1/4" X 3/4" STD. BRASS TEE
1 EA.
9
1/4" PETCOCK (M X F)
1 EA,
10
3/4" BRASS NIPPLE
VARIABLE
FUNCTION
THE FUNCTION OF A PRESSURE REDUCING VALVE IS TO REDUCE
HIGH-WATER PRESSURES IN THE SERVICE CONNECTION TO AN
ACCEPTABLE RANGE OF 55 TO 75 PSI INSTALLATION OF A
PRESSURE REDUCING VALVE IS REQUIRED WHERE THE SERVICE
CONNECTION PRESSURE EXCEEDS 80 POUNDS PER SQUARE INCH
IN ACCORDANCE TO THE UNIFORM PLUMBING CODE.
INSTALLATION
THE PRESSURE REDUCING VALVE SHALL BE LOCATED ON
THE CUSTOMER'S PROPERTY "DOWNSTREAM" OF THE
METER BOX. RESPONSIBILITY FOR PROPER INSTALLATION,
OPERATION, AND MAINTENANCE OF THE VALVE SHALL BE
ASSUMED BY THE CUSTOMER. THREE POSSIBLE
CONFIGURATIONS FOR INSTALLATION OF THE VALVE ARE
SHOWN ABOVE. A BUILDING DEPARTMENT PLUMBING
PERMIT IS REQUIRED PRIOR TO INSTALLATION
�Y PUBLIC WORKS 3/4" & 1" INDIVIDUAL PRESSURE REDUCING STD. PLAN - 340.5
` DEPARTMENT VALVE ASSEMBLY
MARCH 2O10
W-417204
IN COMPLIANCE WITH CITY OF RENTON STANDARDS