HomeMy WebLinkAbout402.1 DocuSign Envelope ID:345B681 D-914F-4F2D-AB59-7C192D3B78A3 Meg 60" MIN. USE ROMAC COUPLING OR APPROVED ,•`••:� EQUAL WHEN CONNECTING TO AN EXISTING SEWER MAIN , • l+s!'r.•.v • t U I '' '• '�j�i'i''i i''i ''i i�i'i i'i'�' BACKFILLWITH COF TOOSPRINGLINE • ,., 7 '':.••.:y. •' •_!:, i4�i'�'i, ;= a.-:•. CONCRETE BLOCKING NOTES: 1. OUTSIDE DROPS SHALL BE INSTALLED ONLY WHERE APPROVED BY THE CITY. 2. MANHOLE SHALL CONFORM TO ALL APPLICABLE REQUIREMENTS OF STANDARD PLAN 400.1. 3. OUTSIDE DROP SHALL BE THE SAME DIAMETER AS THE EXISTING SEWER MAIN • 4. NEW DROPS THAT CONNECT TO ALL EXISTING SEWER MAIN LINE MATERIALS EXCEPT DUCTILE IRON SHALL BE PVC SDR 35. DROPS CONNECTING TO DUCTILE IRON SHALL BE AWWA C900 PIPE WITH AWWA C907 FITTINGS. 5. DROP TEE SHALL BE A MINIMUM OF 3 FEET BELOW THE CONE SECTION. 6. MANHOLE SHALL BE CORE—DRILLED FOR NEW DROP. USE KOR—N—SEAL CONNECTORS OR APPROVED EQUAL. 7. CHANNEL BASE WITH 3000 PSI CONCRETE. WIDTH AND DEPTH OF CHANNEL SHALL MATCH THE LARGEST DIAMETER PIPE. SLOPE SHELF TO CHANNEL AT 1—INCH PER FOOT MIN. 8. USE ROMAC COUPLING OR EQUAL WHEN CONNECTING TO AN EXISTING SEWER MAIN. 9. MANHOLE CONE SECTION AND ACCESS LADDER MAY NEED TO BE RELOCATED TO ALLOW DROP. STD.PLAN-402.1 PUBLIC WORKS OUTSIDE DROP CONNECTION ' AP y,K��f DEPARTMENT FOR SANITARY MANHOLE Martin Pastucha 10/26/2020 \--..13,0004 FD988449D... GATE